Drok 200444 Multi-Function Digital Meter Instruction Manual
- June 5, 2024
- Drok
Table of Contents
200444
Parameter:
Measure accuracy: 1% ± 2 words
Voltage: AC 80.0 – 300.0V
Current: AC 0 – 99.99A, minimum resolution is 0.01A
Active Power: 0 – 30000W
The minimum resolution of 0-9999.9W: 0.1W
The minimum resolution in other range: 1W
Electric energy: 0 – 99999kwh
The minimum resolution of 0 – 999.9kwh: 0.01kwh
The minimum resolution of 1000.0 – 9999.9kwh: 0.1kwh
The minimum resolution of 10000.0 – 99999kwh: 1kwh
Power frequency: 45.0Hz – 65.0Hz
Power factor: 0.00 – 1.00PF
Speed: 2 times / second
Size: 79 43 48mm
Installation size: 76 * 39mm
Auto-saving: When power is off, the electric energy will be saved. The saved
electric energy will be accumulated continue when the meter power on next
time.
Extreme working conditions:
Working temperature: -10 ~ 50℃
Working humidity: 10 ~ 80% (no frost)
Working pressure: 80 ~ 106 kPa
Sun: no directly sunshine
It’ll damage the instruments if the voltage input wires and CT wires are connected wrong.
Application Method:
According to the connection graph, connect the green wire of the secondary
current transformer to the blue terminal of the meter and make the wire of the
measurement circuit through the hole in the current transformer.
Supply power and start to measure and display the result.
Press down the button for 5 seconds, the electric energy will be cleared.
Attention:
The meter will be destroyed when you make the wrong connection.
This meter is suitable for 50 – 60HZ AC power, it couldn’t be used for the
square wave, the output of the inverter, and correction sine wave.
Don’t squeeze the screen when you install the meter, otherwise, may occur
garbled/broken code.