DMP 711 Zone Expander Module Installation Guide
- June 6, 2024
- DMP
Table of Contents
DMP 711 Zone Expander Module
GET STARTED
Zone expander modules allow you to increase the number of reporting zones
available on DMP panels. Refer to the panel installation guide for more
information about zone expansion modules and the maximum number allowed per
panel. The modules connect to the panel 4-wire Keypad Bus or LX-Bus™ and are
set to an address that determines the reporting zone number. The 711 provides
one Type A Class B zone.
The 711 housing mounts to any flat surface using the mounting holes provided
in the base. Snap on the cover to complete the installation.
What’s Included
- 711 Expander Module
- 1k Ohm Resistor
Compatibility
XT30/XT50 and XR150/XR550 Series Panels
PCB Layout
INSTALLATION
Address the Module
The 711 Zone Expander uses two rotary switches identified as TENS and ONES
to set the module address. See LX-Bus Zone Numbers below for LX-Bus addresses
and set the switches to match the last two digits of the address. For example,
for address 502 on an XR550 Series panel set the TENS switch to zero and the
ONES switch to two.
Keypad Bus Zone Numbers
The 711 module uses zone 1 only. The last three zone numbers cannot be used
for other devices. For example, turn the 711 switches to address 02 (TENS = 0,
ONES = 2) to set the module zone number to zone 21. Zones 22, 23, and 24
cannot be used.
KEYPAD ADDRESS
| SWITCHES| | ZONE NUMBER|
---|---|---|---|---
TENS| ONES| XT30/50| XR150| XR550
1| 0| 1| 11| 11| 11
2| 0| 2| 21| 21| 21
3| 0| 3| 31| 31| 31
4| 0| 4| 41| 41| 41
5| 0| 5| 51| 51| 51
6| 0| 6| 61| 61| 61
7| 0| 7| 71| 71| 71
8| 0| 8| 81| 81| 81
9| 0| 9| N/A| N/A| 91
10| 1| 0| N/A| N/A| 101
11| 1| 1| N/A| N/A| 111
12| 1| 2| N/A| N/A| 121
13| 1| 3| N/A| N/A| 131
14| 1| 4| N/A| N/A| 141
15| 1| 5| N/A| N/A| 151
16| 1| 6| N/A| N/A| 161
LX-Bus Zone Numbers
Refer to Table 1 for a partial list of XR550 Series panel LX-Bus zone numbers. XR150 Series panels only use LX-Bus 1 (LX500).
LX-BUS ADDRESS
|
LX-BUS NUMBER
| SWITCHES|
ZONE NUMBER
---|---|---|---
TENS| ONES
501| 1 (LX500)| 0| 1| 501
506| 1 (LX500)| 0| 6| 506
623| 2 (LX600)| 2| 3| 623
654| 2 (LX600)| 5| 4| 654
742| 3 (LX700)| 4| 2| 742
768| 3 (LX700)| 6| 8| 768
833| 4 (LX800)| 3| 3| 833
877| 4 (LX800)| 7| 7| 877
919| 5 (LX900)| 1| 9| 919
994| 5 (LX900)| 9| 4| 994
Install the Module
Wiring the 711 Module
Connect the Red, Green, Yellow, and Black wires from the panel Keypad Bus
or LX-Bus™ to the matching terminals or harness wires on the zone expander.
Caution: Do not use looped wire under terminals. Break wire run to
provide supervision of connections.
Wiring Specifications for Keypad and LX-Bus
DMP recommends using 18 or 22 gauge unshielded wire for all keypad and LX-Bus
circuits. Do not use twisted pair or shielded wire for LX-Bus and Keypad Bus
data circuits. To maintain auxiliary power integrity when using 22-gauge wire
do not exceed 500 feet. When using 18-gauge wire do not exceed 1,000 feet.
Install an additional power supply to increase the wire length or add devices.
Maximum distance for any one circuit (length of wire) is 2,500 feet despite
the wire gauge or number of branches. Increased wire distance from the panel
decreases DC voltage on the wire. Maximum number of devices per 2,500 feet
circuit is 40.
Note: Each panel allows a specific number of supervised keypads. Add additional keypads in the unsupervised mode. Refer to the panel installation guide for the specific number of supervised keypads allowed.
Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC. If the voltage at any device is less than the required level, add an auxiliary power supply at the end of the circuit. When voltage is too low, the devices cannot operate properly. Refer to the panel installation guide and LX-Bus/Keypad Bus Wiring Application Note (LT-2031). Also see the 710 Module Installation Sheet (LT-0310) for more information.
Protection Zone Supervised 5 V, Class B, Style A
- Max Impedance : 100 Ω
- Ground Fault Detected: < 1200 Ω
- Normal Operating Range: 650 Ω to 1200 Ω
Program the Module
You can program the zone expander module zone with any panel Burglary or Fire zone type or as an Arming type zone when used with keyswitches.
Zone Expander Data LED
The zone expander LED flashes each time the module responds to a poll from the
panel. If there is a problem with the panel, panel programming, or the green
data wire between the panel and the zone expander module, the LED stops
flashing and “System Trouble” appears in the keypad display.
COMPLIANCE INFORMATION
UL
To comply with ANSI/UL 365 Police-Connected Burglary System or ANSI/UL 609
Local Burglary Alarm Systems, the module must be mounted in a listed enclosure
with a tamper installed. The keypad and LX-Bus are rated Class B, Style 3.5.
ULC Commercial Burglary
XR100/XR500 & XR150/XR350/XR550 Series panels Place the 711 and other zone
expander modules in a listed enclosure and connect a DMP Model 307 Clip-on
Tamper Switch to the enclosure programmed as a 24-Hour zone. The 711 zone can
only be used in Low Risk applications. Medium or High Risk applications must
use panel zone inputs.
SPECIFICATIONS
- Operating Voltage Operating Current: 8.8 to 15.0 VDC
- Standby : 11 mA (+ 1.6 mA per active zone)
- Alarm: 11 mA (+ 2 mA per active zone)
- Zone Voltage: 5 VDC, max 2 mA
- EOL Value: 1k Ohm
- Dimensions: 1.25 W x 2.75 H in. 3.18 W x 6.99 H cm.
- Wire Specification: Accepts 12 to 22 AWG wire
CERTIFICATIONS
- California State Fire Marshal (CSFM)
- New York City (FDNY COA #6167)
- Commercial Burglar and Fire Accessory Zone Expander
- Signaling Device
Underwriters Laboratory (UL) Listed
- ANSI/UL 365 Police Station Connect Burglar Alarm Systems
- ANSI/UL 609 Local Burglar Alarm Units & Systems
- ANSI/UL 864 Fire Protective Signaling Systems
- ANSI/UL 985 Household Fire Warning System Units
- ANSI/UL 1023 Household Burglar Alarm System Units
- ANSI/UL 1076 Proprietary Burglar Alarm Units & Systems
- ANSI/UL 1610 Central Station Burglar Alarm Units
- ANSI/UL 1635 Digital Alarm Communication System Units
- ULC Subject-C1023 Household Burglar
- ULC/ORD-C1076 Proprietary Burglar
- ULC S304 Central Station Burglar
- ULC S545 Household Fire
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>