HardHead 014100 Wireless Smoke Detector Instruction Manual

June 6, 2024
HardHead

Wireless Smoke Detector

Item no. 014100

OPERATING INSTRUCTIONS
****Important! Read the user instructions carefully before use. Save them for future reference. (Translation of the original instructions)

|
---|---
|

SAFETY INSTRUCTIONS

Carefully read the instructions before use! Save these instructions for future reference.

  • Do not use the product in damp, dusty or smoky environments.
  • Do not install the product so that light and sound are blocked.
  • When the battery capacity reaches a low level the smoke detector will emit an audio prompt approximately every 43/60 seconds to indicate that the battery needs to be replaced.
  • Store the smoke detector and packaging materials out of the reach of children.
  • If several connected products are installed, make sure that no objects obstruct communication.
  • The alarm function must only be tested with the test button on the product. Do not use any other test method. Test the alarm function every week, to verify correct functionality.
  • The alarm might not be noticed by all persons in the building. The alarm signal is strong so that it will be easily noticed when the danger exists. Nevertheless, there are several circumstances that can prevent the alarm signal from being detected, for example, strong background noise indoors or outdoors, deep sleep, diminished hearing, or influence of alcohol or drugs. Alarm devices must therefore be chosen and adapted to such and other conceivable difficulties in detecting the alarm signal. If for example a person in the household has diminished hearing and therefore can be expected to have difficulty in detecting the alarm signal, special alarms with light and/or vibration signals must be installed. To provide effective protection from personal injury or death, a smoke detector must be heard very quickly.

SYMBOLS

| Read the instructions.
---|---
| Approved in accordance with the relevant directives.
****| Recycle discarded products in accordance with local regulations.

19

NB2831 Jula AB, Box 363, SE-532 24 SKARA, SWEDEN Item No.014100
DoP reference No. D0P442055 Can be downloaded from www.jula.com
EN 14604:2005/AC:2008 Smoke alarm device.
Intended for Fire Safety and installed in buildings.
Essential Characteristic 1-8:pas.
CPR NO 2831-CPR-F1066

Standard EN 14604-2005/AC:2008
Frequency 433.92 MHz
Sound level for alarm 85 dB/3 m
Range 80 m
Size H4.8 x 012.5 cm
operating tempera ure – 0 to
Ambient humidity 95(:. RH (non-condensing)

Operating voltage

For smoke detector 9 VDC
For the wireless transmitter, 3 x 1.5 V batteries  I 4.5 VDC

Low battery level indicator

Smoke detector < 7.35 V A short audio signal is given at 43-second intervals
Wireless transmitter < 3.3 V A short audio signal is given at 60-second

intervals

Power consumption in operation

Smoke detector, inactive ≤10pA
Smoke detector, active  ≤20 mA
A wireless transmitter, inactive  ≤230 pA
A wireless transmitter, active  ≤4 mA

NOTE:

  • The optical smoke detector can be wirelessly interconnected with up to 22 optical smoke detectors.

DESCRIPTION

  • Photoelectric smoke detection
  • High sensitivity
  • Low power consumption
  • Can be connected to an unlimited number of other units

PARTS
Front

  1.  Casing
  2. Alarm status light (red LED)
  3. Test button
  4. Buzzer
  5. Status light connection/learning (red/ green LED)
  6. Learn button
    FIG. 1

Back

  1. Base
  2. Slot
  3. Compartment for 9 V battery
  4. Compartment for 1. V battery
    FIG. 2

Mounting plate

  1. Mounting plate
  2. Screw hole
  3. Hook
    FIG. 3

INSTALLATION

  1. Choose a suitable place to install within range of the other units.
  2. Use the mounting plate as a template and mark out and drill holes in the ceiling. Insert plugs in the holes.
  3. Screw on the mounting plate.
  4. Align the two hooks on the mounting plate to the slots in the base. Turn the base clockwise so that the hooks slot in place.
  5. Carry out a communication test after completing the installation.
    FIG. 4

INSERTING BATTERIES

  1. Unpack the product, turn the mounting plate anticlockwise and remove the batteries (9 V and 1.5 V). Remove the protective film from the batteries.
  2. Insert the 9 V battery with the polarity shown in the battery compartment.
  3. Turn the locking arm inward and insert the 1.5 V batteries with the polarity shown in the battery compartment.
  4. Align the two hooks on the mounting plate to the slots in the base and turn the plate clockwise so that the hooks slot in place.

HOW TO USE

TESTING/CONNECTING/REMOVING
When the smoke detector has started a red alarm status light flashes at 43-second intervals.

TEST
Press the test button. A loud audio signal is heard and the red alarm status light starts flashing. The red/green status light for connecting/learning mode flashes and a wireless alarm signal is given at the same time to all the connected smoke detectors within range. This shows that the smoke detector is working properly. You can also do a test with artificial smoke.

REPLACING THE BATTERY

  1. Grip the smoke detector casing, twist anticlockwise, and unhook the detector from the wall/ceiling holder.
  2. Remove the old battery and then conned the new battery.
  3. Put the new battery in the battery compartment, fit the detector in the wall/ ceiling holder and lock it in place in the holder by twisting clockwise.
  4. Test the smoke detector by pressing the test button. The alarm gives a loud audio prompt. If there is no loud alarm signal the smoke detector is either defective or incorrectly installed. See the troubleshooting section.

OBS!

  • The detector will not fit in the wall/ ceiling holder if no battery is inserted.
  • Do not take out the battery unless a new battery is to be immediately inserted.

SETTING/CONNECTING
Setting as host unit: When two or more smoke detectors are connected, press the learn button once. The red/green status light changes colour once. Set host units to the mode for green status light. Setting as a slave: Set slave units to the mode for red status light.
CONNECTED

  1. When the correct setting is made, keep the test button on the host unit pressed until the red alarm status light and the red/green status light for connection/ learn flash continuously and a wireless alarm signal is given.
  2. When a slave unit receives a signal from the host unit the status light for learn mode flashes continuously and an alarm is given at the same time by all the connected units. The red status light goes off.
  3. When the required units are connected, press the test button on one of the alarm units. The other connected smoke detectors give an alarm and the status lights flash continuously.

REMOVAL

Press the learn button on the unit to be removed, to put the unit in the mode for green status light. Press the test button to activate normal alarm mode. The red status light for alarm and the red/green status light for connection/learns flash continuously to show that the smoke detector has been removed.
FIRE DRILLS
When an alarm sounds everyone must know what to do. Prepare yourself and others in the building by establishing evacuation plans, and practice regularly.

  1. Let everyone hear the alarm signal and ensure that they all know what it means.
  2. Establish two exits from each room and one evacuation route from the building for each of these two exits.
  3. Teach everyone to feel doors before opening them. If the door is warm it must not be opened — choose an alternative exit.
  4. Explain that smoke and fumes rise to the ceiling — creep along the floor if evacuation must take place through smoke-filled rooms.
  5. Establish an assembly area outside the building.

IN CASE OF FIRE

  1. Stay calm — panic is your worst enemy.
  2. Evacuate the building as quickly as possible. Feel all doors before opening them, and do not open warm doors. Choose an alternative exit if necessary. Creep along the floor and never stop to try to take something with you.
  3. Assemble in previously agreed place outside the building.
  4. Alarm the fire brigade when you are outside the building.
  5. Never go back into a burning building. Wait until the fire brigade arrives.

NOTE:
These guidelines increase the chances of the involved parties to manage in the event of a fire, but to work they must be practiced regularly!

MAINTENANCE

  • Test the smoke detector every week.
  • Clean the smoke detector every month. Remove the batteries before cleaning. Check the connection with the test button after cleaning.
  • If the smoke detector is not working properly, check the batteries.
  • Only replace the batteries with new batteries of the same type.

TROUBLESHOOTING

Problem Cause Action
Nothing happens when the test button is pressed. 9 V battery not properly
inserted. Insert the 9 V battery with the polarity shown in the battery

compartment.
Nothing happens when the learn button is pressed.| 1.5 V batteries not properly inserted.| Insert 3 x 1.5 V batteries with the polarity shown in the battery compartment.
An audio signal is given at 43-second intervals.| 9 V battery discharged.| Replace the 9 V battery.
An audio signal is given at 60-second intervals.| 1.5 V batteries discharged.| Replace the 3 x 1.5 V batteries.

Care for the environment! Must not be discarded with household waste! This product contains electrical or electronic components that should be recycled. Leave the product for recycling at the designated station e.g. the local authority’s recycling station. Jula reserves the right to make changes. In the event of problems, please contact our customer service. www.jula.com

For latest version of operating instructions, see www.jula.com
Documents No: 014100 user manual.
Version No: 01
Issue date: 20210310 2831-CPR-F1066
2021-06-24 Jula AB

EU DECLARATION OF CONFORMITY

Jula AB, Box 363, SE-532 24 SKARA, SWEDEN
This declaration of conformity is issued under the sole responsibility of the manufacturer

Smoke Alarm, Wireless Dual pack
Item number 014100
Conforms to the following directives, regulations and standards
Construction Products Regulation 305/2011 EN 14604:2005/AC:2008
Radio Equipment Directive 2014/53/EU EN 300 220-2 V3.2.1, EN 301 489-1 V2.2.3, EN 301 489-3 V2.1.1
RoHS Directive 2011/65/EU and (EU) 2015/863 EN 50581:2012
This product was CE marked in year -20
Skara 2020-11-06

CHRISTIAN BLANK BUSINESS AREA MANAGER

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HardHead User Manuals

Related Manuals