Honeywell Home Pro TH2000DV Series Programmable Thermostats Installation Guide
- June 5, 2024
- Honeywell Home
Table of Contents
Honeywell Home Pro TH2000DV Series Programmable Thermostats
View all Honeywell Home thermostat manual
This manual covers the following models
- TH1100DV: For Heat only systems
- TH2110DV/TH1110DV: For 1 Heat/1 Cool systems
- TH2210DV/TH1210DV: For 2 Heat/1 Cool heat pump systems only
(Pull thermostat from wallplate and turn over to find model number.)
System Types
TH2110DV/TH1110DV:
- Gas, oil, or electric heat with air conditioning
- Warm air, hot water, high-efficiency furnaces, 1 Heat/1 Cool heat pumps, steam, gravity
- Heat only
- Heat only with fan
- Cool only
- 750 mV heating systems
TH2210DV/TH1210DV:
- 2 Heat/1 Cool heat pumps
TH1100DV:
- Gas, oil, or electric heat
- Warm air, hot water, steam, gravity
- Heat only
- 750 mV heating systems
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions can
damage the product or cause a hazardous condition.
Wallplate installation
Pull at the bottom to remove the thermostat from the wallplate.
Remove the wallplate from the thermostat as shown at left, then follow the directions below for mounting.
- Pull wires through wire holes.
- Position wallplate on wall, level and mark hole positions with a pencil.
- Drill holes at marked positions as shown below, then tap in supplied wall anchors.
- Place wallplate over anchors, insert and tighten mounting screws.
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube,
do not place the old control in the trash. Contact the Thermostat Recycling
Corporation at www.thermostat-recycle.org or
800-238-8192 for information on how and
where to properly and safely dispose of your old thermostat.
Power options
Wiring
TH2110DV/TH1110DV:
- Changeover valve energized in heating
- Changeover valve energized in cooling Fan relay
- Compressor contactor
- Heat relay
- 24 Vac common. For 2-transformer systems, use common wire from the cooling transformer.
- 24 Vac power from heating transformer
- Rc 24 Vac power from the cooling transformer
TH2210DV/TH1210DV:
- Changeover valve energized in heating
- Changeover valve energized in cooling
- Fan relay
- Compressor contactor
- Aux/E Auxiliary heat relay C 24 Vac common R
- 24 Vac power
TH1100DV:
- W Heat relay
- C 24 Vac common
- R 24 Vac power
Installation Guide
Wiring guide — conventional and heat pump systems
NOTES:
Wire specifications: Use 18- to 22-gauge thermostat wire. A shielded cable
is not required.
- Power supply. Provide disconnect means and overload protection as required.
- Remove jumper for 2-transformer systems.
- Optional 24 Vac common connection.
- The common connection must come from the cooling transformer.
- Use either O or B terminals for the changeover valve.
- Use a small piece of wire (not supplied) to connect W and Y terminals.
- Set fan operation switch to Heat Pump (see page 5).
Fan operation settings
TH2110DV/TH1110DV only:
- Gas or Oil: For gas or oil heating systems, leave the fan operation switch in this factory-set position. (This setting is for systems that control the fan in a call for heat.)
- Electric or Heat Pump: Change the switch to this setting for heat pump or electric heat systems.(This setting is for systems that allow the thermostat to control the fan in a call for heat, if a fan wire is connected to the G terminal.)
Thermostat mounting
Align the thermostat with the tabs on the wallplate, then push gently until
the thermostat snaps in place.
Installer setup
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
To begin, press and hold the and buttons until the display changes
.
- Press the or button to change the setting.
- Press the and buttons simultaneously for one second to
- advance to the next function.
- Press and hold the and buttons to exit and save settings.
- NOTE: If you do not press any button for 60 seconds while you are in the setup menu, the thermostat automatically saves any changes made and exits the menu.
Setup function
- 5 Heating cycle rate
- (CPH: cycles/hour)
- (TH2110DV, TH1110DV and TH1100DV)
- 6 Auxiliary heat
- cycle rate (CPH)
- (TH2210DV and TH1210DV)
- 9 Compressor cycle rate (CPH) (TH2110DV, TH2210DV, TH1110DV, TH1210DV)
- 13 Early Start (TH2110DV and TH2210DV)
- 14 Temperature display
- 15 Compressor protection
- (TH2110DV, TH2210DV, TH1110DV, TH1210DV)
- 20 Clock display (TH2110DV and|
- TH2210DV)
- 25 Lower temperature range (TH1100DV only)
- 40 Restore program
Settings & options (factory default in bold)
- For gas or oil furnaces of less than 90% efficiency For steam or gravity systems
- For hot water systems & furnaces of over 90% efficiency For electric furnaces
- [Other cycle rate options: 2 or 4 CPH]
- For hot water systems & furnaces of over 90% efficiency
- For steam or gravity systems
- For gas or oil furnaces of less than 90% efficiency For electric furnaces
- [Other cycle rate options: 2 or 4 CPH]
- Recommended for most compressors
- [Other cycle rate options: 1, 2, 4, 5, or 6 CPH]
- On **See page 8 Off
- Fahrenheit Celsius
- Five-minute compressor off time (See page 8) No compressor off time
- 12-hour display 24-hour display
- Standard range 40°F to 90°F (4.5°C to 32°C) Lower range (for garage mode) 35°F to 90°F
- (1.5°C to 32°C)
- Off
- On-program schedule default settings are listed in the operating manual
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage,
avoid cycling the compressor quickly.
CAUTION: ELECTRONIC WASTE NOTICE
The product and batteries should not be disposed of with other household
waste. Check for the nearest authorized collection centers or authorized
recyclers. The correct disposal of end-of-life equipment will help prevent
negative consequences for the environment and human health.
FCC statement at: https://customer.resideo.com/en-US/support/residential
/codes-andstandards/FCC15105/Pages/default.aspx
Special functions
Early Start (Setup Function 13): Early start allows the heating or cooling to
turn on before the program start time, so the temperature is reached at the
time you set.
Compressor Protection (Setup Function 15): Forces the compressor to wait a few
minutes before restarting, to prevent damage. During the wait time, the
message Cool On or Heat On (heat pumps only) will flash on the display.
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Cover plate assembly Part Number 50002883-001 *Use to cover marks left by old
thermostats.
Specifications
Temperature Ranges
- Heat: 40° to 90°F (4.5° to 32°C)
- Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature
- 32° to 120°F (0° to 48.9°C)
Shipping Temperature
- -20° to 120°F (-28.9° to 48.9°C)
Operating Relative Humidity
- 5% to 90% (non-condensing)
Physical Dimensions
- 3-7/16”H x 4-10/16”W x 1-3/16”D 87mm H x 119mm W x 30mm D
Electrical Ratings
- System Voltage (50/60Hz) Running Current
- Heat (1st stage) 20-30 Vac 0.02-1.0 A
- (Powerpile) 750 mV DC 100 mA DC
- Auxiliary heat 20-30 Vac 0.02-1.0 A
- Cooling 20-30 Vac 0.02-1.0 A
References
- condition.pro
- Switch the 'Stat – Stewardship Program Focused on Recovering and Recycling Thermostat
- Home - Thermostat Recycling Corporation (TRC)
- Support Materials & Resources | Resideo
- Support & Resources for Residential Professionals | Resideo
- FCC Rules Part 15: Residential Codes & Standards | Resideo
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>