TSH25 Touch Safe Heaters
Instruction Manual
SCE-TSH25 Touch Safe Heaters
SCE-TSH25 & SCE-TSH50 | SCE-TSH75 & SCE-TSH100 | SCE-TSH150 |
---|
| |
MODEL SELECTION:
- Determine the surface area of the enclosure in square feet.
- Select the Touch Safe Heater unit from the chart based on square feet of the enclosure.
- Units should be installed in the lower quarter of the enclosure.
- When enclosure width is greater than height, two smaller units will heat the area more efficiently than one larger unit.
SURFACE AREA EQUATION:
2[(Height x Width)+(Height x Depth)+(Width x Depth)] ÷ 144
CIRCUIT DIAGRAM
NOTES
- All heaters are delivered with a DIN rail Clip 1.37”.
- Maximum Surface Temperature on casting: 80C/176F.
- 4.75” Minimum Thermal Safety gap required above or to side of this device.
FT2 AREA| TSH-25| TSH-50| TSH-75| TSH-100|
TSH-150
---|---|---|---|---|---
0 – 8| One| | | |
9 -16| One| | | |
17-24| | One| | |
25 – 32| | One| | |
33 – 40| | | One| |
41- 48| | | One| |
49 – 56| | | One| |
57 – 64| | | One| |
65 – 72| | | | One|
73 – 80| | | | One|
81- 88| | | | | One
89 -120| | | | | One