CDP R-SMART 751 Interactivo 750VA-350W Pan LCD 10 Outlets User Manual
- June 5, 2024
- CDP
Table of Contents
R-SMART 751 Interactivo 750VA-350W Pan LCD 10 Outlets
User Manual
PACKAGE CONTENTS
You should have received the following items inside of package:
- UPS Unit
- Quick Guide
- Communication cable
PRODUCT OVERVIEW
Front View:
- Input voltage
- Output voltage
- AC mode indicator
- Load level
- Overload indicator
- Battery mode indicator
- Battery level
- Low battery indicator
- Fault indicator
Back View:
- Output receptacles
- AC input
- Circuit breaker
- USB port
Installation and Initial Startup
NOTE: Before installation, please inspect the unit. Be sure that nothing
inside the package is damaged.
Placement & Storage Conditions
Install the UPS in a protected area that is free of excessive dust and has
adequate airflow. Please place the UPS away from other units by at least 20 cm
to avoid interference. Do NOT operate the UPS where the temperature and
humidity are outside the specified limits. (Please check the specs for the
limitations.) Connect to Utility and
Charging
Plug in the AC input cord to the wall outlet. For the best results, suggest
charging the battery at least 4 hours before initial use. The unit charges its
battery while connecting to the utility.
Connect the Loads
Plug in the loads to output receptacles on the rear panel of the UPS. Simply
turn on the power switch of the UPS unit, then devices connected to the UPS
will be protected by the UPS unit.
CAUTION: NEVER connect a laser printer or scanner to the UPS unit. This
may cause damage to the unit. Connect Communication Cable
To allow for unattended UPS shutdown/start-up and status monitoring, connect
the communication cable to one end to the USB port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
Turn On/Off the Unit
Turn on the UPS unit by pressing the power switch. Turn off the UPS unit by
pressing again the power switch.
IMPORTANT SAFETY WARNING
(SAVE THESE INSTRUCTIONS)
CAUTION! To prevent the risk of fire or electric shock, install in a
temperature and humidity-controlled indoor area free of conductive
contaminants. (See the specifications for the acceptable temperature and
humidity range.)
CAUTION! To reduce the risk of overheating the UPS, do not cover the UPS’
cooling vents and avoid exposing the unit to direct sunlight or installing the
unit near heat emitting appliances such as space heaters or furnaces.
CAUTION! Do not attach non-computer-related items, such as medical
equipment, life-support equipment, microwave ovens, or vacuum cleaners to UPS.
CAUTION! Do not plug the UPS input into its own output.
CAUTION! Do not allow liquids or any foreign object to enter the UPS. Do
not place beverages or any other liquid-containing vessels on or near the
unit.
CAUTION! In the event of an emergency, press the OFF button and
disconnect the power cord from the AC power supply to properly disable the
UPS.
CAUTION! Do not attach a power strip or surge suppressor to the UPS.
CAUTION! If the UPS is with metal chassis, for safety purposes, grounding
is a must during UPS installation in order to reduce leakage current below
3.5mA.
Attention hazardous through electric shock. Also with the disconnection
of this unit from the mains, hazardous voltage still may be accessible through
the supply from the battery. The battery supply should be therefore
disconnected in the plus and minus pole at the quick connectors of the battery
when maintenance or service work inside the UPS is necessary.
CAUTION! Servicing of batteries should be performed or supervised by
personnel knowledgeable of batteries and the required precautions. Keep
unauthorized personnel away from batteries.
CAUTION! When replacing the batteries, use the same number and type of
batteries.
CAUTION! The internal battery voltage is 12VDC. Sealed, lead-acid, 6-cell
battery.
CAUTION! Do not dispose of batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes.
CAUTION! Unplug the UPS prior to cleaning and do not use liquid or spray
detergent.
CAUTION! A battery can present a risk of electric shock and a high short
circuit current. The following precaution should be observed before replacing
batteries:
- Remove watches, rings, or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect the charging source prior to connecting or disconnecting the battery’s terminal.
SOFTWARE DOWNLOAD & INSTALLATION
Please follow the steps below to download and install monitoring software:
- Go to the website http://www.power-software-download.com
- Click the ViewPower software icon and then choose your required OS to download the software.
- Follow the on-screen instructions to install the software.
- When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.
Trouble Shooting
Use the table below to solve minor problems.
Problem | Possible Cause | Solutions |
---|
No words display
on the front panel.| Low battery.| Charge the UPS for at least 6 hours.
Battery fault.| Replace the battery with the same type of battery.
The UPS is not turned on.| Press the power switch again to turn on the UPS.
The alarm continuously sounds when the mains is normal.| The UPS is
overloaded.| Remove some loads first. Before reconnecting equipment, please
verify that the load matches the UPS capability specified in the specs.
When power fails, backup time is shortened.| The UPS is overloaded.| Remove
some critical load.
The battery voltage is too low.| Charge the UPS for at least 6 hours.
Battery defect. It might be due to a high-temperature operation environment,
or improper operation of the battery.| Replace the battery with the same type
of battery.
The mains is normal but the UPS in battery mode.| The power cord is loose.|
Reconnect the power cord properly.
Specifications
Model | 750VA | 1000VA |
---|---|---|
CAPACITY | 750 VA / 375 W | 1000 VA /500 W |
INPUT
Voltage| 110/120 VAC or 220/230/240 VAC
Voltage Range| 81-145 VAC / 162-290 VAC
OUTPUT
Voltage Regulation| +/-10%
Transfer Time| Typical 2-6 ms, 10 ms max.
Waveform| Simulated Sine Wave
BATTERY
Type & Number| 12 V/7 AH x 1| 12 V/9 AH x 1
Charging Time| 4-6 hours recover to 90% capacity
autonomy| 3 minutes at 100% charge
PHYSICAL
Dimension (DxWxH)| 287 x 100 x 142 mm
Net Weight (kgs)| 4.25| 4.9
ENVIRONMENT
Humidity| 0-90 % RH @ 0-40° C (non-condensing)
Noise Level| Less than 40 dB
operating altitude| 3000 msnm
MANAGEMENT
USB| Supports Windows® 2000/2003/XPNista/2008/7, Linux, Unix, and MAC
WARRANTY
CHICAGO DIGITAL POWER INC. warranties this product against defective materials
or workmanship for one year from the date of original purchase) with the
possibility to be extended to 2 years). Proof of purchase is required.
I. – To make this warranty valid proof of purchase is required. Bring the
product to the original purchase place or to the nearest CDP service center.
Make sure to bring also this warranty policy. For information about service
centers in your country please call the following numbers. (If your country is
not here please send a mail to
sen.ficiocdpups.com)
Bolivia: 800-1 001 56 | Salvador: 800-6773 | Panama: 011-00800-2268611 |
---|---|---|
Colombia: 01800-5181617 | Honduras: 800-2561-6099 | Peru: 0800-54674 |
Costa Rica: 800-4357237 | Mexico: 001800-5148611 | Dominic Republic: |
1888-7514876
Venezuela: 0800-1627485
II. – Chicago Digital Power will repair or replace the product at its own
criteria without a cost during the warranty period.
III. – Repair or replacement time should never exceed 30 days from the date
that the unit is received at the CDP Service Center.
IV.-In case this warranty policy is lost please a copy at the original
purchase place.
Warranty Limitations
(a). This warranty does not include damage that arises from negligence, misuse
or use not in accordance with the product instruction.
(b). When the product has been opened or serviced by a non-authorized service
facility, has been altered or changed.
(c). Warranty is voiced if utility wiring is reversed or lacks of ground.
(d). Warranty not valid for normal wear and tear.
(Please complete and submit this information, otherwise, you will not have
access to the guarantee)
(No guarantee will be offered if this format does not accompany the unit at
the time of its return to the place of purchase)
Name:…………………………..
Address:………………………..
Phone number:……………..
e-mail:……………………………
Shop place:…………………….
Purchase address:…………..
E-mail from the place of purchase:………………….
Product AVR UPS No-Break Inverter
STORE SEAL…………………………………
DATE OF DELIVERY……………………
Model:………………………………………………
Enter this link to register your product.
Bolivia: 800-100156
Colombia: 01 800-51 81 61 7
Costa Rica: 800-4357237
El Salvador: 800-6773
Honduras: 800-2561-6099
Mexico: 001 800-51 4861 1
Panama: 011-00800-2268611
Peru: 0800-54674
Dominic Republic: 1888-7514876
Venezuela: 0800-1627485
www.cdpenergy.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>