Milesight UC51x Series LoRaWAN Solenoid Valve Controller User Guide

June 5, 2024
Milesight

Milesight UC51x Series LoRaWAN Solenoid Valve Controller

Safety Precautions

Milesight will not shoulder responsibility for any loss or damage resulting from not following the instructions of this operating guide. The device must not be remodeled in any way. Do not place the device close to objects with naked flames. Do not place the device where the temperature is below/above the operating range. Make sure electronic components do not drop out of the enclosure while opening. When installing the battery, please install it accurately, and do not install the reverse or
wrong model. The device must never be subjected to shocks or impacts.

Declaration of Conformity

UC51x series is in conformity with the essential requirements and other relevant provisions of the CE, FCC, and RoHS.


Copyright©2011-2022 Milesight. All rights reserved.

All information in this guide is protected by copyright law. Whereby, no organization or individual shall copy or reproduce the whole or part of this user guide by any means without written authorization from Xiamen Milesight IoT Co., Ltd.

For assistance, please contact Milesight technical support:
Email: iot.support@milesight.com
Tel: 86-592-5085280 Fax: 86-592-5023065
Address: Building C09, Software Park III, Xiamen 361024, China

Revision History
Date Doc Version Description
Feb. 20, 2021 V 1.0 Initial version
Nov.26, 2021 V 1.1 Description Update
March 10, 2021 V 2.0 Update based on 2.0 hardware

Product Introduction

Overview

UC51x series LoRaWAN® wireless solenoid valve controller is a device used to remotely control DC latching solenoids of the valve. It contains 2 solenoid interfaces and 1 pulse interface, which can be easily controlled locally or remotely.
Besides ultra-low-power LoRaWAN® technology, UC51x series also provides both solar and built-in battery power supply for uninterrupted operation. For outdoor applications, it equips with IP67-rated enclosure and M12 connectors to protect from water and dust under harsh environments.

Features
  • Compatible with standard DC latching solenoids
  • OPEN/CLOSE control by mobile App locally or commands remotely
  • Two pulse water meter interfaces for flow monitoring
  • Transmission distance up to 15 km with line of sight
  • Waterproof design including IP67 case and M12 connectors
  • Solar powered and built-in chargeable battery
  • Quick wireless configuration via NFC
  • Time and flow control via Milesight IoT Cloud

Hardware Introduction

Packing List

If any of the above items is missing or damaged, please contact your sales Representative.

Hardware Overview

Interface 1 &2:

Pin Description
1 DC+/OUT1(Red) of Solenoid Valve
2 DC-/OUT2 (Black) of Solenoid Valve
3 GND
4 INSERT BOOT1
5 GND
6 GPIO for pulse meter connection

Power Button
Function Action LED Indication
Turn On Press and hold the button for more than 3s. Off → On
Turn Off Press and hold the button for more than 3s. On → Off
Reset Press and hold the button for more than 10s. Blinks.
Check On/Off Status **** Quickly press the power button. Light On: Device

is on.
Light Off: Device is off.

Dimensions (mm)

Operation Guide

Log in the ToolBox

UC51 series can be monitored and configured via ToolBox App or ToolBox software. Please select one of them to complete configuration.

NFC Configuration
  1. Download and install “Milesight ToolBox” App from Google Play or Apple App Store.

  2. Enable NFC on the smartphone and launch Milesight ToolBox.

  3. Attach the smartphone with NFC area to the device to read basic information.

  4. Basic information and settings of devices will be shown on ToolBox if it’s recognized successfully. You can turn on/off the device by tapping the button on the Device Status. In order to protect the security of devices, password validation is required when first configuration. Default password is 123456.

  5. Tap “Read” button to check current status of device. 6

  6. Tap “Write” button to write all your settings to the device.

Note:

  1. Ensure the location of smartphone NFC area and it’s recommended to take off phone case.
  2. If the smartphone fails to read/write configurations via NFC, keep the phone away and back to try again.
  3. UC51x series can also be configured by dedicated NFC reader, which can be purchased from Milesight IoT.
USB Configuration
  1. Download ToolBox from Milesight IoT website.

  2. Open the case of UC51x and connect the UC51x to computer via type-C port.

  3. Open the ToolBox and select type as “General”, then click password to log in ToolBox. (Default password: 123456)

  4. After logging in the ToolBox, you can click “Power On” or “Power Off” to turn on/off device and change other settings.

Solenoid Valve Control

Solenoid valve can be controlled by ToolBox App or ToolBox software locally. Via ToolBox Software:
Click “Open” or “Close” button on the “Status” page to change the status of solenoid valves.

Via ToolBox App:
Click buttons of Valve Status on the “Device -> Status” page, then attach the smart phone to device to change the status of solenoid valves.

LoRaWAN Settings

LoRaWAN settings is used for configuring the transmission parameters in LoRaWAN® network.
Basic LoRaWAN Settings:
Go to “LoRaWAN Settings - > Basic” of ToolBox software or “Setting - > LoRaWAN Settings” of ToolBox App to configure join type, App EUI, App Key and other information. You can also keep all settings by default.

Parameters Description
Device EUI Unique ID of the device which can also be found on the label.
App EUI Default App EUI is 24E124C0002A001.
Application Port The port used for sending and receiving data, default port

is 85.
Join Type| OTAA and ABP mode are available.
LoRaWAN Version| V1.0.2, V1.0.3, V1.1 are available.
Application Key| Appkey for OTAA mode, default is 5572404C696E6B4C6F52613230313823.
Device Address| DevAddr for ABP mode, default is the 5th to 12th digits of SN.
Network Session Key| Nwkskey for ABP mode, default is 5572404C696E6B4C6F52613230313823.
Application Session Key| Appskey for ABP mode, default is 5572404C696E6B4C6F52613230313823.
RX2 Data Rate| RX2 data rate to receive downlinks.
RX2 Frequency| RX2 frequency to receive downlinks. Unit: Hz
Spread Factor| If ADR is disabled, the device will send data via this spread factor.
Confirmed Mode| If the device does not receive ACK packet from network server, it will resend data 3 times at most.
Rejoin Mode| Reporting interval ≤ 30 mins: the device will send specific mounts of LoRaMAC packets to check connection status every 30 mins; If no reply after specific packets, the device will re-join.
Reporting interval > 30 mins: the device will send specific mounts of LoRaMAC packets every to check connection status every reporting interval;
If no reply after specific packets, the device will re-join.
ADR Mode| Allow network server to adjust datarate of the device.
Tx Power| Tx power of the device.

Note:

  1. Please contact sales for device EUI list if there are many units.
  2. Please contact sales if you need random App keys before purchase. 
  3. Select OTAA mode if you use Milesight IoT cloud to manage devices.
  4. Only OTAA mode supports rejoin mode.
LoRaWAN Frequency Settings:

Go to “LoRaWAN Settings- > Channel” of ToolBox software or “Setting - > LoRaWAN Settings” of ToolBox APP to select supported frequency and select channels to send uplinks. Make sure the channels match the LoRaWAN® gateway.

If frequency is one of CN470/AU915/US915, you can enter the index of the channel that you want to enable in the input box, making them separated by commas.
Examples:
1, 40: Enabling Channel 1 and Channel 40
1-40: Enabling Channel 1 to Channel 40
1-40, 60: Enabling Channel 1 to Channel 40 and Channel 60
All: Enabling all channels
Null: Indicates that all channels are disabled

Note:
For -868M model, default frequency is EU868;
For -915M model, default frequency is AU915.

Solenoid Settings

Go to “Device Settings - > Basic” of ToolBox software or “Setting - > General Settings” of ToolBox App to change the reporting configurations.

Parameters Description
Reporting Interval Reporting interval of transmitting data to network server.

Default: 20min, Range: 1-1080 mins.
Solenoid Valve
Wiring Switch| After this parameter is enabled, when users connect the solenoid cable to any solenoid interface, the device will turn on automatically.
Data Reporting| Select the contents to report to network server. All: Report all interface status;
Valve 1 & Water Meter 1: Report the status of the Valve 1 interface and data of GPIO1;
Valve 2 & Water Meter 2: Report the status of the Valve 2 interface and data of GPIO2.
Device Return to Power Supply State| If the device loses power and return to power supply, the device will be on or off according to this parameter.
Class Type| Working mode of LoRaWAN® device.

UC511: Class A, Class B and Class C are available; UC512: Class A and Class B are available.

Response Time| When the device works under Class A mode, it only receives control commands every reporting interval comes. In order to shorten the delay time of control, the device will send blank package to allow to receive the control commands every Response Time interval.
Note:
The shorter the response time, the shorter the battery life.
Ping Slot Periodicity| When the device works under Class B mode, set the interval to open the reception window.
Change Password| Change the password for ToolBox App or software to read/write this device.

Note:

  1. When device connects to network server of Milesight gateway, the blank package will takeupthe frame count but not show on the package list.
  2. Reboot or re-join will not affect the counting
Schedule Settings

Go to “Device Settings - > Schedule” of ToolBox software or “Setting - > Schedule” of ToolBox App to configure the solenoid switch plans.

12

  1. Configure a plan as your request and enable it.
    Condition| Description
    ---|---
    Item| It supports adding 16 plans at most.
    Status| Enable or disable this plan.
    Initial State of

Solenoid Valve

| Control the solenoid to open or close the valve during the plan.
Start Time/End Time| Set the time range to execute this plan.
Water Volume (Pulses)| Set the amount of water flow through the valve during this plan, 0 means this condition will not work.
Note: either time or water volume reaches the condition, the plan is completed and will stop executing.
Repeat| Set the regularly weekly schedule to execute this plan. If none is selected, the plan will only execute once.

2. Click “Write” to write the schedule plan setting into the device. 3. Click “Save Schedule” to backup the schedule plan settings as file; if you need to import this schedule from other devices, click “Read Schedule” to import the setting. 4. Click “Clear All” to reset all schedule plan settings in this device.

Note:

  1. Ensure the device time is correct. After joining the network, the network server will assign the time to the device. You can also manually sync the time via ToolBox or downlink commands.
  2. When the device has multiple schedule plan settings that are conflicted, the device will only execute one plan whose item number is largest.

Maintenance

Upgrade

ToolBox Software:

  1. Download firmware from www.milesight-iot.com to your PC. 2
  2. Go to “Maintenance - > Upgrade” of ToolBox software, click “Browse” to import firmware and upgrade the device. You can also click “Up to Date” to search for the latest firmware of the device and upgrade.

Mainntenance

ToolBox App:

  1. Download firmware from www.milesight-iot.com to your smartphone.
  2. Open ToolBox App and click “Browse” to import firmware and upgrade the device.

Note:

  1. Operation on ToolBox is not supported during the upgrade.
  2. Only Android version ToolBox supports the upgrade feature.
Backup

UC51x devices support configuration backup for easy and quick device configuration in bulk. Backup is allowed only for devices with the same model and LoRa frequency band. Note that the backup file will not save schedule setting, please backup plan setting on “Schedule” page. Please select one of following methods to backup device:

ToolBox Software:

  1. Go to “Maintenance - > Backup and Reset”, click “Export” to save current configuration as json format backup file.
  2. Click “Browse” to select backup file, then click “Import” to import the configurations.

ToolBox App:

  1. Go to “Template” page on the App and save current settings as a template. You can also edit the template file.
  2. Select this template and attach to another device to write configuration.
Reset to Factory Default

Please select one of following methods to reset device:
Via Hardware: Open the case of UC51x and hold on power button more than 10s.
Via ToolBox Software: Go to “Maintenance - > Backup and Reset” to click “Reset”.

Via ToolBox App: Go to “Device -> Maintenance” to click “Reset”, then attach smart phone with NFC area to UC51x to complete reset.

Installation

UC51x series support wall mounting or pole mounting. Before installation, make sure you have the mounting bracket, wall or pole mounting kits and other required tools.

Wall Mounting:

  1. Fix the wall plugs into the wall, then fix the mounting bracket to the wall plugs with screws.
  2. Put the device on the mounting bracket, then fix the bottom of the device to the bracket with a fixing screw.

Pole Mounting:

  1. Straighten out the hose clamp and slide it through the rectangular rings in the mounting bracket, wrap the hose clamp around the pole. After that use a screwdriver to tighten the locking mechanism by turning it clockwise.
  2. Put the device on the mounting bracket, then fix the bottom of the device to the bracket with a fixing screw.

Milesight IoT Cloud Management

UC51x series can be managed by Milesight IoT Cloud platform. Milesight IoT cloud is a comprehensive platform that provides multiple services including device remote management and data visualization with the easiest operation procedures. Please register a Milesight IoT Cloud account before operating following steps.

Add UC51x to Cloud
  1. Ensure Milesight LoRaWAN® gateway is online in Milesight IoT Cloud. For more info about connecting gateway to cloud please refer to gateway’s user guide.

  2. Go to “My Devices” page and click “+New Devices”. Fill in the SN of UC51x and select associated gateway.

  3. Click and go to “Basic Settings” to change class type the same as device settings.

    Besides, configure the unit of per pulse if you connect the water meter.

  4. Click and go to “Interface Settings” to select used interfaces and customize the name and thresholds.

Solenoid Valve Control

Solenoid valve can be controlled by Milesight IoT cloud webpage or App.

  1. Click to open the solenoid valve and configure the duration.

You can also add a switch on the dashboard to control the status of solenoid valves. 20

Note: If the working mode of UC51x is LoRaWAN® Class A, control commands will delay until the time icon disappear.

  1. Go to “Triggers” page to add actions to trigger the solenoid valve to open for a period of time or a specific volume of water.
    Note: Water volume control is only worked when you connect water meter to UC51x device.

Device Payload

UC51x Series use the standard Milesight IoT payload format based on IPSO. Please refer to the UC51x Series Communication Protocol; for decoders of Milesight IoT products please click here.

References