MEAN WELL LRS-450-5 Single Output Switching Power Supply Instruction Manual
- June 1, 2024
- MEAN WELL
Table of Contents
MEAN WELL LRS-450-5 Single Output Switching Power Supply
Product Information
Specifications
MODEL| DC VOLTAGE| RATED CURRENT| CURRENT RANGE| RATED POWER| RIPPLE & NOISE
(max.)| OUTPUT SETUP, RISE TIME| HOLD UP TIME (Typ.)| VOLTAGE RANGE| FREQUENCY
RANGE| EFFICIENCY (Typ.)
---|---|---|---|---|---|---|---|---|---|---
LRS-450-5| 5V| 75A| 0 ~ 75A| 375W| 200mVp-p| 1500ms, 50ms/230VAC
1500ms,50ms/115VAC at full load| 16ms/230VAC 12ms/115VAC at full load| 90 ~
132VAC / 180 ~ 264VAC by switch 255 ~ 370VDC (swith on
230VAC)| 47 ~ 63Hz| 87%
LRS-450-12| 12V| 37.5A| 0 ~ 37.5A| 450W| 200mVp-p| 1500ms, 50ms/230VAC
1500ms,50ms/115VAC at full load| 16ms/230VAC 12ms/115VAC at full load| 90 ~
132VAC / 180 ~ 264VAC by switch 255 ~ 370VDC (swith on
230VAC)| 47 ~ 63Hz| 90%
Product Usage Instructions
Installation:
Follow these steps to install the power supply:
- Ensure the power supply is disconnected from the power source.
- Mount the power supply securely in a well-ventilated area.
- Connect the input and output terminals correctly.
Powering On:
To power on the unit:
- Ensure all connections are secure.
- Connect the power supply to a compatible power source within the specified voltage range.
- Switch on the power supply using the designated switch.
Troubleshooting:
If you encounter any issues with the power supply, refer to the
troubleshooting section of the user manual for guidance or contact customer
support for assistance.
Frequently Asked Questions (FAQ)
-
Q: Can this power supply be used at high altitudes?
A: Yes, this power supply can operate at altitudes up to 5000 meters. -
Q: What is the efficiency of the LRS-450-15 model?
A: The efficiency of the LRS-450-15 model is rated at 90%.
Features
- MEANWELL Patent Number: ZL202220241473.0
- AC input range selectable by switch
- Withstand 300VAC surge input for 5 second
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Forced air cooling
- Built-in cooling Fan ON-OFF control
- 1U low profile
- Withstand 5G vibration test
- High operating temperature up to 70°C
- Operating altitude up to 5000 meters (Note.10)
- 3 years warranty
- MTBF>1KK hrs
Applications
- Industrial automation machinery
- Industrial control system
- Mechanical and electrical equipment
- Electronic instruments, equipment or apparatus
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
LRS-450 series is a 450W single-output enclosed type power supply with 35mm of low profile design. Adopting the input of 115VAC or 230VAC (select by switch), the entire series provides an output voltage line of 5V, 12V, 15V, 24V, 36V and 48V.In addition to the high efficiency up to 92%, with the built-in long- life fan LRS-450 can work under -20~+70°C with full load. LRS-450 has complete protection functions and 5G anti-vibration capability; It is complied with complete international safety regulations LRS-450 series serves as a high price-to-performance power supply solution for various industrial applications.
Model Encoding
SPECIFICATION
MODEL| LRS-450-5| LRS-450-12| LRS-450-15| LRS-450-24|
LRS-450-36| LRS-450-48
---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 5V| 12V| 15V| 24V| 36V| 48V
RATED CURRENT| 75A| 37.5A| 30A| 18.8A| 12.5A| 9.4A
CURRENT RANGE| 0 ~ 75A| 0 ~ 37.5A| 0 ~ 30A| 0 ~ 18.8A| 0 ~ 12.5A| 0 ~
9.4A
RATED POWER| 375W| 450W| 450W| 451.2W| 450W| 451.2W
RIPPLE & NOISE (max.) **Note.2| 200mVp-p| 200mVp-p| 200mVp-p|
240mVp-p| 360mVp-p| 360mVp-p
VOLTAGE ADJ. RANGE Note.3| 4.75 ~ 5.5V| 11.4 ~ 13.2V| 14.25 ~ 16.5V|
22.8 ~ 26.4V| 34.2 ~ 39.6V| 45.6 ~ 52.8V
VOLTAGE TOLERANCE Note.4| ±2.0%| ±1.5%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION Note.5| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION Note.6| ±2.0%| ±1.0%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME Note.7| 1500ms, 50ms/230VAC
1500ms,50ms/115VAC at full load
HOLD UP TIME (Typ.)| 16ms/230VAC 12ms/115VAC at full load
INPUT| VOLTAGE RANGE Note.8| 90 ~ 132VAC / 180 ~ 264VAC by
switch 255 ~ 370VDC (with on 230VAC)
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 87%| 90%| 90%| 91%| 92%| 92%
AC CURRENT (Typ.)| 10A/115VAC 6A/230VAC
INRUSH CURRENT (Typ.)| 35A/115VAC 60A/230VAC
LEAKAGE CURRENT| <2mA / 240VAC
PROTECTION (Note.9)| OVERLOAD| 105 ~ 150% rated output power
Constant current limiting, the unit will shut down after 3 sec. re-power on to
recover
OVERVOLTAGE| 5.75 ~ 6.75V| 13.8 ~ 16.2V| 18 ~ 21V| 27.6 ~ 32.4V| 41.4 ~
48.6V| 55.2 ~ 64.8V
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down the o/p voltage, and re-power on to recover
FUNCTION| FAN ON/OFF CONTROL**
(Typ.)
| RTH3≧50℃ FAN ON, ≦40℃ FAN OFF
ENVIRONMENT| WORKING TEMP.| -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, and Z
axes
OVERVOLTAGE CATEGORY| Ⅲ: According to EN61558, EN50178, EN60664-1,
EN62477-1; altitude up to 2000 meters
SAFETY| SAFETY STANDARDS| BS IEC/UL 62368-1, EAC TP TC 004,
KC62368-1(except for 5V), BIS IS13252(Part1):2010/IEC60950-1: 2005(except for
48V), BSMI CNS15598-1, GB 4943.1, BS EN/EN61558-1, BS EN/EN61558-2-16
approved,
Designed by AS/NZS 61558.1/2.16, AS/NZS 62368.1
WITHSTAND VOLTAGE| I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC / 25℃/
70% RH
EMC EMISSION| Compliance to EAC TP TC 020, BSMI CNS15936, KC KSC 9832,
KSC 9835
EMC IMMUNITY| Compliance to EAC TP TC 020, KC KSC 9832, KSC 9835
OTHERS| MTBF| 1508.9K hrs min. Telcordia SR-332(Bellcore); 252.2K
hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 22512435mm (LWH)
PACKING| 0.85Kg/15pcs/14.11Kg/0.84CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC
input, rated load and 25°C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted
pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Voltage adjustment can only be operated within the input range of
100~120VAC or 200-240VAC. If the voltage adjustment is performed outside this
range, it may cause abnormal output.
4. Tolerance: includes set up tolerance, line regulation and load regulation.
5. Line regulation is measured from low line to high line at rated load.
6. Load regulation is measured from 0% to 100% rated load.
7. Length of set up time is measured at cold start. Turning the power supply
on/off frequently may lead to an increase of the set up time.
8. Derating may be needed under low input voltages. Please refer to”Static
Characteristics” sections for details.
9. Once protections are triggered, 3min(Typ.) of cold down time is required
before restart.
10. The ambient temperature derating of 5°C/1000m is needed for operating
altitude greater than 2000m(6500ft).
11. This power supply does not meet the harmonic current requirements
outlined by EN61000-3-2. Please do not use this power supply under the
following conditions:
a) the end devices is used within the European Union, and
b) the end-devices is connected to public mains supply with 220Vac or greater
rated nominal voltage, and
c) the power supply is:
– installed in end-devices with average or continuous input power greater than
75W, or
– belong to part of a lighting system
Exception:
Power supplies used within the following end-devices do not need to fulfill
EN61000-3-2
a) professional equipment with a total rated input power greater than 1000W;
b) symmetrically controlled heating elements with a rated power less than or
equal to 200W
12.RCM is on voluntary basis and meets relevant IEC or AS/NZS standards
complying with AS/NZS 4417.1. * Product Liability Disclaimer : For detailed
information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Mechanical Specification
Installation Manual
Please refer to: http://www.meanwell.com/manual.html
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>