smartbitt 1.5K Online UPS System User Manual
- June 5, 2024
- smartbitt
Table of Contents
User Manual
1K/1.5K/2K/3K Online UPS
Uninterruptible Power Supply System
Version: 1.6
Important Safety Warning
Please comply with all warnings and operating instructions in this manual
strictly. Save this manual properly and read carefully the following
instructions before installing the unit. Do not operate this unit before
reading through all safety information and operating instructions carefully
1-1. Transportation
- Please transport the UPS system only in the original package to protect against shock and impact.
1-2. Preparation
- Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate to the environment.
- Do not install the UPS system near water or in moist environments.
- Do not install the UPS system where it would be exposed to direct sunlight or near a heater.
- Do not block ventilation holes in the UPS housing.
1-3. Installation
- Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
- Place cables in such a way that no one can step on or trip over them.
- Do not connect domestic appliances such as hair dryers to UPS output sockets.
- The UPS can be operated by any individual with no previous experience.
- Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
- Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
- Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
- When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.
1-4. Operation
- Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
- The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
- In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
- Prevent no fluids or other foreign objects from inside of the UPS system.
1-5. Maintenance, service and faults
-
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
-
Caution – Risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
-
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals
of high capability capacitors such as BUS-capacitors. -
Only persons who are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
-
Caution – Risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
-
Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
-remove wristwatches, rings, and other metal objects
-use only tools with insulated grips and handles. -
When changing batteries, install the same number and same type of batteries.
-
Do not attempt to dispose of batteries by burning them. This could cause a battery explosion.
-
Do not open or destroy batteries. Escaping electrolytes can cause injury to the skin and eyes. It may be toxic.
-
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
-
Do not dismantle the UPS system.
Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing
inside the package is damaged. Please keep the original package in a safe
place for future use.
NOTE: There are two different types of online UPS: standard and long-run
models. Please refer to the following model table.
Model | Type | Model | Type |
---|---|---|---|
1K | Standard | 1KL | Long-run |
1.5K | 1.5KL | ||
2K | 2KL | ||
3K | 3KL |
2-1. Rear panel view
1K(L) / 1.5K(L) TOWER
- Programmable outlets: connect to non-critical loads.
- Output receptacles: connect to mission-critical loads.
- AC input
- Input circuit breaker
- Network/Fax/Modem surge protection
- Emergency power-off function connector (EPO)
- USB communication port
- RS-232 communication port
- SNMP intelligent slot
- External battery connection (only available for L model)
- Output terminal
- Output circuit breaker
- Input terminal
2-2. Setup the UPS
Step 1: External battery connection (for long-run models only) Follow the
right chart to make external battery connection.
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid
using extension cords.
- For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package.
- For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input plug is a NEMA 5-15P for 1K, 1KL, 1.5K and 1.5KL models, NEMA 5-20P for 2K and 2KL models.
Note: For Low voltage models: Check if the site wiring fault indicator
lights up in the LCD panel. It will be illuminated when the UPS is plugged
into an improperly wired utility power outlet (Refer to Troubleshooting
section). Please also install a circuit breaker (40A) between the mains and AC
input in 3K model for safety operation.
Step 3: UPS output connection
- For socket-type outputs, there are two kinds of outputs: programmable outlets and general outlets. Please connect non-critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting a shorter backup time for non-critical devices.
- For terminal-type input or outputs, please follow the below steps for the wiring configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm2 power cords. Suggest using AWG12-10 or3.3mm2 -5.3mm2 power cords for NEMA type.
c) Upon completion of the wiring configuration, please check whether the wires are securely affixed.
d) Put the small cover back to the rear panel.
Step 4: Communication connection
Communication port:
To
allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable to one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with an intelligent slot perfect for either SNMP or AS400
card. When installing either SNMP or AS400 cards in the UPS, it will provide
advanced communication and monitoring options.
PS. USB port and RS-232 port can’t work at the same time.
Step 5: Network connection
Network/Fax/Phone surge port
Connect a single modem/phone/fax line into a surge-protected “IN” outlet on the back panel of the UPS unit. Connect from the “OUT” outlet to the equipment with another modem/fax/phone line cable.
Step 6: Disable and enable the EPO function
Keep pin 1 and pin 2 closed for UPS’s normal operation. To activate the EPO
function, cut the wire between pin 1 and pin 2.
Step 6: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the
UPS.
Note The battery charges fully during the first five hours of normal
operation. Do not expect full battery run capability during this initial
charge period.
Step 7: Install software
For optimal computer system protection, install UPS monitoring software to
fully configure UPS shutdown. You may insert provided CD into CD-ROM to
install the monitoring software. If not, please follow the steps below to
download and install monitoring software from the internet:
- Go to the website http://www.power-software-download.com
- Click the ViewPower software icon and then choose your required OS to download the software.
- Follow the on-screen instructions to install the software.
- When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.
Operations
3-1. Button operation
Button | Function |
---|---|
ON/Mute Button |
- Turn on the UPS: Press and hold the On/Mute button for at least 2 seconds to turn on the UPS.
- Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system. But it’s not applied to the situations when warnings or errors occur.
- Up key: Press this button to display the previous selection in UPS setting mode.
- Switch to UPS self-test mode: Press and hold the On/Mute button for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
OFF/Enter Button|
- Turn off the UPS: Press and hold this button for at least 2 seconds to turn off the UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enables setting by pressing this button.
- Confirm selection key: Press this button to confirm selection in UPS setting mode.
Select Button|
- Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery voltage, output voltage, and output frequency. It will return back to the default display when pausing for 10 seconds. Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or bypass mode.
- Down key: Press this button to display the next selection in UPS setting mode.
ON/Mute + Select
Button|
- Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS will enter to bypass mode. This action will be ineffective when the input voltage is out of acceptable range.
3-2. LCD Panel
Display | Function |
---|
Remaining backup time information
| Indicates the remaining backup time in pie chart.
| Indicates the remaining backup time in numbers.
H: hours, M: minute, S: second
Fault information
| Indicates that the warning and fault occur.
| Indicates the warning and fault codes, and the codes are listed in detail in
3-5 section.
Mute operation
| Indicates that the UPS alarm is disabled.
Output & Battery voltage information
| Indicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
Load information
| Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
| Indicates overload.
| Indicates the load or the UPS output is short circuit.
Programmable outlets information
| Indicates that programmable management outlets are working.
Mode operation information
| Indicates the UPS connects to the mains.
| Indicates the battery is working.
| Indicates the bypass circuit is working.
| Indicates
the ECO mode is enabled.
| Indicates the Inverter circuit is working.
| Indicates the output is working.
Battery information
| Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 76-100%.
| Indicates the battery is fault.
| Indicates low battery level and low battery voltage.
Input & Battery voltage information
| Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
3-3. Audible Alarm
Battery Mode | Sounding every 4 seconds |
---|---|
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
Bypass Mode | Sounding every 10 seconds |
3-4. LCD display wordings index
Abbreviation | Display content | Meaning |
---|---|---|
ENA | Enable | |
DIS | Disable | |
ESC | Escape | |
HLS | High loss | |
LLS | Low loss | |
BAT | Battery | |
CF | Converter | |
EP | EPO | |
TP | Temperature | |
CH | Charger | |
FU | Bypass frequency unstable | |
EE | EEPROM error |
3-5. UPS Setting
There are three parameters to set up the UPS.
Parameter 1: It’s for program alternatives. There are 10 programs to set up.
Refer to the below table. Parameter 2 and parameter 3 are the setting options
or values for each program.
- 01: Output voltage setting
Interface | Setting |
---|
|
Parameter 3: Output voltage
For 200/208/220/230/240 VAC models, you may choose the following output
voltage:
200: presents output voltage is 200Vac
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
For 100/110/115/120/127 VAC models, you may choose the following output
voltage:
100: presents output voltage is 100Vac
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac (Default)
127: presents output voltage is 127Vac
- 02: Frequency Converter enable/disable
Interface | Setting |
---|---|
Parameters 2 & 3: Enable or disable converter mode. You may choose the |
following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
- 03: Output frequency setting
Interface | Setting |
---|---|
Parameter 2 & 3: Output frequency setting. |
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following output frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
- 04: ECO enable/disable
Interface | Setting |
---|---|
Parameter 3: Enable or disable the ECO function. You may |
choose the following two options:
ENA: ECO mode enable
DIS: ECO mode disabled (Default)
- 05: ECO voltage range setting
Interface | Setting |
---|---|
Parameters 2 & 3: Set the acceptable high voltage point and low voltage |
point for ECO mode by pressing the Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2. For
200/208/220/230/240 VAC models, the setting range in parameter 3 is from +7V
to +24V of the nominal voltage. (Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in parameter 3 is from
+3V to +12V of the nominal voltage. (Default: +6V)
LLS: Low loss voltage in ECO mode in parameter 2. For 200/208/220/230/240
VAC models, the setting range in parameter 3 is from -7V to -24V of the
nominal voltage. (Default: -12V)
For 100/110/115/120/127 VAC models, the setting voltage in parameter 3 is from
-3V to -12V of the nominal voltage. (Default: -6V)
- 06: Bypass enable/disable when UPS is off
Interface | Setting |
---|---|
Parameter 3: Enable or disable the Bypass function. You may choose the |
following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
- 07: Bypass voltage range setting
Interface | Setting |
---|---|
Parameters 2 & 3: Set the acceptable high voltage point and acceptable |
low voltage point for Bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from 230Vac to
264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140: setting the high voltage point in parameter 3 from 120Vac to
140Vac(Default: 132Vac)
LLS: Bypass low voltage point For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from 170Vac to
220Vac (Default: 170Vac)
For 100/110/115/120/127 VAC models:
85-115: setting the low voltage point in parameter 3 from 85Vac to
115Vac. (Default: 85Vac)
- 08: Programmable outlets enable/disable
Interface | Setting |
---|---|
Parameter 3: Enable or disable programmable outlets. |
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
- 09: Programmable outlet setting
Interface | Setting |
---|
|
Parameter 3: Set up backup time limits for programmable outlets.
0-999: setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on battery mode.
(Default: 999)
- 10: Autonomy limitation setting
Interface | Setting |
---|
|
Parameter 3: Set up backup time on battery mode for general outlets.
0-999: setting the backup time in minutes from 0-999 for general outlets
on battery mode.
0: When setting as “0”, the backup time will be only 10 seconds.
999: When setting as “999”, the backup time setting will be disabled.
(Default)
- 00: Exit setting
3-6. Operating Mode Description
Operating mode | Description | LCD display |
---|---|---|
Online mode | When the input voltage is within an acceptable range, UPS will |
provide pure
and stable AC power to output. The UPS will also charge the battery at online
mode.|
ECO mode| Energy-saving mode:
When the input voltage is within the voltage regulation range, UPS will bypass
voltage to output for energy saving|
Frequency
Converter mode| When the input frequency is within 40 Hz to 70 Hz, the UPS can
be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still
charge the battery under this model.|
Battery mode| When the input voltage is beyond the acceptable range or power
failure and the alarm is sounding every 4 seconds, UPS will backup power from
the battery.|
Bypass mode| When the input voltage is within an acceptable range but UPS is
overloaded, UPS will enter bypass mode or bypass mode can be set by the front
panel. The alarm is sounding every 10 seconds.|
Standby mode| UPS is powered off and has no output supply power, but still can
charge batteries.|
3-7. Faults Reference Code
Fault event | Fault code | Icon |
---|---|---|
Bus start fail | 1 | x |
Bus over | 2 | x |
Bus under | 3 | x |
Bus unbalance | 4 | x |
Bus fault | 5 | x |
Inverter soft start fail | 11 | x |
Inverter voltage high | 12 | x |
Inverter voltage Low | 13 | x |
Inverter output short | 14 | |
Battery voltage too high | 27 | |
Battery voltage too low | 28 | |
Over-temperature | 41 | x |
Overload | 43 |
3-8. Warning indicator
Warning | Icon (flashing) | Alarm |
---|---|---|
Low Battery | Sounding every second | |
Overload | Sounding twice every second | |
The battery is not connected | Sounding every second | |
Over Charge | Sounding every second | |
Site wiring fault | Sounding every second | |
EPO enable | Sounding every second | |
Over-temperature | Sounding every second | |
Charger failure | Sounding every second | |
Battery fault | Sounding every second | |
Out of bypass voltage range | Sounding every second | |
Bypass frequency unstable | Sounding every second | |
EEPROM error | Sounding every second |
NOTE: “Site Wiring Fault” function can be enabled/disabled via software. Please check the software manual for the details.
Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom | Possible cause | Remedy |
---|---|---|
No indication and alarm even though the mains is normal. | The AC input power | |
is not connected well. | Check if the input power cord is firmly connected to |
the mains.
The AC input is connected to the UPS output.| Plug AC input power cord to AC
input correctly.
The icon and the warning code flash on the LCD display and the alarm is
sounding every second.| EPO function is activated.| Set the circuit in the
closed position to disable the EPO function.
The icon and flashing on the LCD display and the alarm is sounding every
second.| Line and neutral conductors of UPS input are reversed.| rotate mains
power socket by 180° and then connect to UPS system.
The icon and flashing on the LCD display and the alarm is sounding every
second.| The external or internal battery is incorrectly connected.| Check if
all batteries are connected well.
The fault code is shown as 27 and the icon is lit on the LCD display and the
alarm is continuously sounding.| The battery voltage is too high or the
charger is at fault.| Contact your dealer.
The fault code is shown as 28 and the icon is lit on the LCD display and the
alarm is continuously sounding.| The battery voltage is too low or the charger
is at fault.| Contact your dealer.
The icon and is flashing on the LCD display and the alarm is sounding twice
every second.| UPS is overload| Remove excess loads from UPS output.
UPS is overloaded. Devices connected to the UPS are fed directly by the
electrical network via the Bypass.| Remove excess loads from UPS output.
After repetitive overloads, the UPS is locked in the Bypass mode. Connected
devices are fed directly by the mains.| Remove excess loads from UPS output
first. Then shut down the UPS and restart it.
The fault code is shown as 43 The icon is lit on the LCD display and the alarm
is continuously sounding.| The UPS shut down automatically because of overload
at the UPS output.| Remove excess loads from UPS output and restart it.
The fault code is shown as 14 and the icon is lit on the LCD display and the
alarm is continuously sounding.| The UPS shut down automatically because a
short circuit occurs on the output.| Check output wiring and if connected
devices are in short circuit status.
---|---|---
Fault code is shown as 01, 02, 0304, 05, 11, 12, 13, and 41 on the LCD display
and the alarm is continuously sounding.| A UPS internal fault has occurred.
There are two possible results: 1. The load is still supplied, but directly
from AC power via bypass.
2. The load is no longer supplied by power.| Contact your dealer
Battery backup time is shorter than nominal value| Batteries are not fully
charged| Charge the batteries for at least 5 hours and then check capacity. If
the problem still persists, consult your dealer.
Batteries defect| Contact your dealer to replace the battery.
The fault code is shown as 05 on the LCD display. At the same time, an alarm
is continuously sounding and output is cut off| A UPS internal fault has
occurred and BUS is shortcircuit| Consult your dealer. If the UPS power is on
again before repair, the DC/DC MOSFET will damage.
Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life
(3~5 years at 25°C ambient temperature) has been exceeded, the batteries must
be replaced. In this
case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a
cool, dry location. During storage, recharge the battery in accordance with
the following table:
Storage Temperature | Recharge Frequency | Charging Duration |
---|---|---|
-25°C – 40°C | Every 3 months | 1-2 hours |
40°C – 45°C | Every 2 months | 1-2 hours |
Specifications
**CAPACITY*| 1000 VA / 800 W| 1500 VA / 1200 W| 2000 VA / 1600 W| 3000 VA
/ 2400 W
---|---|---|---|---
INPUT|
Voltage Range| Low Line Transfer| 160VAC/140VAC/120VAC/110VAC + 5 % or
80VAC/70VAC/60VAC/55VAC + 5 % ( based on load percentage 100% – 80 % / 80 % –
70 % / 70 – 60 % / 60 % – 0)
Low Line Comeback| 168 VAC + 5 % or 84 VAC + 5 %
High Line Transfer| 300 VAC + 5 % or 150 VAC + 5 %
High Line Comeback| 290 VAC + 5 % or 145 VAC + 5 %
Frequency Range| 40Hz ∼ 70 Hz
Phase| Single-phase with ground
Power Factor| ≥0.99 @ Nominal voltage (full load)
OUTPUT**
Output voltage| 200/208/220/230/240VAC or 100/110/115/120/127 VAC
AC Voltage Regulation| ± 1% (Batt. Mode)
Frequency Range (Synchronized Range)| 47 — 53 Hz or 57 — 63 Hz
Frequency Range (Batt. Mode)| 50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz
Overload| 100%-110°A): audible warning
110%-130%: UPS shuts down in 30 seconds at battery mode or transfers to bypass
mode when the utility is normal.
130%: UPS shuts down immediately at battery mode or transfer to bypass mode
when the utility is normal.
Current Crest Ratio| 3:01
Harmonic Distortion| ≤2 % THD (Linear Load)
≤ 4 % THD (Non-linear Load)
Transfer Time| AC Mode to Batt. Mode| Zero
Inverter to Bypass| 4 ms (Typical)
Waveform (Batt. Mode)| Pure Sinewave
EFFICIENC|
---|---
AC Mode| — 87%| — 90%
Batte Mode| — 83%| — 87%
BATTERY
Standard Model| Batte T lie| 12 V / 7 AH|
12 V / 9 AH
| 12 V / 7 AH| 12 V / 9 AH
Numbers| 3| 3| 6| 6
Rechar•e Time| 4 hours recover to 90% capacity (Typical)
Charging Current| 1.0 A(max.)
Charging Voltage|
41.0 VDC + 1%
| ! 82.1 VDC +1%
Long-run Model| Battery Type & Numbers| Depending on the capacity of external
batteries
Charging Current| 4.0 A or 8.0 A(max.)
Charging Voltage| 41.0 VDC + 1%| 82.1 VDC +1%
PHYSICAL
Dimension, D X W X H| 397 X 145 X 220 (mm)| 421 X 190 X 318 (mm)
Net Weight (kqs)| 13| 7| | 14| 7| 26| 13| 28| 13|
ENVIRONMENT
Operation Humidity| 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level| Less than 50dBA @ 1 Meter
---|---
MANAGEMENT
Smart RS-232 or USB| Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix
and MAC
Optional SNMP| Power management from SNMP manager and web browser
- Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100VAC, 200VAC or 208VAC.
** Product specifications are subject to change without further notice.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>