The AQUA Ring detector allows detection of motion in the protected area. This manual applies to the detector with electronics version 3.0 (or newer) and firmware version 3.00 (or newer).
FEATURES
- Quad element pyrosensor.
- Digital motion detection algorithm.
- Digital temperature compensation.
- Selectable detection sensitivity.
- Built-in EOL resistors (Double EOL).
- LED alarm indicator.
- Supply voltage control.
- Tamper protection against cover removal.
DESCRIPTION
After motion is sensed by the detector in the coverage area, the alarm relay contacts will open for 2 seconds. Supply voltage control In the event of the voltage drop below 9 V (± 5%) for more than 2 seconds, the detector will signal a trouble. The trouble is indicated by the activation of alarm relay and the steady red light of LED indicator. The trouble signaling will continue as long as the trouble persists.
Electronics board
-
Terminals:
-
NC – alarm output (NC relay).
-
TMP – tamper output (NC).
-
COM – common ground.
-
12V – power input.
-
Red color LED to indicate:
-
Alarm – ON for 2 seconds;
-
Warm-up – blinking slowly;
-
Low supply voltage – ON.
-
Configuration pins for detector outputs:
-
The built-in resistors are to be used – place the jumpers as shown in Fig. 2 (connect the outputs as shown in Fig. 6)
-
The built-in resistors are not to be used – place the jumpers as shown in Fig. 3 (connect the outputs as shown in Fig. 7).
-
Pyrosensor: Do not touch the pyroelectric sensor,so as not to soil it.
-
Tamper switch (NC).
-
Fixing screw hole .
-
Detector configuration pins:
-
PIR SENS – selecting the PIR sensor sensitivity – see: Fig. 4 (A – low sensitivity, B and C – medium sensitivity,D – high sensitivity).
-
LED ON/OFF – enable/disable the LED indicator (jumper installed – LED enabled; jumper removed – LED disabled).
INSTALLATION
Warning: Disconnect power before making any electrical connections.
- Remove the cover (Fig. 5).
- Remove the electronics board.
- Make the openings for screws and cable in the enclosure base.
- Pass the cable through the prepared opening.
- Secure the enclosure base to the ceiling.
- Fasten the electronics board.
- Connect the wires to the corresponding terminals.
- Using the jumpers, set the detector working parameters.
- Replace the cover.
START-UP AND WALK TEST
Note: When testing the detector, the LED should be enabled.
- Power-up the detector. The LED will start blinking, which indicates the detector warm-up.
- When the LED stops blinking, check that moving within the coverage area will activate the alarm relay and make the LED light up.
- If necessary, change the detector sensitivity (pins PIR SENS.).
SPECIFICATIONS
- Supply voltage : 12 V DC ±15%
- Standby current consumption: 7.5 mA
- Maximum current consumption: 8.5 mA
- EOL resistors: 2 x 1.1 kΩ
- Relay contacts rating (resistive load): 40 mA / 16 V DC
- Alarm signaling period: 2 s
- Warm-up period: 45 s
- Detectable speed: 0.3…3 m/s
- Environmental class according: to EN50130-5 II
- Operating temperature range: -30…+55 °C
- Maximum humidity: 93±3%
- Recommended installation height from 2.2 m to 4.5 m
- Coverage area: 36 m
- when mounted at a heigh t of 2.6 m
- Coverage area: 80 m2
- when mounted at a height of 4.5 m
- Dimensions: ø97 x 29 mm
- Weight :54 g