JTW-ZOM-TC5402W Wireless Addressable Heat Detector User Manual

June 5, 2024
TC

JTW-ZOM-TC5402W Wireless Addressable Heat Detector

General

JTW-ZOM-TC5402W wireless addressable heat detector (hereinafter referred to as the detector) is a smart home fire detector that uses a high-precision thermistor as the sensor. It can be used with the company’s wireless fire alarm control panel /wireless fire linkage control panel (hereinafter referred to as the device) for supporting use. The detector utilizes advanced wireless transceiver technology and a highly integrated micro-processing chip to process data. It has the characteristics of high sensitivity, long transmission distance, and low power consumption. It can accurately and quickly detect changes in ambient temperature, determine fire and call the police.
This product has beautiful appearance design, convenient and reliable installation, and is suitable for places where smokeless fires may occur, a large amount of dust or smoke and steam are trapped under normal circumstances. This product is widely used in various residential buildings. The fire can be detected as early as possible, and the people’s lives and property can be protected to the greatest extent.

Features

  1. Using advanced wireless transceiver technology, signal transmission can be completed without wiring, and the project is simple and convenient.
  2. Using 470MHz frequency band communication, FSK coding technology, strong anti-interference ability, long transmission distance;
  3. With battery low-voltage detection, remind users to replace when the battery is insufficient to maintain the detector’s normal operation.
  4. The use of high-sensitivity thermal elements improves the response speed of the temperature detector to temperature changes.

Technical Specifications

  1. Type:A2R
  2. Battery type: CR17450 3V
  3. Working Current: Standby Current≤3uA
  4. Indicators:Fire Indicator:red, always on when it alarms
  5. Coding method:The control panel is automatically assigned during networking
  6. Communication method:470MHz FSKCoded two-way communication
  7. Communication distance:≤50m
  8. Transmitting power: <20dBm
  9. Frequency band:470MHz
  10. Protection area: When the height of the space is less than 8m, the protection area of a detector is 20m2~30m2 for the general protection site. The specific parameters should be based on the “Code for Design of Automatic Fire Alarm System” (GB 50116-2013).
  11. Use environment:
  12. Dimensions: diameter 100mm, high 54mm (with base)
  13. Protection grade: IP30
  14. Material and color: ABS, off-white
  15. Weight: about 110g (including battery)
  16. Installation hole distance: 60mm
  17. Executive standard: GB 4716-2005 “Point Type Temperature Sensing Fire Detector”

Structure and Working Principle

The outline diagram of the detector is shown in

Working principle
The detector uses a high-precision thermistor sensor, and the output signal of the sensor is input to the single-chip microcomputer after voltage conversion, and the single-chip uses an intelligent algorithm for signal processing. When the temperature in the environment reaches the alarm value, the red light of the detector will be on, and an alarm signal will be sent to the control panel wirelessly. When used as a fire alarm device, the detector is in the state of waiting for the control panel to reset during this process. If the fire alarm is not cleared, the detector will resend the fire alarm signal to the control panel every ten minutes.

Installation

Warning: Before installing the detector, please make sure that the battery polarity is correct and that the base has been installed firmly.

Installation method
The schematic diagram of the detector installation is shown in

The schematic diagram of the base of the detector is shown in Figure 3. Fix the base with two self-tapping screws or stick it firmly with 3M glue. After the base is firmly installed, align the bottom of the detector and rotate the base clockwise to install the detector on the base.

Points for on-site installation
The wireless performance indicators of this product will vary according to the actual use environment. The construction personnel should strictly follow the communication requirements of the wireless product and set the working network segment of the wireless fire alarm system in accordance with the actual working environment of the installation site.

Test

Warning: Please make sure that the polarity of the battery is correct before proceeding.

  1. The detector must be tested after installation or after each regular maintenance.
  2. Simulated fire alarm: After successfully connecting to the network, choose a detector to make it meet the fire alarm conditions artificially (please turn off the fire alarm linkage function to avoid unnecessary alarm linkage), and verify whether the detector reports the fire alarm normally. After the test is over, pass The control panel sends a communication command to reset the detector and informs the relevant management department to restore the system to normal.
  3. During the test, the unqualified detector shall be dealt with according to “general failure and repair” and “maintenance”, and then be tested. If it still fails to pass the test, it should be returned to the factory for repair.

Use and Operation

  1. Network segment setting: Before the detector connects to the network, you should first set the device network segment. Select the network setting on the menu interface of the control panel . After entering the network setting, first set the local address number, and then set the detector to the network according to the actual situation on site Segments (29 options).
  2. The device enters and exits the network: After the detector is powered on, press the “Indicators” button once, the green light flashes once, the detector sends an online command to the control panel , and the control panel displays the detector loop address number, indicating that the detector has successfully connected to the network , Otherwise the detector is not connected to the network. The detector sends online commands for 3s, during which other functions of the keys are disabled.
  3. Equipment alarm: When the temperature in the environment reaches or exceeds the alarm temperature set by the detector, the red light of the detector will be on, and an alarm signal will be sent to the control panel wirelessly. After the control panel responds to the alarm signal, the control panel will display a fire alarm. , The detector is in the state of waiting for the control panel to reset. After confirming that the fire alarm is released, the control panel can send a signal to reset the detector.
  4. Device reset: When the device reports a fire alarm and the control panel responds, it can be reset by operating the control panel . After the detector receives the reset signal, it will perform the reset operation.
  5. Restore factory settings: After the detector is connected to the network, when it is powered on again, the red indicators will be on for 10s; during this period, the factory settings can be restored by pressing the button five times.

Note: The button function only has one click, three consecutive clicks, five consecutive clicks, long press function, and other button methods are invalid.

General failure and repair

General faults and their solutions are shown in the table below :

Fault Reason Solution
No status prompt on the control panel after device alarms The device is not
connected to the network

Restart the network operation

Device networking is unsuccessful

|

Too far away from the control panel or interference sources nearby

| Move the device near the controller, reconnect to the network and remove the source of interference
Red light is off| Low battery or no battery inserted| Replace battery

Maintenance

  1. The detector should take corresponding moisture-proof and anti-corrosion measures.
  2. The detector is cleaned at least once a year to ensure the normal operation of the system. Before the detector is cleaned, the relevant management department should be notified that the system will be maintained, and the logical control function of the area or the system that will be maintained should be closed to avoid unnecessary alarm linkage.
  3. The detector should conduct a simulated fire alarm test every six months to test whether the detector works normally.

Matters needing attention

  1. The horizontal distance between the detector and the air supply hole of the air conditioner should not be less than 1.5m.
  2. The horizontal distance from the detector to the wall and beam side should not be less than 0.5m.
  3. The detector should be installed horizontally. If it must be installed at an angle, the inclination angle should not be greater than 45°.
  4. When the detectors are installed on the ceiling of the inner walkway with a width less than 3m, they should be arranged in the center, and the installation distance of the temperature sensing detectors should not exceed 10m.
  5. After the signal passes through the wall, the signal strength will be greatly attenuated, so try to reduce the number of partition walls for wireless products.
  6. When installing the product, keep it away from metal to reduce the shielding of the signal from metal objects. For example, it cannot be installed in a metal box such as a fire hydrant box or outside of a metal cabinet.
  7. Install in a low-interference environment and far away from motors or large-scale electrical equipment.