SCE-AC3400B120V Air Conditioner User Manual
- June 5, 2024
- SCE
Table of Contents
- SCE-AC3400B120V Air Conditioner
- Safety Instructions
- Functional Principle
- 5. Technical Data
- Performance Graph
- Mounting
- Mounting Principle
- Cutout Dimensions
- Dimensions (H x W x D)
- Controller Programming
- Wiring Diagram
- Taking Into Operation
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
- 1 For supply ranges 380-415 V 50 Hz and 400-420 V 60 Hz, bridge 5 & 6 on X4
- 2 For supply range 420-460 V 60 Hz, bridge 6 & 7 on X4
SCE-AC3400B120V Air Conditioner
User Manual
This instruction manual contains information and instructions to enable the
user to work safely, correctly and economically on the unit. Understanding and
adhering to the manual can help one:
- Avoid any dangers
- Reduce repair costs and stoppages
- Extend and improve the reliability and working life of the unit
PLEASE ENSURE TO USE THE RIGHT VERSION OF THE INSTRUCTION MANUAL SUITABLE FOR
YOUR UNIT
Conditions of Use
The unit is to be used exclusively for the dissipation of heat from control
cabinets and enclosures in order to protect temperature sensitive components
in an industrial environment. To meet the conditions of use, all the
information and instructions in the instruction manual must be adhered to.
Legal Regulations
Liability
The information, data and instructions contained in this instruction manual
are current at the time of going to press. We reserve the right to make
technical changes to the unit in the course of its development. Therefore, no
claims can be accepted for previously delivered units based on the
information, diagrams or descriptions contained in this manual. No liability
can be accepted for damage and production caused by:
- Disregarding the instruction manual
- Operation error
- Inappropriate work on or with the unit
- The use of non-specified spare parts and accessories
- Unauthorized modifications or changes to the unit by the user or his personnel
Saginaw Control & Engineering is only liable for errors and omissions as outlined in the guarantee conditions contained in the main contractual agreement. Claims for damages on any grounds are excluded.
Safety Instructions
Upon delivery the unit is already meeting current technical standards
therefore it can be safely taken into operation. Only trained specialists are
allowed to work on the unit. Unauthorized personnel must be prohibited from
working on the unit. Operating personnel must inform their superiors
immediately if any malfunction of the unit becomes apparent.
Please note that before starting to work on or with the unit, a procedure must
be carried out inside the cabinet on which the unit is to be mounted.
Before commencing work inside the cabinet, the control cabinet manufacturer’s
instruction must be read with regards to:
- Safety instructions
- Instructions on taking the cabinet out of operation
- Instructions on the prevention of unauthorized cabinet reconnection
The electric equipment meets the valid safety regulations. One can find dangerous voltage (above 50V AC or above 100V DC):
- Behind the control cabinet doors
- On the power supply in the unit housing
The units have to be fused according to the type plate and the wiring diagram. Switch the unit off immediately if the electric power supply is interrupted.
Danger Through Incorrect Work on the Unit
Only specialized personnel are allowed to maintain and clean the unit. Regular
maintenance and cleaning must be kept in order to ensure that the unit remains
in perfect working condition and has a long working life.
Danger from Electric Voltage
Only specialized personnel are allowed to maintain and clean the unit. The
personnel must ensure that for the duration of the maintenance and cleaning,
the unit is disconnected from the electrical supply.
Attention
Damage to the unit through the use of inappropriate cleaning materials. Please
do not use aggressive cleaning material.
Instruction
Damage to the environment through unauthorized disposal. All spare parts and
associated material must be disposed of according to the environmental laws.
Functional Principle
The unit functions on the principle of the compression refrigerator. The main components are: refrigerant compressor, condenser, choke and evaporator. These four components of the refrigerant plant are connected with each other by pipes to form a hermetically sealed system in which the refrigerant (R134a) circulates.
- Air Intake, Cabinet Side
- Radial Fan, Cabinet Side
- Evaporator
- Air Outlet, Cabinet Side
- Compressor
- Air Intake, Ambient Side
- Radial Fan, Ambient Side
- Condenser
- Air Outlet, Ambient Side
- Filter Dryer
- Expansion Valve
5. Technical Data
-
Part Number
SCE-AC13650B460V3
SCE-AC13650B460V3SS
SCE-AC13650B460V3SS6 -
Cooling Capacity @ 95°F / 95°F
13650 BTU (3999 Watts) -
Cooling Capacity @ 131°F / 131°F
14959 BTU (4383 Watts) Heating -
Capacity
2000 W -
Compressor
Rotary Compressor -
Refrigerant
R134a -
Refrigerant Charge
35.00 oz -
Max. Pressure
402 psig -
Operating Temperature Range
-4°F – 131°F -
Max. Air Volume Flow
Ambient Air Circuit: 385 cfm Cabinet Air Circuit: 235 cfm -
Mounting
External -
Housing Material
Mild Steel, Powder Coated SS: Stainless Steel AISI 304 SS6: Stainless Steel AISI 316 -
Dimensions (H x W x D)
61.02 x 18.00 x 13.98 inch -
Weight
176 lbs -
Cutout Dimensions
14.80 x 12.80 inch, 14.80 x 13.20 inch -
Rated Operating Voltage / Frequency
400/460 V – 50/60 Hz 3~ Rated Current @ 95°F / 95°F 2.7 A -
Starting Current
8.5 A -
Max. Current
5 A -
Power Consumption @ 95°F / 95°F
1.91 kW -
Max. Power Consumption
2.43 kW -
Fuse Rating
8A (T) – Time Delayed [Slow Acting] -
SCCR
5kA -
Circuit Breaker – MCB Type D or K Slow Acting
9A Slow Acting -
Connection
Connection Terminal Block -
NEMA Protection Class
NEMA 3, 3R, 4 & 12
SS: NEMA 3, 3R, 4, 4X & 12 -
Approvals
CE / cURus / UL Listed -
Industry Standards
IS19,SS: IS20 -
Sound Level at 1.5 meters
73 db(A) -
Max Voltage at Door Switch
5 A DC
Performance Graph
Enviro-Therm® Air Conditioners 13650 BTU/HR (3999 Watts)
Performance Curve
- SCE-AC13650B230V, SCE-AC13650B460V3
- SCE-AC13650B230VSS, SCE-AC13650B460V3SS
- SCE-AC13650B230VSS6, SCE-AC13650B460V3SS6
Mounting
Always disconnect the power supply before opening the unit.
Heat load to be dissipated from enclosure should not exceed specific cooling
output of the unit at any condition. When selecting a cooling unit, always
allow for a safety margin of at least 15% extra cooling output in the worst
conditions. Air inlets and outlets must be completely free from obstruction.
Ensure that flows of air leaving and entering the cooling unit, internal and
external, are not obstructed. Cooling unit enclosure air suction hole must be
installed at the highest possible point. When installing the unit on a door
ensure it can take the weight.
Before drilling the enclosure, ensure the fixing elements and couplings will not interfere with the equipment inside the enclosure itself. Disconnect power before starting any work inside the enclosure. Following this 1:1 Scale Drilling Template, drill the holes and make the required cuts on the enclosure. This template may have been affected by storage conditions, please check this template by verifying values of the largest dimensions before drilling. Fit the sealing strip to the cooling unit on the side connected to the enclosure and follow the installation diagram.
Mounting Principle
WARNING:
- Do not use within the first 15 minutes after installation!
- Use only the supplied mounting hardware.
- Tighten fasteners to 40 inch lb.
- Ensure the mounting surface does not warp after assembly and reinforce it if necessary.
- M6 Bolts
- M6 Toothed Washers
- M6 Flat Washers
- Enclosure
- Mounting Gasket
- Cooling Unit
Cutout Dimensions
Dimensions (H x W x D)
Electrical Connection
The cooling unit is used where heat needs to be dissipated from electrical
control cabinets or similar enclosures in order to protect heat sensitive
components. The unit has two completely separate air circuits which ensure
that the clean cabinet air does not come into contact with the ambient air
which may well be dirty or polluted. Control cabinet air conditioners can
dissipate large quantities of heat from sealed enclosures, such as control
cabinets, into the ambient air and at the same time reduce the cabinet
internal temperature to below that of the ambient air.
The control cabinet air conditioner can function without problems in extreme ambient conditions (e.g. dusty and oily air) with a standard operating temperature ranging between -4°F and 131°F. The stated cooling capacities are according to DIN 3168.
Door Switch
The unit can be switched on and off via a door contact switch. When delivered
the door contact terminals are bridged on the female connector. To connect the
door contact switch remove the bridge and connect door contact switch. The
contact must be closed when the cabinet door is closed.
Controller Programming
The cooling unit is intended to be used as a complementary accessory to larger industrial equipment. The unit is used where heat needs to be dissipated from electrical control cabinets or similar enclosures in order to protect heat sensitive components. It is not intended for household use. The unit has two completely separate air circuits which ensure that the clean cabinet air does not come into contact with the ambient air which may well be dirty or polluted. Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclosures into the ambient air and at the same time reduce the cabinet internal temperature to below that of the ambient air.
The unit can function without problems in extreme ambient conditions (e.g. dusty and oily air) with a standard operating temperature ranging between +10°C and +55°C. Units can be ordered with an additional electrical cabinet heater. For the cooling capacities and environmental ratings please refer to the type plate data.
Controller
The display shows the temperature in the range of -50°C to +150°C (-58°F to +302°F). The temperature is displayed with resolution of tenths between -19.9°C and +99.9°C (-3.8°F to +211.8°F). During programming, it shows the codes and values of the parameters. The display also shows icons according to occurring events.
Programming
The operating parameters can be modified using the front keypad. Access
differs depending on the type of parameter. Access to configuration parameters
is protected by a password that prevents unwanted modifications or access by
unauthorised persons.
Setting cooling set point, St1:
- Press and hold “SET” until the display shows St1. Once released the pre-set value of St1 will appear.(default: +35°C / +95°F)
- Reach the desired value by using ▲ or ▼.
- Press “SET” again to save the new value of St1.
Setting heating set point, St2 (only for units supplied with internal heater):
- Press “SET” twice slowly and display should show St2 and then the pre-set value of St2.(default: +5°C / +41°F)
- Reach the desired value by using ▲ or ▼.
- Press “SET” again to save the new value of St2.
Setting temperature units (°C / °F), low temperature alarm and high temperature alarm:
-
Press “PRG” button for 5 seconds to reach the modifiable parameter list.
-
Use ▲ or ▼ to reach the desired parameter:
• C18 for temperature unit of measure
• °C = 0
• °F = 1
• P25 for low temperature alarm threshold (default -10°C / +14°F)
• P26 for high temperature alarm threshold (default +55°C / +131°F) -
Press “SET” on the desired parameter to display the current value.
-
Use ▲ or ▼ to reach the desired value.
-
Pressing “SET” temporarily saves the new value and returns to the parameters list.
-
Repeat steps 2-5 to set other parameters.
-
Press “PRG” for 5 seconds to permanently save the new values.
Test Function
Different test functions can be used depending on the combination of keys
pressed. Such tests run for the duration of 4 minutes.
- “SET+▲” tests Compressor and Ambient Blower relays.
- “SET+▼” tests Alarms and Heater relays
Alarm Relay Function
Both normally closed (NC) and normally open (NO) alarm contacts are provided.
These refer to the alarm state. Under normal conditions, the NC contact is
closed and the NO contact is open. When an alarm condition is present or the
door contact is open, the NC contact will open and the NO contact will close.
System power failure will give an alarm condition.
Notes:
- State 2: Additional icons (1,3,4, Reverse, Direct, Test) depending on operation.
- State 3: The display shows “OFF” alternating with the standard display.
- State 4: The display shows “EXX” alternating with the standard display – at the same time, the alarm icon flashes.
Typical alarm codes:
Error Code Description
- E01 Probe B1 fault
- E02 Probe B2 fault
- E04 High temperature alarm
- E05 Low temperature alarm
Important Notes
- Whilst programming, if no button is pressed for 10 seconds, the display starts flashing, and after 1 minute returns to the main display without saving changes.
- l To increase scrolling speed, press and hold the ▲ or ▼ button for at least 5 seconds.
- When pressing “PRG” for 3 seconds, the firmware revision code is displayed for 2 seconds.
- When cleaning the controller panel, do not use ethanol, hydrocarbons, ammonia or their byproducts. Use neutral detergents and water.
- In order to protect the unit’s components, minimum relay output on (3 or 7 minutes) and off (4 minutes) times and minimum time (7 or 11 minutes) between activation of the same relay output are applied.
- In case of digital inputs not configured, probes not fitted or configured, or St2 not enabled on the controller the display shows ‘nO’.
Wiring Diagram
- Mc Compressor
- Ma Ambient Fan
- Mi Internal Fan
- TS Temperature Sensor
- PDB Phase Detection Board
- CE Condensate Evaporator
- CH Compressor Heater
- HR Heater Relay
- IH Internal Heater
- C Controller
- C1 Contractor
- R1 Motor Overload Protector
- AR Alarm Relay
- X4 Electrical Supply Connections
1 L1 – 380-415/400-460 V 50/60 Hz 3~
2 L2 – 380-415/400-460 V 50/60 Hz 3~
3 L3 – 380-415/400-460 V 50/60 Hz 3~
4 Earth/Ground
5 P1 High Temp alarm NO
6 P2 High Temp alarm COM
7 P3 High Temp alarm NC
8 T1 Door Switch Contact
9 T2 Door Switch Contact
Notes:
-
1 For supply ranges 380-415 V 50 Hz and 400-420 V 60 Hz, bridge 5 & 6 on X4
-
2 For supply range 420-460 V 60 Hz, bridge 6 & 7 on X4
Taking Into Operation
Attention!
The unit can be damaged by lack of lubricant. To ensure that the compressor is
adequately lubricated, the oil, which has been displaced during transport,
must be allowed to flow back into it. The unit must therefore be allowed to
stand for at least 30 minutes before being connected to the mains and taken
into operation. Upon connection the internal fan will start working. If the
temperature inside the enclosure is higher than the set value of the
controller, both the compressor and external air fan start working. Once the
air inside the enclosure reaches the set temperature, the compressor and
external fan will stop.
The unit is pre-set at 95°F, which is suitable for most of the electronic
devices.
If Drainage required, use PVC 10mm (3/8 inch) ID Hose.
Repair
Failure | Condition | Cause | Solution |
---|
Unit Does Not Cool
| Internal fan does not work| Power not connected.| Verify power supply
Internal fan works, external fan and compressor do not work
| Enclosure temperature is
below setting temperature (St)
| Verify values of parameter “St”
Door switch contact is open| Verify door switch
Controller does not work| Replace controller
Internal fan works, external fan and compressor do not
work Display shows alternating
“OFF” and temperature
| The sequence of the phases inside the power supply connector is incorrect|
Change phases inside power supply connector
External and internal fan work, compressor does not work
| Compressor motor electrical failure| Verify external fan, verify ambient
temperature, clean condenser
Capacitor for compressor failed| Replace capacitor
Compressor works, external fan does not work| External fan needs to be
replaced| Replace external fan
Enclosure Overheating
| Compressor and fans (external
and internal) work all the time
| Unit cooling undersized| Enclosure needs a bigger cooling unit
Enclosure needs a bigger cooling unit
| Thermal compressor protector triggered| Verify ambient temperature,
clean condenser
Refrigerant leakage| Contact dealer/service center
Excessive Condensate
|
Door enclosure open
|
Ambient air gets into the enclosure
| Ensure door is closed, add a door switch and connect it to controller
Door enclosure closed
| Enclosure IP degree minimum
IP54
| Seal openings on enclosure
Damaged/misplaced sealing
strip
| Repair strip accordingly
Maintenance & Cleaning
WARNING:
Always switch power supply off before starting any maintenance on the unit.
Any repairs that may be needed must only be done by qualified personnel. The cooling unit is a low maintenance type and for most environments, no filter is required. If an air filter is installed, check it periodically for dirt and clogs. Clean or replace filter when necessary.
Disposal
The cooling unit contains R134a refrigerant and small quantities of
lubricating oil. Replacement, repairs and final disposal must be done
according to the regulations of each country for these substances.
Transportation & Storage
During transport and storage the cooling unit must be kept in the position
marked on the box and at a temperature between -40˚F and 158˚F and a relative
humidity of max. 95% (at 77°F). Check that the packaging has not been damaged
during transport.
Parts Supplied
- 1 x Air Conditioner
- 1 x Instruction Manual with technical information
- 1 x Mounting Template in 1:1 scale
- 1 x Installation pack containing:
- 11 x M6 Bolts
- 11 x A6.4 Toothed Washers
- 11 x A6.4 Washers
- 1 x Female Connector with shorted wired positions for door contact
Saginaw Control and Engineering 95 Midland Road
Saginaw, MI 48638-5770
Phone: 989-799-6871
Fax: 989-799-4524
sce@saginawcontrol.com
Warranty / Limits of Liability
All goods manufactured by SCE shall be warranted to be free of defects in
material or workmanship for a period of two years from the date of shipment.
Should the product be proven to SCE to be defective, we shall option to repair
or replace the product. At no time will SCE reimburse purchaser for
unauthorized rework on any product.
Air Conditioners & Heat Exchangers are warranted on parts and service for a
period of two years from the date of shipment by Saginaw Control and subject
to the following conditions and exclusions:
All Goods must be installed and operated according to the following specifications: Maximum voltage variation no greater than plus or minus 10% of nominal rating; Maximum frequency variation no greater than plus or minus 3 Hz. from nominal rating; Must not exceed minimum and maximum rated temperatures; Must not exceed (BTU/Hr) rating; Filters must be cleaned regularly; Must be installed and grounded in accordance with all relevant electrical and safety codes, as well as the National Electric Code and OSHA rules and regulations; Must be installed in a stationery application, free of vibration. Our warranty does not warranty product that has been modified, subjected to abuse, negligence in operation or maintenance, or if product is used in a manner that exceeds its designed capabilities and rating.
Warranty related claims will be returned to the factory for evaluation and final disposition of the claim, any replacement parts will be invoiced at standard pricing and credit issued for the returned product. If the product has been found to have been modified, subjected to abuse, negligence in operation or maintenance, or if product has been used in a manner that exceeds its designed capabilities and rating, credit may be reduced, denied or additional cost may be assessed and passed on to the purchaser, such as return freight.