Philio PST10 4-in-1 Multi Sensor Instruction Manual
- June 5, 2024
- Philio
Table of Contents
- Philio PST10 4-in-1 Multi Sensor
- Function Compare A/B/C/E
- Specification
- Troubleshooting
- Overview
- Wake
- Choosing A Mounting Location
- Installation
- Z-Wave Configuration Settings
- Z-Wave Supported Command Class
- Troubleshooting
- FCC Interference Statement
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Philio PST10 4-in-1 Multi Sensor
4 in 1 Multi-Sensor PST10 – A/B/C/E
The 4 in 1 multi-sensor PST10 has PIR, door/window, temperature, and light sensor for combining several functionalities in one device. This device is a security-enabled Z-Wave Plus™ product. The encrypted Z-Wave Plus™ messages support PST10 to communicate with other Z-Wave Plus™ products. PST10 can be used with Z-Wave™ devices (with the Z-Wave™ logo) from different manufacturers, it can also be included in the Z-Wave™ networks from different manufacturers. The product is supported with Over-the-Air (OTA) feature for firmware upgrades.
Function Compare A/B/C/E
| PIR| Door/Window| Temperature| Light sensor
---|---|---|---|---
PST10-A| V| V| V| V
PST10-B| V| | V| V
PST10-C| | V| V| V
PST10-E| V| V| V|
Specification
Power | 3VDC (CR123A lithium battery) |
---|---|
RF distance | Min. 40M indoor, |
100M outdoor line of sight,
RF Frequency
| 868.40 MHz, 869.85 MHz(EU)
908.40 MHz, 916.00 MHz(US) 920.9MHz, 921.7MHz, 923.1MHz (TW/KR/Thai/SG)
RF Maximum Power| +10dBm (Peak), -10dBm
(Average)
Dimension| 24.9 x 81.4 x 23.1mm
25.2 x 7.5 x 7 mm (magnetic)
Weight
| 23.2g (PST10-A, PST10-B, PST10-E)
21.2g (PST10-C)
Location| indoor use only
Operation temperature| -20oC ~ 50oC
Humidity| 85%RH max
FCC ID| RHHPST10
Troubleshooting
Symptom | Cause of Failure | Recommendation |
---|---|---|
The device can not join to Z-Wave™ network | The device may in a Z- Wave™ | |
network. | Exclude the device then include again. |
For Instruction to http://www.philio-tech.com
Overview
CAUTION
- replacement of a battery with an incorrect type that can defeat a safeguard (for example, in the case of some lithium battery types);
- disposal of a battery into fire or a hot oven, or mechanically crushing or cutting of a battery, that can result in an explosion;
- leaving a battery in an extremely high temperature surrounding environment that can result in an explosion or the leakage of flammable liquid or gas;
- a battery subjected to extremely low air pressure that may result in an explosion or the leakage of flammable liquid or gas The marking information is located at the bottom of the apparatus \
Add to/Remove from Z-WaveTM Network
There are two tamper keys in the device, one is in the back side, another is
in the front side. Both of them can add, remove, reset or association from
Z-WaveTM network. The table below lists an operation summary of basic Z-Wave
functions. Please refer to the instructions for your Z-WaveTM Certificated
Primary Controller to access the Setup function, and to Add/Remove/associate
devices
Notice : Including a node ID allocated by Z-WaveTM Controller means “Add”
or “Inclusion”. Excluding a node ID allocated by Z-WaveTM Controller means
“Remove” or “Exclusion”.
Function | Description |
---|
Add
| 1. Have Z-WaveTM Controller entered inclusion mode.
2. Pressing tamper key three times within 2 seconds to enter the inclusion mode.
3. After add successful, the device will wake to receive the setting command from Z-WaveTM Controller about 20 seconds.
Remove
| 1. Have Z-WaveTM Controller entered exclusion mode.
2. Pressing tamper key three times within 2 seconds to enter the exclusion mode.
Node ID has been excluded.
Reset
| Notice: Use this procedure only in the event that the primary controller is lost or otherwise inoperable.
1. Pressing button four times and keep about 5 seconds.
2. IDs are excluded and all settings will reset to factory default.
---|---
SmartStart
| 1. Product has a DSK string, you can key in first five digit to increment smart start process, or you can scan QR code.
2. SmartStart enabled products can be added into a Z-Wave network by scanning the Z-Wave QR Code present on the product with a controller providing SmartStart inclusion. No further action is required
and the SmartStart product will be added automati- cally within 10 minutes of being switched on in the network vicinity.
*notice1:The QR code can be found on the device or in the box.
Association
| This machine provides 2 groups of nodes. Group one support 1 nodes maximum and group two support 5 nodes maximum.
Group 1(Lifeline Group): Used for returned events. Command class:
1. Notification report
2. Sensor multilevel report
3. Device Reset Locally Notification
4. Battery Report
5. Indicator Report
Group 2: Used for light control, the device will send the “Basic Set” command to this group.
Command class:
1. Basic Set
• Failed or success in add/remove the node ID can be viewed
Notice T 1M: Always RESET a Z-WaveTM device before trying to add it to a Z-Wave network
Z-WaveTM Notification
After the device adding to the network, it will wake up once per day in
default. When it wake-up it will broadcast the “Wake Up Notification” message
to the network, and wake up 10 seconds for receiving the set commands. The
wake-up interval minimum setting is 30 minutes, and the maximum setting is 120
hours. And the interval step is 30 minutes. If the user wants to wake up the
device immediately, please remove the front cover, and press the tamper key
once. The device will wake up 10 seconds.
Z-WaveTM Message Report
When the PIR motion-triggered, the device will report the trigger event and
also report temperature and illumination level.
Motion Report: When the PIR motion detected, the device will unsolicited
to send the report to the nodes in group 1.
Door/Window Report: When the door/window state changed, the device will
unsolicited to send the report to the nodes in group 1.
Notification Report (V8)
Notification Type: Access Control (0x06)
Event: Door/Window is open (0x16)
Door/Window is closed (0x17)
Tamper Report: The tamper keys are pressed over 5 seconds. The device
will into the alarm state. In that state, if any one of the tamper keys be
released, the device will unsolicited to send the report to the nodes in group
Notification Report (V8)
Notification Type: Home Security (0x07)
Event: Tampering. Product covering removed (0x03)
Temperature Report:
When the PIR motion detected state changed, the device will unsolicited to
send the “Sensor Multilevel Report” to the nodes in group 1.
Sensor Type : Temperature (0x01)
Temperature differential report
This function default is enabled, to disable this function by setting the
configuration NO.12 to 0.
In the default, when the temperature is changed to plus or minus one degree
Fahrenheit (0.5 degrees Celsius), the device will report temperature
information to the nodes in the group 1.
Caution 1: Enable this functionality, it will cause the PIR Motion to disable
detection when the temperature measurement. In other words, The PIR motion
will blind one second in every one minute.
LightSensor Report:
When the PIR motion detected state changed, the device will unsolicited to
send the “Sensor Multilevel Report” to the nodes in group 1.
Sensor Type: Luminance (0x03)
LightSensor differential report
This function default is disabled, to enable this function by setting the
configuration NO.13 not to zero. And if the light sensor is changed to plus or
minus the value (setting by the configuration NO.13), the device will report
illumination information to the nodes in group 1.
Caution 1: Enable this functionality, it will cause the PIR Motion to
disable detection when the illumination measurement. In other words, The PIR
motion will blind one second in every one minute.
Timing Report
Besides the event triggered could report message, the device also support the
timing unsolicited report of the status.
- Door/window state report: Every 6 hours report once in default. It could be changed by setting the configuration NO. 2.
- Battery level report: Every 6 hours report once in default. It could be changed by setting the configuration NO. 8.
- Low battery report: When the battery level is too low. (Lose battery report when a power-on or PIR trigger.)
- light sensor level report: Every 6 hours report once in default. It could be changed by setting the configuration NO. 9.
- Temperature report: Every 6 hours report once in default.
It could be changed by setting the configuration NO. 10.
Notice: Configuration NO. 8 could be setting to zero to disable the auto
report. And the configuration NO. 11 could change the tick interval, the
default value is 30, if setting to 1, that means the minimum auto report
interval will be one minute.
Power Up Procedure
Battery Power Check
When the device power up, the device will detect the power level of the
battery immediately. If the power level is too low, the LED will continue
flash about 5 seconds. Please change another new battery.
Wake
When the device powered on, the device will wake for about 20 seconds. In this duration, the controller can communicate with the device. Normally the device is always sleeping to save the battery energy.
Security Network
The device supports the security function. When the device is included with a
security controller, the device will auto switch to the security mode. In the
security mode, the follow commands need using Security CC wrapped to
communicate, otherwise, it will not respond.
- COMMAND_CLASS_VERSION_V3
- COMMAND_CLASS_MANUFACTURER_SPECIFIC_V2
- COMMAND_CLASS_DEVICE_RESET_LOCALLY
- COMMAND_CLASS_ASSOCIATION_V2
- COMMAND_CLASS_ASSOCIATION_GRP_INFO
- COMMAND_CLASS_POWERLEVEL
- COMMAND_CLASS_CONFIGURATION
- COMMAND_CLASS_NOTIFICATION_V8
- COMMAND_CLASS_FIRMWARE_UPDATE_MD_V4
- COMMAND_CLASS_BATTERY
- COMMAND_CLASS_SENSOR_MULTILEVEL_V11
- COMMAND_CLASS_WAKE_UP_V2
Operation Mode
There are two modes “Test” and “Normal”. “Test Mode” is for the user test the
sensor function when installation.“Normal Mode” is for the normal operation.
Operation Mode can be switched by pressing a button or tamper key two times.
LED can indicate which mode it is. Lighting on one second means entering test
mode, flashing once means entering
normal mode.
When the event is triggered, normally the LED won’t indicate, unless the
battery is in a low level, the LED will flash once. But in the “Test Mode” the
LED also will light ON one second.
When the event is triggered, the device will emit the signal to turn ON the
lighting equipment, those nodes are in group 2. And delay a while to turn OFF
the lighting equipment. The delay time is set
by configuration
The PIR motion re-detected interval, in the “Test Mode” was fixed to 10
seconds. In the “Normal Mode”, it is according to the setting of the
configuration NO. 6.
Notice: When the tamper key of the backside is released, the device is
always in the “Test Mode”, no matter the DIP switch setting.
Choosing A Mounting Location
Select the mounting location so that the expected motion of an intruder would
cross. the detector’s coverage pattern. The device comes to Wall-mounted.
Before selecting a position for a Motion
Detector the following points should be noted:
- Do not position the detector facing a window /fan /air-condition or direct sunlight. Motion Detectors are not suitable for use in conservatories or draughty areas.
- Do not position the detector directly above or facing any source of heat, eg: fires, radiators, boiler etc.
- Where possible, mount the detector so that the logical path of an intruder would cut across the fan pattern rather than directly towards the detector
Battery Installation
When the device reports the low battery message, users should replace the
battery. The battery type is CR123A, 3.0V.
To open the front cover, follow the steps below.
- Use a screwdriver to loosen the screw. (step 1)
- Hold the front cover and push it up. (Step 2)
Replace the battery with a new one and replace the cover.
- Align the bottom of the front cover with the lower cover. (Step 3).
- Push the top of the front cover to close and lock the screw. (Step 4 and step 1)
Installation
- In the first time, add the device into the Z-WaveTM network. First, make sure the primary controller is in the inclusion mode. And then pressing tamper key three times within 2 seconds to enter the inclusion mode. After add successful, the device will wake to receive the setting command from Z-WaveTM Controller about 20 seconds.(refer to fig. 1)
- Let the controller associate with the device into the first group, any light switch that intend to be turned on when the device trig please associate with the device into the second group.
- In the accessory pack, There is double-coated tape. you can use a double-coated type for the test at the beginning. The right way for double coated type installation is to stick it to the position of the back. the sensor will enter the test mode, You may test if the installed position is good or not by this way (refer to fig. 2 and fig. 3)
CAUTION:
The lens installation direction is down.
Warning:
- Before the product is installed, please make sure the surface is clean. Especially for the surface of glass and wood, keep it dry before installation.
- It is highly recommended to press the product on double-sided tape for 30 seconds.
Z-Wave Configuration Settings
| Name| Def.| Valid| A| B| C| E| Description
---|---|---|---|---|---|---|---|---
1
| ****
Basic Set Level
| ****
0xFF
| ****
0 ~
99
,0xFF
| ****
þ
| ****
þ
| ****
o
| ****
þ
| Setting the BASIC command value to turn on the light. For dimmer equipment 1 to 99 means the light strength.0 means turn off the light. The 0xFF means last level for multi- level Switch.
2
| Auto Report Door/ Window State Time| ****
12
| ****
0~127
| ****
þ
| ****
o
| ****
þ
| ****
þ
| The interval time for auto report
the door/window state. 0 means turn off auto report door/window state.
The default value is 12. The tick time
can setting by the configuration No.11.
3
| ****
PIR
Sensitivity
| ****
99
| ****
0 ~
99
| ****
þ
| ****
þ
| ****
o
| ****
þ
| PIR sensitivity settings.
0 means disable the PIR motion. 1 means the lowest sensitivity, 99 means the highest sensitivity.
High sensitivity means can detected long distance, but if there is more noise signal in the environment, it
will re-trigger too frequency.
4| Operation Mode| 0x31| ****
All
| | | | | Operation mode. Using bit to control.
1| | þ| þ| þ| þ| Bit0 : Setting the temperature scale. (1: Fahrenheit,
0:Celsius)
0| | –| –| –| –| Bit1 : Reserve.
0| | þ| o| þ| þ| Bit2 : Disable the door/window function. (1:Disable,
0:Enable)
0| | –| –| –| –| Bit3 : Reserve.
| Name| Def.| Valid| A| B| C| E| Description
---|---|---|---|---|---|---|---|---
| | 1| | þ| þ| þ| o| Bit4 : Disable the illumination report after event
triggered. (1:Disable, 0:Enable)
1
| | þ| þ| þ| þ| Bit5 : Disable the temperature report after event
triggered. (1:Disable, 0:Enable)
0| | –| –| –| –| Bit6: Reserve.
0| | –| –| –| –| Bit7: Reserve.
5| Customer Function| 0x13| ****
All
| | | | | Customer function switch, using bit control.
1| | þ| þ| þ| þ| Bit0 : Tamper On/Off (1:On, 0:Off)
1| | þ| þ| þ| þ| Bit1 : Red LED On/Off (1:On, 0:Off)
0
| | ****
þ
| ****
þ
| ****
o
| ****
þ
| Bit2 : Motion Off.(1:On, 0:Off) Note: Depends on the Bit2,
1: Report Notification CC,
Type: 0x07, Event: 0xFE
10
| | ****
þ
| ****
þ
| ****
þ
| ****
þ
| Bit3 、 Bit4 : Trigger Basic on/off function.
00: Disable
01: Door / Window Enable, PIR Disable
10: PIR Enable, Door / Window Disable
11: PIR & Door / Window Enable
0
| | ****
þ
| ****
o
| ****
þ
| ****
þ
| Bit5 : Door/Window Trigger Basic on/ off function.
0: Open Door/Window trigger
1: Close Door/Window trigger
0| | –| –| –| –| Bit6 : Reserve.
| Name| Def.| Valid| A| B| C| E| Description
---|---|---|---|---|---|---|---|---
| | 0| | –| –| –| –| Bit7: Reserve.
6
| ****
PIR Re-
Detect Interval Time
| ****
6
| ****
1 ~
60
| ****
þ
| ****
þ
| ****
o
| ****
þ
| In the normal mode, after the PIR motion detected, setting the re- detect time. 10 seconds per tick, default tick is 6 (60 seconds).
Setting the suitable value to prevent received the trigger signal too frequently. Also can save the battery energy.
Notice: If this value bigger than the configuration setting NO. 7 There is a period after the light turned off and
the PIR not start detecting.
7
| ****
Turn Off Light Time
| ****
7
| ****
1
~ 60
| ****
þ
| ****
þ
| ****
þ
| ****
þ
| After turn on the lighting, setting the delay time to turn off the lighting when the PIR motion or door/windows is not detected . 10 seconds per tick, default tick is 7 (70 seconds).
0 means never send turn off light
command.
8
| ****
Auto Report Battery Time
| ****
12
| ****
0
~ 127
| ****
þ
| ****
þ
| ****
þ
| ****
þ
| The interval time for auto report the battery level.
0 means turn off auto report battery. The default value is 12. The tick time can setting by the configuration
No.11.
9
| ****
Auto Report LightSenso r Time
| ****
12
| ****
0
~ 127
| ****
þ
| ****
þ
| ****
þ
| ****
o
| The interval time for auto report the illumination.
The default value is 12. The tick time can setting by the configuration
No.11.
| Name| Def.| Valid| A| B| C| E| Description
---|---|---|---|---|---|---|---|---
10
| ****
Auto Report Temperatu re Time
| ****
12
| ****
0
~ 127
| ****
þ
| ****
þ
| ****
þ
| ****
þ
| The interval time for auto report the temperature.
The default value is 12. The tick time can setting by the configuration
No.11.
11
| ****
Auto Report Tick Interval
| ****
30
| ****
0
~ 0xFF
| ****
þ
| ****
þ
| ****
þ
| ****
þ
| The interval time for auto report each tick. Setting this configuration will effect configuration No.2 , No.8, No.9 and No.10.
The unit is 1 minute.
12
| ****
Temperatu re Differential Report
| ****
2
| ****
1
~ 100
| ****
þ
| ****
þ
| ****
þ
| ****
þ
| The temperature differential to report.
0 means turn off this function. The unit is 0.5 Celsius.
Enable this function the device will detect per 30 seconds.
And when the temperature is over 140 degree Fahrenheit, it will continue report.
Enable this functionality will cause some issue please see the detail in
the “Temperature Report” section.
13
| ****
LightSenso r Differential Report
| ****
20
| ****
1
~ 100
| ****
þ
| ****
þ
| ****
þ
| ****
o
| The LightSensor Differential to report.
0 means turn off this function. The unit is percentage.
Enable this function the device will detect per 10 seconds.
And when the lightSensor is over 20
percentage, it will continue report.
14| PIR Trigger| 1| 1~3| þ| þ| o| o| PIR Trigger Mode:
| Name| Def.| Valid| A| B| C| E| Description
---|---|---|---|---|---|---|---|---
| ****
Mode
| | | | | | | Mode1: Normal Mode2: DayTime Mode3: AtNight
15
| ****
PIR
NightLine
| ****
100
| 1
~ 10000
| þ| þ| o| o| PIR night line Lux conditions: LightSensor determines whether
the level is night. (Unit 1Lux)
Manufacturer Specific| 2| Highest granted Security Class
---|---|---
Battery| 1| Highest granted Security Class
Multilevel Sensor| 11| Highest granted Security Class
Wake up| 2| Highest granted Security Class
Indicator| 3| Highest granted Security Class
Multi Channel Association| 3| Highest granted Security Class
Z-Wave Supported Command Class
Command Class | Version | Required Security Class |
---|---|---|
Z-Wave Plus™ Info | 2 | None |
Version | 3 | None |
Supervision | 1 | None |
Transport Service | 2 | None |
Security 2 | 1 | None |
Device Reset Locally | 1 | Highest granted Security Class |
Association | 2 | Highest granted Security Class |
Association Group Information | 3 | Highest granted Security Class |
Powerlevel | 1 | Highest granted Security Class |
Configuration | 4 | Highest granted Security Class |
Notification | 8 | Highest granted Security Class |
Firmware Update Meta Data | 5 | Highest granted Security Class |
Manufacturer Specific | 2 | Highest granted Security Class |
--- | --- | --- |
Battery | 1 | Highest granted Security Class |
Multilevel Sensor | 11 | Highest granted Security Class |
Wake up | 2 | Highest granted Security Class |
Indicator | 3 | Highest granted Security Class |
Multi Channel Association | 3 | Highest granted Security Class |
Troubleshooting
Symptom | Cause of Failure | Recommendation |
---|---|---|
The device can not join to Z-Wave™ network | The device may in a Z-Wave™ | |
network. | Exclude the device then include again. | |
Disposal
This marking indicates that this product should not be disposed with other
household wastes throughout the EU. To prevent possible harm to the
environment or human health from uncontrolled waste disposal, recycle it
responsibly to promote the sustainable reuse of material resources. To return
your used device, please use the return and collection systems or contact the
retailer where the product was purchased. They can take this product for
environmentally safe recycling.
Philio Technology Corporation
8F., No.653-2, Zhongzheng Rd., Xinzhuang Dist., New Taipei City 24257,
Taiwan(R.O.C) www.philio-tech.com
FCC Interference Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
FCC Caution: Any changes or modifications not expressly approved by the
party responsible for compliance could void the user’s authority to operate
this equipment.
This transmitter must not be co-located or operating in conjunction with any
other antenna or transmitter.
Warning
Do not dispose of electrical appliances as unsorted municipal waste, use
separate collection facilities. Contact your local government for information
regarding the collection systems available. If electrical appliances are
disposed of in landfills or dumps, hazardous substances can leak into the
groundwater and get into the food chain, damaging your health and well-being.
When replacing old appliances with new once, the retailer is legally obligated
to take back your old appliance for disposal at least for free of charge.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>