FLEXIT 118044 ProNordic Controller Instruction Manual

June 5, 2024
FLEXIT

FLEXIT 118044 ProNordic Controller

Important safety intructions

DANGER!
All electrical connections must be carried out by qualified electricians.

If possible, back up the controller that is to be replaced.

Procedure:

  1. Insert a blank SD memory card into the regulator.

  2. Back up the values to the memory card.
    Start page > Main menu > System objects > Save/load > Sett.save -> Ext.m. = Execute

  3. Wait until:
    Start page > Main menu > System objects > Save/load > OK

Remove the defective controller

  1. Check that the power to the product is off.
  2. Detach all contacts.
  3. Loosen the four locks using a screwdriver.
  4. Lift out the controller.

Install a new controller

  1. Place the controller on the DIN rail

  2. Press in the four locks

  3. Refit all contacts

  4. Switch on the power

  5. Read back an existing backup if there is one: Procedure:

    • Insert the memory card into the regulator.

    • Log in with 2000.

    • Load the values from the memory card.
      Start page > Main menu > System objects > Save/load > Sett.load <- Ext.m.. = Execute

    • Wait until:
      Start page > Main menu > System objects > Save/load > OK

    • Restart the process unit:
      Start page > Main menu > System objects > Save/load > Restart required! = Execute

  6. If there is no backup, the following settings must be done:
    Log in with 2000.

    • Start page > Main menu > Configuration > Configuration IOs > Integrations > +Fan configuration = Done
    • Start page > Mainmenu > Configuration > Configuration IOs Z Integrations > Flexit MB Extender (Communicat.info.)

Set “K-factor, SplyFan” and “K-factor, ExhFan” according to the following table:

Unit K-value
Supply air Extract air
S100R 74
S140R 74
S180R 76,5
S220R 80
S240R 129
S260R 150
S300R  
S340R  
L110R 74
L150R 72
L190R 84
L230R 132
L270R 154
L310R  
L350R  
  • Start page > Main menu > Configuration > Configuration IOs > Configuration IOs = Done
  • Start page > Main menu > Configuration > Configuration IOs > Rstart Required! = Execute

Our products are subject to continuous development and we therefore reserve the right to make changes. We also disclaim liability for any printing errors that may occur.

Flexit AS
Tlf +47 69 81 00 00
post@flexit.no www.flexit.no

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals