Carrier 40MBFQ Floor Console Ductless System Owner’s Manual

June 6, 2024
Carrier

Carrier Logo

Carrier 40MBFQ Floor Console Ductless System

Carrier 40MBFQ Floor
Console Ductless System

NOTE TO EQUIPMENT OWNER:
Please read this Owner’s Information Manual carefully before installing and using this appliance and keep this manual for future reference.
For your convenience, please record the model and serial numbers of your new equipment in the spaces provided. This information, along with the installation data and dealer contact information, will be helpful should your system require maintenance or service.

A NOTE ABOUT SAFETY
Any time you see this symbol in manuals, instructions and on the unit, be aware of the potential for personal injury. There are 3 levels of precaution:

  1. DANGER identifies the most serious hazards which will result in severe personal injury or death.
  2. WARNING signifies hazards that could result in personal injury or death.
  3. CAUTION is used to identify unsafe practices which could result in minor personal injury or product and property damage.

NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

WARNING
PERSONAL INJURY, DEATH AND / OR PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or service agency must use factory−authorized kits or accessories when modifying this product.
Read and follow all instructions and warnings, including labels shipped with or attached to unit before operating your new air conditioner.

GENERAL

The floor console fan coil unit provides quiet, maximum comfort. In addition to cooling and/or heating, the floor console fan coil unit matched with an outdoor condensing unit filters and dehumidifies the air in the room to provide maximum comfort.
IMPORTANT: The floor console fan coil unit should be installed by authorized personnel only; using approved tubing and accessories. If technical assistance, service or repair is needed, contact the installer. The floor console fan coil unit can be set up and operated from the remote control (provided). If the remote is misplaced, the system can be operated from the AUTO setting on the unit.

Operating Modes
The floor console unit has five operating modes:

  • FAN Only
  • AUTO
  • HEATING (heat pumps only)
  • COOLING
  • DEHUMIDIFICATION (DRY)

FAN Only
In the FAN Only mode, the system filters and circulates the room air without changing room air temperature.

AUTO
In the AUTO mode, the system automatically cools or heats the room according to the user-selected set point.
NOTE: AUTO mode is recommended for use on single zone applications ONLY. Using AUTO CHANGEOVER on multi-zone applications could set an indoor unit to STANDBY mode, indicated with two dashes (–) on the display, which will turn off the indoor unit until all the indoor units are in the same mode (COOLING or HEATING). HEATING is the system’s priority mode. Simultaneous HEATING and COOLING is not allowed.

HEATING
In the HEATING mode, the system heats and filters the room air.

COOLING
In the COOLING mode, the system cools, dries and filters the room air.

DEHUMIDIFICATION (DRY)
In DEHUMIDIFICATION mode, the system dries, filters and slightly cools the room air temperature. This mode prioritizes air dehumidification but it does not take the place of a dehumidifier.

Wireless Remote Control

The remote control transmits commands to set up and operate the system. The control has a window display panel that displays the current system status. The control can be secured to a surface when used with the mounting bracket provided.

Wired Remote Control (Optional)
Refer to the Wired Controller manual.

24V Interface (Optional)
Allows the control of the Ductless System with a third party thermostat.

PARTS LIST

Carrier 40MBFQ Floor Console Ductless System-1

INDOOR UNIT DISPLAY PANELS

Carrier 40MBFQ Floor Console Ductless System-2

NOTE: Images within this manual are for illustration purposes only. Actual model may differ slightly.

WIRELESS REMOTE CONTROL FUNCTION BUTTONS

Before you begin using your new air conditioner, familiarize yourself with the remote control.Carrier 40MBFQ Floor Console Ductless
System-3

NOTE: New remote controller starting on production of week 10 year 2021 (serial number 1021V17181). For advanced functions, refer to the RG10B(B1)/BGEFU1 Wireless Remote Controller’s Service Manual.

WIRELESS REMOTE CONTROL LCD SCREEN INDICATORS

Carrier 40MBFQ Floor Console Ductless System-4

REMOTE CONTROL

CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage. Handle the control with care and avoid getting the control wet.

IMPORTANT: The wireless remote control can operate the unit from a distance of up to 26 ft. (8 m) as long as there are no obstructions.
NOTE: If a Wireless Remote controller is used, relocate the IR (Infrared) Receiver within line of sight of the remote location using the 6 ft. cable included. The factory location of the IR receiver is inside the control box.
When the timer function is used, the remote control should be kept in the vicinity of the unit (within 26 ft. (8 m).
The remote control can perform the following basic functions:

  • Turn the system ON and OFF
  • Select the operating mode
  • Adjust room air temperature set point and fan speed

Refer to the “WIRELESS REMOTE CONTROL FUNCTION BUTTONS” on page 4 for a detailed description of all the capabilities of the remote control.

Battery Installation

Two AAA 1.5v alkaline batteries (included) are required to operate the remote control.

To install or replace batteries:

  1. Slide the back cover off the control to open the battery compartment.
  2. Insert the batteries. Follow the polarity markings inside the battery compartment.
  3. Replace the battery compartment cover.

NOTES:

  1. When replacing batteries, do not use old batteries or a different type of battery. This may cause the remote control to malfunction.
  2. If the remote is not going to be used for several weeks, remove the batteries. Otherwise, battery leakage may damage the remote control.
  3. The average battery life under normal use is about 6 months.
  4. Replace the batteries when there is no audible beep from the indoor unit or if the Transmission Indicator fails to light.
  5. When batteries are removed, the remote control erases all programmed settings. The control must be reprogrammed after the insertion of new batteries.

Remote Control Operation – Quick Start
NOTE: When transmitting a command from the remote control to the unit, be sure to point the control toward the right side of the unit. The unit confirms receipt of a command by sounding an audible beep.

  1. Turn the unit on by pushing ON/OFF.
    NOTE: If there is a preference for °C rather than °F (default), press and hold TEMP  or TEMP  together for approximately 3 seconds.

  2. Select the desired mode by pushing MODE.Carrier 40MBFQ Floor Console Ductless System-5

  3. Select the temperature set point by pointing the control toward the unit and pressing the increase/decrease temperature set point buttons until the desired temperature appears on screen.

  4. Press FAN to select the desired fan speed.
    NOTE: If the unit is operating in DRY or AUTO mode, the fan speed will be automatically set.

  5. Set the airflow direction. When the unit is turned on, the Up-Down airflow louvers default to the cooling or heating position. The user can adjust the horizontal Up-Down airflow louver position by pushing DIRECT or have continuous louver movement by pressing SWING.

Manual Operation

If the remote control is lost, damaged, or the batteries are exhausted, MANUAL can be used to run the unit. When MANUAL is pressed once, the AUTO mode takes affect (heat or cool). When this button is pressed twice, the system enters the TEST mode and runs for 30 minutes in the COOLING mode (it will run in the AUTO mode afterward). When pressed three times, the system turns OFF.Carrier
40MBFQ Floor Console Ductless System-6
he set conditions of manual operation are as follows:

  • Preset set point: 76°F (24°C)
  • Fan speed: AUTO
  • Discharge air direction: Pre-set position based on operation in the COOL or HEAT mode
BASIC REMOTE CONTROL OPERATION

Before operation, ensure the unit is plugged in and power is available.
COOL ModeCarrier 40MBFQ Floor Console Ductless
System-7

  1. Press MODE to select the COOL mode.
  2. Set your desired temperature using TEMP  or TEMP 
  3. Press FAN to select the fan speed in a range of AU‘100%,
  4. Press ON/OFF to start the unit.
Setting Temperature

The operating temperature range for units is 60-86°F (16-30°C)/(68-82 °F (20-28°C) (depends on model). You can increase or decrease the set temperature in 1°F (0.5°C) increments.
HEAT ModeCarrier 40MBFQ Floor Console Ductless
System-8

  1. Press MODE to select the HEAT mode.
  2. Set your desired temperature using TEMP A or TEMP V.
  3. Press FAN to select the fan speed in the range of AU-100%.

NOTE: As the outdoor temperature drops, the performance of your unit’s HEAT function may be affected. In such instances, we recommend using this air conditioner in conjunction with other heating appliances.

AUTO Mode
In AUTO mode, the unit automatically selects the COOL, FAN, or HEAT operation based on the set temperature.Carrier 40MBFQ Floor Console Ductless
System-9

  1. Press MODE to select AUTO.
  2. Set your desired temperature using TEMP A or TEMP V
  3. Press ON/OFF to start the unit.
    NOTE: FAN Speed can not be set in the AUTO mode.

DRY ModeCarrier 40MBFQ Floor Console Ductless
System-10

  1. Press MODE to select the DRY mode.
  2. Set your desired temperature using TEMP A or TEMP V
  3. Press ON/OFF to start the unit.

FAN ModeCarrier 40MBFQ Floor Console Ductless
System-11

  1. Press MODE to select the DRY mode.
  2. Set your desired temperature using TEMP A or TEMP V
  3. Press ON/OFF to start the unit.

REMOTE CONTROL FUNCTIONS

Pressing ON/OFF
When the air conditioner is not in operation, the remote control displays the last set point and mode.

  • Press ON/OFF to start the unit.
    – The unit starts in the last operating mode and set point. The ON/OFF indicator appears.

  • Press ON/OFF to stop the unit.
    – All the indicator lights on the unit go out, and the remote control displays the set point and mode.

NOTE: If ON/OFF is pressed too soon after a stop, the compressor will not start for 3 to 4 minutes due to the inherent protection against frequent compressor cycling. The unit only emits an audible beep when the signals are received correctly.

Selecting an Operating Mode
Use OPERATING MODE to select one of the available modes.Carrier 40MBFQ Floor
Console Ductless System-12

Setting the Room Temperature Set Point
Press TEMP A or TEMP V to raise or lower the temperature. The unit confirms the signal receipt with a beep and the value
of the set temperature appears on the display and changes accordingly. The temperature can be set between 62 F (17 C) and 86 F (30 C) in increments of 1°F or 1°C.
NOTE: In the COOLING mode, if the temperature selected is higher than the room temperature, the unit will not start. The same applies for the HEATING mode if the selected temperature is lower than the room temperature.

Selecting the Fan SpeedCarrier 40MBFQ Floor Console Ductless
System-13

Press FAN to select the fan speed.
NOTE: When the unit is on, the fan runs continuously in cooling or heating. When in heating, there might be situations where the fan will slow down or shut off to prevent cold blow.

Selecting the Up-Down Airflow Louver Position
To optimize comfort, the horizontal louver should be adjusted to the desired position.
When COOLING
Adjust the up-down airflow louver downwards or horizontally (see Fig. 15).Carrier 40MBFQ Floor Console Ductless System-14 When HEATING
Adjust the up−down airflow louver vertically (see Fig. 17).Carrier 40MBFQ
Floor Console Ductless System-15The horizontal up−down airflow louvers can be adjusted by pressing DIRECT on the remote controller. Press SWING to set the louvers to a stationary position or to move continuously. The up−down airflow louver position is stored in the settings, however it is deactivated when the TURBO or MANUAL settings are set, or when a power interruption takes place

Air Direction
Press DIRECT repeatedly to choose one of the up−down airflow louver positions. Every time DIRECT is pushed, the specific louver swings 30 degrees.
In the COOLING, DEHUMIDIFICATION, and FAN ONLY modes, the up−down airflow louver swings in the cooling range.
In the HEATING mode, the louver swings in the heating range. NOTE: Always use the remote controller to adjust the up−down airflow louver position, otherwise abnormal operation may occur. If the horizontal louver is manually adjusted out of its range, power the unit off and then back on again.

Auto Swing
For automatic horizontal up−down airflow louver swing, push SWING.Carrier
40MBFQ Floor Console Ductless System-16

Selecting Right−Left Direction of the Louver
The right-left louvers can be adjusted manually to direct the airflow to achieve optimal comfort in the space. A knob can be found on the right side and the left side of the louvers.Carrier 40MBFQ Floor Console Ductless
System-17

CAUTION! Do not adjust the up−down airflow louver by hand. When adjusting by hand, the mechanism may not operate properly or condensation may drip from the air outlets.

AIRFLOW SELECTION SIZE 12

  1. Open the front panel.
    CAUT ION! Before opening the front panel be sure to stop the operation and turn the breaker OFF. Do not touch the metal parts on the inside of the indoor unit, as it may result in injury.

  2. 2. Make the airflow selection that best suits you. When setting the air flow selection, use the Dual Air Flow icon (see Fig. 23).Carrier 40MBFQ Floor Console Ductless System-18

NOTE: The air conditioner automatically determines the appro-priate blowing pattern based on the operating mode or situation.

Operating Mode

OPERATING MODE COOL MODE HEAT MODE



Situation

| When the room totally cools, or when one hour has passed since turning on

the air condi- tioner

| ****

At operation start or other times when the room is not totally cooled.

| ****


At times other than below (normal time)

| ****


At the start or when the air temp. is low.





Blowing Pattern

| So air does not come into direct contact

with people, air is blown from the upper air outlet, and the room temp. is

equalized.

| ****


Air is blown from the upper and lower air outlets for high speed cooling during the COOL mode, and for filling the room with warm air during the HEAT mode (see Fig. 18).

| ****

To keep air from coming into direct contact with occupants, air blows from the upper air outlet.

Carrier 40MBFQ Floor Console Ductless System-19
Air is blown from the upper air outlet during the DRY mode, so cold air does not come into direct contact with people.

When Setting the Air Outlet Selection Switch to Single Air FlowCarrier
40MBFQ Floor Console Ductless System-20

  • Regardless of the operating mode or situation, air blows from the upper air outlet.
  • Use this switch when you do not want air coming from the lower air

NOTE: Lower air outlet only available on size 12.

Timer Function
TIMER ON (to start the unit) and TIMER OFF (to stop the unit) can be used separately or together.

Timer ON Only
This function allows the unit to start automatically at the set time. The TIMER ON function can be set while the unit is on or off.

Unit On

  1. Press TIMER ON to initiate the auto-on time sequence. The set time is displayed in the remote control display. Every time TIMER ON is pressed, the time increases by 30 minutes, up to 10h. It increases by 60 minutes, afterwards, until the time setting reaches 24h.
  2. When the TIMER ON is set, the TIMER light on unit illuminates. The unit continues to run at the set time.

Unit Off

  1. Set the timer described in the UNIT ON section. The unit starts at the set time.
  2. Adjust the TIMER ON settings to 0.0 to cancel this option.

Timer OFF Only
This function allows the unit to stop automatically at the set time. The timer can be set while the unit is on or while it is off.

Unit On
Press TIMER OFF to initiate the auto-off time sequence. The set time appears on the remote control display. Every time TIMER OFF is pressed, the time increases by 30 minutes, up to 10h. It increases by 60 minutes, afterwards, until the time settings reach 24h. When the TIMER OFF is set, the timer light on the unit illuminates and the unit turns off automatically at the set time.

Unit Off

  1. Set the TIMER OFF as described in the UNIT ON section. The TIM-ER display on the unit illuminates and the unit remains off.
  2. Adjust the TIMER ON settings to 0.0 to cancel this option.

Timer ON and Timer OFF
Use both functions to program the unit to turn on and shut off at specified times.

Unit Off

  1. Set TIMER ON as previously described.
  2. Set TIMER OFF as previously described. The unit starts automatically at the set TIME ON and turns off at the set TIME OFF.

Unit On

  1. Set TIME OFF as previously described.
  2. Set TIME ON as previously described. The unit turns off automatically at the set TIME OFF and turns on at the set TIME ON.

SLEEP Mode
SLEEP mode is used to conserve energy. The mode can be used when the unit is in the COOL, HEAT or AUTO mode only.

HEATING Mode
Same as the COOLING mode however the set points are lowered by 1.8°F (1°C).

COOLING Mode
Push SLEEP. After 1 hour the set point raises by 1.8°F (1°C). After another hour, the set point raises by another 1.8°F (1°C) and the fan runs in a low speed. The unit shuts off 5 hours after setting the SLEEP mode. SLEEP mode cancels if either MODE, TEMP, FAN, TIMER, or ON/OFF on the remote control is pressed.

TURBO Mode
Use TURBO to cool or heat the room rapidly.

  1. Press TURBO. An audible “beep” is heard if the indoor unit supports this function. The fan runs on super high speed. The TURBO mode terminates automatically 20 minutes after selecting TURBO.
  2. To cancel TURBO, select TURBO mode again. When the TURBO mode terminates, the unit reverts to the original setting.

Clean Mode (Available only on sizes 18 to 24)
Press CLEAN to activate or deactivate the self−cleaning function. Under this function, the air conditioner automatically cleans and dries the evaporator. The cleaning cycle takes 16 minutes, after which the unit turns off automatically. Pressing CLEAN in the middle of the cycle cancels the operation and turns off the unit. This function can be activated only in the COOL or DRY mode.

SILENCE Mode
NOTE: The SILENCE Mode (SLC) is not available on this model.

LED Light
Press LED to turn the display light on and off.

Resetting the Remote Control
If the batteries in the remote control are removed, the current settings will be canceled and the control returns to the initial settings and will be in standby mode. Push ON/OFF to activate.

Time Delay
If ON/OFF is pressed too soon after a stop, the compressor will not start for 3 to 4 minutes due to the inherent protection against frequent compressor cycling. The unit only emits an audible beep when the signals are received correctly.

Heating Features
If the unit is in the heating mode, there is a delay when the fan starts. The fan starts only after the coil is warmed up to prevent cold blow.

Auto Defrost Operation
In HEATING mode, if the outdoor coil is frosted, the indoor fan and outdoor fan turns off while the system removes the frost from the outdoor coil. The system automatically reverts to normal operation when frost is removed from the outdoor unit.

Auto Start
If the power fails while the unit is operating, the unit stores the operating condition, and the unit will start operation automatically under those conditions when the power is restored.

CLEANING, MAINTENANCE AND TROUBLESHOOTING

CAUTION!
ELECTRICAL SHOCK HAZARD
Failure to follow this caution may result in personal injury or death. Always turn off power to the system before performing any cleaning or maintenance to the system. Turn off the outdoor disconnect switch located near outdoor unit. Be sure to disconnect the indoor unit if on a separate switch.

CAUTION!
EQUIPMENT DAMAGE/OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper unit operation. Operating the system with dirty air filters may damage the indoor unit and could cause reduced cooling performance, intermittent system operation, frost build-up on indoor coil or blown fuses.

Periodic Maintenance
Periodic maintenance is recommended to ensure proper operation of the unit. Recommended maintenance intervals may vary depending on the installation environment, e.g., dusty zones, etc. Refer to Table 2 on page 15.

Cleaning the Coil
Clean the coil at the beginning of each cooling season, or when necessary. Use a vacuum cleaner or a long-bristle brush to avoid damage to the coil fins.

Cleaning the Air Filters
Remove and clean the air filters once a month. A clogged air conditioner can reduce the cooling efficiency of your unit, and can also be bad for your health. NOTE: If air filters show signs of excessive wear or are torn, they must be replaced. Contact your local dealer for replacement filters.

  1. Open the front panel.Carrier 40MBFQ Floor Console Ductless System-21
    Carrier 40MBFQ Floor Console Ductless System-22

  2. Remove the air filter.Carrier 40MBFQ Floor Console Ductless System-23Carrier 40MBFQ Floor Console Ductless System-24

  3. Remove the carbon filter. Hold the frame’s tabs and remove the four claws. The carbon filter can be renewed by washing it with water once every 6 months.
    NOTE: The manufacturer recommends that the carbon filter be replaced every year.Carrier 40MBFQ Floor Console Ductless System-25

  4. Clean the air filter. A vacuum cleaner or pure water may be used to clean the air filter. If the dust accumulation is excessive, please use a soft brush and mild detergent to clean it and dry out in cool place.
    IMPORTANT: The air-in side should face up when using vacuum cleaner. The air- in side should face down when using water.

  5. Set the air filter and the carbon filter as they were and close the front panel. Operating the unit without the air filters may result in equipment damage or even failure as dust will accumulate inside the indoor unit.

CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage. When cleaning the front panel, do not use water hotter than 105°F (40.6°C) and do not pour water onto the fan coil. Do not use abrasive or petroleum based cleaners as they may damage the front panel.

Indoor Unit Front Panel

To clean the front panel on the indoor unit, wipe the outside with a soft, dry cloth.
Preparing for Extended Shutdown Period
Clean the filters and reposition them in the unit. Operate the unit in FAN ONLY mode for 12 hours to dry all internal parts. Turn the main power supply off and remove batteries from the remote control.

System Operation Recommendations

The items outlined in the following list help to assure proper system operation:

  • Replace both remote control batteries at the same time.
  • Point the remote control toward the unit display panel when transmitting a command.
  • Keep doors and windows closed while unit is operating.
  • Contact an authorized service representative if a problem arises that cannot be easily resolved.
  • Do not perform cleaning or maintenance activities while the unit is on.
  • Keep the display panel on the unit away from direct sunlight and heat as this may interfere with remote control transmissions.
  • Do not block air intakes and outlets on the indoor or outdoor units.

Energy Saving Recommendations
The following recommendations will add greater efficiency to the ductless system:

  • Select a comfortable thermostat setting and leave it at chosen setting. Avoid continually raising and lowering the setting.
  • Keep the filter clean. Frequent cleaning may be necessary depending on indoor air quality.
  • Use drapes, curtains or shades to keep direct sunlight from heating the room on very hot days.
  • Limit the unit’s run time by using the TIMER function.
  • Do not obstruct the air intake on the front panel.
  • Turn on the air conditioning unit before the indoor air becomes too uncomfortable.

TROUBLESHOOTING

INDOOR UNIT EVERY MONTH EVERY 6 MONTHS EVERY YEAR
Clean Air Filter* · ·
Replace Carbon Filter ·
Change Remote Control Batteries ·
OUTDOOR UNIT EVERY MONTH EVERY 6 MONTHS EVERY YEAR
Clean Outdoor Coil from Outside ·
Clean Outdoor Coil from Inside† ·
Blow Air Over Electric Parts† ·
Check Electric Connection Tightening† ·
Clean Fan Wheel† ·
Check Fan Tightening† ·
Clean Drain Pans† ·

Common Problems

PROBLEM POSSIBLE CAUSE SOLUTION


Unit/System Does Not Work

| The circuit breaker has tripped or a fuse has blown.| Reset the circuit breaker or replace the fuse with the specified replacement fuse.
Power failure| Restart the operation when the power is restored.
Diagnostic lights illuminate.*| Call your service representative
Voltage is too low.| Call your service representative.




Poor cooling performance

| The filter is blocked by dust.| Clean the air filter
Temperature is not set properly.| Check the temperature and reset if necessary.
A window or door is open.| Close the window or door.
The outdoor unit is obstructed.| Turn the unit off, remove the obstruction and turn it back on.
The fan speed is too low.| Change the fan speed selection.
The operation mode is in Fan instead of Cool.| Change the operating mode to Cool or reset the unit.



Poor heating performance

| The filter is blocked with dust.| Clean the filter.
The temperature is set too low.| Check the temperature and reset if necessary.
A window or door is open| Ensure all the doors and windows are closed while operating the unit.
The outdoor unit is obstructed.| Turn the unit off, remove the obstruction and turn the unit back on.
Unit stops during operation| The OFF timer is not operating correctly.| Restart the operating mode.
Diagnostic lights illuminate| Call a service representative for service

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals