VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator User Manual

June 5, 2024
VENTS

VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery

Ventilator

VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery
Ventilator product

This user’s manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about purpose, technical details, operating principle, design, and installation of the TwinFresh Comfo RB(1)-50/85 unit and all its modifications. Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country. The information in this user’s manual is correct at the time of the document’s preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means in any information search system or translated into any language in any form without the prior written permission of the Company.

SAFETY REQUIREMENTS

All user’s manual requirements, as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards, must be observed when installing and operating the unit. Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations. Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation and maintenance. The present user’s manual should be carefully read before beginning work.

  1. Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
  2. While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise.
  3. Misuse of the unit and any unauthorized modifications are not allowed.
  4. Do not expose the device to adverse atmospheric agents (rain, sun, etc.).
  5. Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
  6. Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
  7. Do not close or block the intake or extract vents in order to ensure the efficient air flow.
  8. Do not sit on the unit and do not put objects on it.
  9. The information in this user’s manual was correct at the time of the document’s preparation.
  10. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
  11. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means in any information search system or translated into any language in any form without the prior written permission of the Company.
  12. Never touch the unit with wet or damp hands.
  13. Never touch the unit when barefoot.

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. The connection to the supply mains must be made through a means of disconnection, which is incorporated in the fixed wiring in accordance with the wiring rules, and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard. Ensure that the appliance is switched off from the supply mains before removing the guard. Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.

THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.

PURPOSE

  • The ventilator is designed to ensure continuous mechanical air exchange in flats, cottages, hotels, cafés and other domestic and public premises. The ventilator is equipped with a regenerator that enables supply of fresh filtered air heated by means of extract air heat energy recovery.
  • The ventilator is designed for installation on external walls and partitions.
  • The unit is rated for continuous operation.

DELIVERY SET

Name Number
Indoor assembly unit of the ventilator 1 pc.
Telescopic air duct 1 pc.
Regenerator with filters, assembled 1 pc.
Outer ventilation hood 1 pc.
Remote control 1 pc.
Cardboard mounting plate 1 pc.
Sealing gasket 1 pc.
Mounting kit 1 pc.
Mounting wedges 1 kit
User’s manual 1 pc.
Mounting hood installation instruction 1 pc.
Packing box 1 pc.

DESIGNATION KEYVENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy
Recovery Ventilator 1

TECHNICAL DATA

  • The temperature in the room where the indoor unit of the ventilator is installed must be in the range from +1 ˚C to +40 ˚C with relative humidity up to 65% (no condensation buildup). If the conditions for using the ventilator are beyond the specified limits, turn off the ventilator. Provide fresh air supply through windows.
  • The temperature of the transported air should be in the range from -15 ˚C to +40 ˚C.
  • The unit is rated as a class II electric appliance.
  • Ingress protection rating against access to hazardous parts and water ingress is IP24.
  • The ventilator design is constantly being improved, thus some models may be slightly different from those described in this manual.VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator 2
  • The telescopic design of the air duct allows its length to be adjusted without mechanical cutting. The thickness of the wall, in which the ventilator can be installed, depending on the used outer hood, is shown in the table below.
    Ventilator model| Allowable wall thickness [mm]
    ---|---
    TwinFresh Comfo RB(1)-50/85| 240 – 425
    TwinFresh Comfo RB(1)-50/85 – 2| 120 – 300
    TwinFresh Comfo RB(1)-50/85 – 3| 240 – 440
  • The technical specifications of the particular model are indicated on the unit casing.
  • The overall and connecting dimensions of the outer ventilation hood, the outside protrusion length of the air duct A and the mounting sequence of the hood are stated in its installation instruction.
  • The overall dimensions of the front panel are stated in the figure below.VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator 3

DESIGN AND FUNCTIONING

  1. The ventilator consists of an indoor unit with a decorative front panel, a telescopic air duct, and an outer ventilation hood. Two filters, two air flow rectifiers and a ceramic regenerator are installed in the inner duct of the telescopic air duct. The air filters are designed to purify supply air and prevent foreign objects from ingress into the heat exchanger and the fan.
  2. The ceramic regenerator utilities extract air heat energy to warm up supply air flow. The cord laid inside the regenerator is designed to pull the regenerator from the air duct. The heat exchanger is heat insulated with a special insulating material.
  3. The outer ventilation hood is used to prevent direct ingress of water and other objects to the ventilator.

VENTILATOR DESIGN

VENTS TwinFresh Comfo RB-50 Single-Room Reversible
Energy Recovery Ventilator 4

Ventilation unit

Generates air flow by means of the fan rotation. The ventilation unit is covered with a ventilation grille on the inner wall side to prevent ingress of foreign objects into the fan. The ventilation unit is equipped with automatic shutters to prevent air backflow. The air shutters open during operation of the ventilator and close when the unit is turned off.

  • Inner air duct Inner part of the telescopic air duct.
  • Ceramic regenerator Utilises extract air heat energy to warm up supply air flow.
  • Outer air duct Outer part of the telescopic air duct.

Openings for the humidity sensor

Provide contact of air with the humidity sensor that controls indoor humidity level.

Ventilator power indicator

Shows operating status of the ventilator.

Filter replacement indicator

Indicates the need to replace the filter.

Infra-red receiver and light sensor

Responds to signals from the remote control and detects illumination level to activate/deactivate the night mode.

The indoor unit is equipped with automatic shutters. During the ventilator operation the automatic shutters are opened and let the air flow freely through the ventilator. The automatic shutters are closed for 2 minutes at the ventilator shut down.

A ventilator is off — the automatic shutters are closedVENTS TwinFresh
Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator
5

A ventilator is on — the automatic shutters are openedVENTS TwinFresh
Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator
6

The ventilator has four ventilation modes

  • Natural air supply. The automatic shutters are opened, the fan is idle.
  • Air supply. The ventilator supplies fresh air to the premise.
  • Ventilation. The ventilator operates in permanent supply or extract mode at a set speed depending on the CN7 jumper position.
  • Regeneration. The ventilator operates in reversible mode with heat and humidity recovery.

In the Regeneration mode the ventilator operates in two cycles, 70 seconds each.
Cycle I. Warm stale air is extracted from the room. As it flows through the ceramic regenerator, it heats and moisturizes the regenerator, transferring up to 90 % of heat energy. In 70 seconds as the ceramic regenerator gets warmed the ventilator is switched to the supply mode.
Cycle II. Fresh intake air from outside flows through the ceramic regenerator, absorbs accumulated moisture and is heated up to the room temperature. In 70 seconds as the ceramic regenerator gets cooled down, the ventilator is switched to the exhaust mode and the cycle is renewed.

MOUNTING AND SET-UP

  • READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
  • DO NOT BLOCK THE AIR DUCT OF THE INSTALLED VENTILATOR WITH DUST ACCUMULATING MATERIALS, SUCH AS CURTAINS, CLOTH SHUTTERS, ETC.
    AS IT PREVENTS AIR CIRCULATION IN THE ROOM.
  1. Prepare a round core hole in the outer wall. The hole size is shown in the figure below.
  2. While preparing core holes it is recommended to make preparations for layout of the power cable and other required cables. Use the supplied cardboard template to mark the relative position of the duct opening and cable exit points.VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator 7
  3. Insert the air duct in the wall. For ease of installation use the mounting wedges included in the delivery set. The air duct end must protrude for distance A which enables the installation of an outer ventilation hood. The distance A is stated in the installation instruction for the ventilation hood.VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator 8
  4. Remove the mounting plate to access the control board. It is necessary for the connection of the ventilator to the power supply and connection of other ventilators as stated in the “Connection to power mains” section, page 10.
  5. To remove the mounting plate, unscrew the four self-tapping screws as shown in the figure below. Then disconnect the mounting plate from the unit with care and push it aside to enable access to the control board. While doing that avoid abrupt movements not to damage the connecting cables between the control board and the mounting plate. Disconnect the mounting plate from the ventilation unit by disconnecting the two connectors. Assemble the mounting plate unit in reverse order. Install the cables with care.VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator 9
  6. Using the cardboard template supplied, mark the holes for attaching the ventilator as shown in the figure below. Drill the holes and insert the dowels. Install the mounting plate unit on the wall, while laying a sealing gasket under it, fix the unit with self-tapping screws from the mounting kit. Install the mounting plate back with the connectors in place and secure it with four screws.VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator 10
  7. Install the air flow rectifier, filter, ceramic regenerator, one more filter and one more air flow rectifier inside the telescopic air duct. Then install the ventilation unit on the mounting plate unit.VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator 11

Insert the air duct into the wall as shown in the picture on the left. Install the air duct with a minimum slope of 3 mm down towards the street. On the outer wall side the air duct end must protrude to a distance that enables the installation of the outer ventilation hood. Distance A is stated in the installation instruction for the ventilation hood. The air duct length can be changed before and after its fixation in the wall. In the former case, calculate the required length before mounting and in the second case, be sure to have enough access to cut the air duct length after its installation.

CONNECTION TO POWER MAINS

  1. DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
  2. CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER CAREFUL READING OF THE PRESENT USER’S MANUAL.
  3. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL. ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
  • The ventilator is rated for connection to single-phase AC 1~100-230 V 50/60 Hz power mains.
  • Connect the ventilator to power mains through the external automatic circuit breaker with a magnetic trip integrated into the fixed wiring system.
  • The power cable is connected to the upper terminal block. The neutral is connected directly to the corresponding socket of the terminal block, and the phase wire is connected to the wire from the fuse holder using the supplied insulated end cap. For connection, insert the two stripped wires into the cap and crimp them with a special tool.VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator 12

Ventilation mode setting

Air direction in the Ventilation mode is determined by position of the jumper on the control board. The circuit board of the controller is located inside the ventilation unit.

Connection of several ventilators in series

  • When the ventilators are connected in series, all the connected ventilators are controlled with the first ventilator and remote control. To connect the ventilators in series, connect the control terminals with a cable as shown in the diagram below. Connect the second ventilator with the third ventilator in the same way, etc.
  • For connection, use a screened cable with a wide cross-section of at least 0.25 mm2 (not included in the delivery set).
  • When the ventilators are connected in series, power must be supplied separately to each of them.VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator 14

ALL THE CONNECTED IN-SERIES VENTILATORS MUST BE GROUNDED!

CONTROL

The ventilator is operated with a remote control or the buttons on the ventilator casing, see the figure below. The operation buttons on the ventilator casing have limited functionality and include activating the second and third speed and setting three of four ventilation modes. The remote control has wider control capabilities. The guaranteed minimum reach distance of the remote control is 3 m. The IR receiver is located at the bottom of the fan assembly. Please consider the location of the port while using the remote control. In case of power failure, the ventilator reverts to the previous operation mode after power supply resumption.VENTS TwinFresh Comfo RB-50
Single-Room Reversible Energy Recovery Ventilator 15

REMOTE CONTROL

When connected in series, the ventilators operate depending on the position of the jumper for setting the Ventilation mode on the control board. The setting of the Ventilation mode is described on page 11.VENTS TwinFresh Comfo RB-50
Single-Room Reversible Energy Recovery Ventilator 16

REMOTE CONTROL OF THE VENTILATION UNIT

Set the speed switch to position and the operation mode switch to position to enable remote control of the ventilation unit.

Turning the ventilator on/off

ON/OFF

Night mode

ON/OFF

If the Night mode is activated, the ventilator switches to the first speed in the dark time of the day when the light is turned off. Activation of the night mode is confirmed by a long sound signal. Exiting the night mode is confirmed by a short sound signal.

Speed changeover

  1. First speed
  2. Second speed
  3. Third speed.

Operation mode

  • Natural air supply mode. The room is ventilated in a natural way, the fan is off.
  • Air supply mode. Air is supplied to the room at a set speed. All the connected in-series ventilators operate in supply mode with no reference to the CN7 jumper position.
  • Ventilation mode. Air is extracted (factory setting) or supplied at a selected speed. All the ventilators connected in series operate depending on the position of the CN7 jumper.
  • Regeneration mode. The ventilator operates for 70 seconds in the supply mode and 70 seconds in the exhaust mode. Heat recovery is also performed in this mode.

Humidity Control mode

The humidity control may be activated in the Regeneration mode only by pressing one of the humidity control buttons. in the Humidity Control mode the ventilator humidity sensor monitors the extracted air humidity and controls the fan speed depending on the difference between the set humidity point and actual indoor humidity. If indoor humidity is about the set range or has slight deviations, the ventilator operates with the second speed. If indoor humidity is above the set humidity point, the ventilator changes to the third speed. If indoor humidity is below the set humidity point, the ventilator changes to the first speed.

  • Humidity threshold – 45 %
  • Humidity threshold – 55 %
  • Humidity threshold – 65 %

THE HUMIDITY CONTROL FUNCTION MAY BE ACTIVATED WITH THE REMOTE CONTROL ONLY!

TECHNICAL MAINTENANCE

DISCONNECT THE UNIT FROM THE POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS! ENSURE THAT THE UNIT IS SWITCHED OFF FROM THE SUPPLY MAINS BEFORE REMOVING THE GUARD.

Maintenance of the ventilator means regular cleaning of the ventilator surfaces of dust and cleaning and replacement of the filters.

Heat exchanger and filter maintenance (3-4 times per year)

  1. Remove the ventilation unit.
  2. Remove the air flow rectifier.
  3. Remove the filter upstream of the regenerator.
  4. Pull the regenerator cord to remove the regenerator from the air duct.
  5. Be careful while pulling the regenerator to avoid its damage.
  6. Remove the filter downstream of the regenerator.

Clean the filters as often as required, but at least 3 times a year

  • After completion of the period set for the motor hour meter (factory setting 90 days) the filter replacement indicator in the bottom of the mounting plate (see page 7) glows to indicate the need of the filter cleaning of replacement.
  • Wash the filters, let those dry out and install the dry filters inside the air duct.
  • Vacuum cleaning is allowed.
  • The filter rated service life is 3 years.
  • For new filters contact the Seller.

Some dust may accumulate on the regenerator block even in case of regular maintenance of the filtersVENTS TwinFresh Comfo RB-50 Single-Room Reversible
Energy Recovery Ventilator 21

  • Clean the heat exchanger regularly to ensure its high heat recovery efficiency.
  • Vacuum clean the regenerator not less than once a year.

Fan inspection (once per year)VENTS TwinFresh Comfo RB-50 Single-Room
Reversible Energy Recovery Ventilator 22

  • Take off the ventilation unit and clean the fan blades.
  • Remove dust using a soft brush, cloth or a vacuum cleaner.
  • Do not use water, abrasive detergents, solvents, sharp objects for cleaning.
  • The impeller blades must be cleaned once a year.

To reset the operating hours counter after installing filters and a regenerator in the ventilator, press and hold the button for 10 seconds. The red indicator, indicating that the filter is dirty, should go out.

Replacement of the remote control battery (if necessary)

  1. Replace the battery of the remote control after prolonged use. No response of the ventilator for pressing the remote control buttons indicates the need to replace the battery.
  2. The battery type is CR2025.
  3. To replace the battery of the remote control, remove the battery holder with a battery.
  4. Replace the battery and install the holder with a new battery back to the remote control.

TROUBLESHOOTING

POSSIBLE MALFUNCTIONS AND TROUBLESHOOTING

Problem Possible reasons Troubleshooting


When switching on the ventilator, the fan does not start.

| ****

No power supply.

| Make sure the power supply line is connected correctly, otherwise troubleshoot a connection error.
The fuse has blown.| Replace the fuse with a new one (2.5 A, 250 V, 5*20 mm).
The motor is jammed, the impeller blades are soiled.| Turn the ventilator off. Troubleshoot the motor jam and impeller clogging. Clean the blades. Turn the ventilator on.
Circuit breaker tripping during the ventilation unit start-up.| Overcurrent as a result of short circuit in the electric line.| Turn the ventilator off.

Contact the Seller for further information.



Low air flow.

| Low set fan speed.| Set higher speed of the fan.


The filters, the fan or the regenerator are clogged.

| ****

Clean or replace the filter. Clean the fan and the heat exchanger.


Noise, vibration.

| The impeller is clogged.| Clean the impeller.
Loose screw connection of the unit casing or the outer ventilation hood.| Tighten the screws of the ventilator or the outer ventilation hood.

STORAGE AND TRANSPORTATION REGULATIONS

  • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with a temperature range from +5 °C to + 40 °C and relative humidity up to 70 %.
  • The storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
  • Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
  • Follow the handling requirements applicable for the particular type of cargo.
  • The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
  • Avoid sharp blows, scratches, or rough handling during loading and unloading.
  • Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3- 4 hours.

MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of the Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following a test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to the elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.

The warranty repair does not include

  • routine technical maintenance
  • unit installation/dismantling
  • unit setup
    • To benefit from a warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.

The manufacturer’s warranty does not apply to the following cases

  • User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
  • Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
  • User’s failure to ensure timely technical maintenance of the unit.
  • External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
  • Redesign or engineering changes to the unit.
  • Replacement and use of any assemblies, parts and components not approved by the manufacturer.
  • Unit misuse.
  • Violation of the unit installation regulations by the user.
  • Violation of the unit control regulations by the user.
  • Unit connection to power mains with a voltage different from the one stated in the user’s manual.
  • Unit breakdown due to voltage surges in power mains.
  • Discretionary repair of the unit by the user.
  • Unit repair by any persons without the manufacturer’s authorization.
  • Expiration of the unit warranty period.
  • Violation of the unit transportation regulations by the user.
  • Violation of the unit storage regulations by the user.
  • Wrongful actions against the unit were committed by third parties.
  • Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
  • Missing seals if provided by the user’s manual.
  • Failure to submit the user’s manual with the unit purchase date stamp.
  • Missing payment paperwork certifying the unit purchase.
  1. FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-FREE OPERATION OF THE UNIT.
  2. USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.

CERTIFICATE OF ACCEPTANCE

Unit Type Single-room reversible energy recovery ventilator
Model TwinFresh Comfo __
Serial Number
Manufacture Date

Quality Inspector’s Stamp

|

SELLER INFORMATION

Seller|
---|---
Address|
Phone Number|
E- mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|

INSTALLATION CERTIFICATE

The TwinFresh Comfo __  unit is installed pursuant to the requirements stated in the present user’s manual.

Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:|

WARRANTY CARD

Unit Type Single-room reversible energy recovery ventilator
Model TwinFresh Comfo __
Serial Number
Manufacture Date
Purchase Date
Warranty Period
Seller

Documents / Resources

| VENTS TwinFresh Comfo RB-50 Single-Room Reversible Energy Recovery Ventilator [pdf] User Manual
TwinFresh Comfo RB-50, TwinFresh Comfo RB1-50, TwinFresh Comfo RB-85, TwinFresh Comfo RB1-85, Single-Room Reversible Energy Recovery Ventilator
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals