JL3PR Job Link System Pressure Probe
Instruction Manual
Quick Start
- Install the Fieldpiece Job Link® system app on your mobile device and sign up for an account if you’re a new user.
- Remove the single screw of the yellow battery cover and install 2 x AAA batteries.
- Press for 1 second to power on.
- Open Measurements in the Job Link® app and favorite the probe to the tool manager.
- View live measurements on your mobile device up to 1000 feet away.
What’s Included
Job Link® System Pressure Probe
- 2 x Replacement Gaskets
- 2 x AAA Batteries
- Operator’s Manual
- 1 Year Limited Warranty
WARNING
Hand turns the female fitting to connect and disconnect. DO NOT use the
plastic body to increase leverage. Doing so can cause damage, and leaks, and
void the warranty. Do not apply more than 800 psig.
Description
The JL3PR Job Link® System Pressure Probe sends long-range wireless pressure
measurements directly to the Fieldpiece Job Link® system mobile app.
Easily reach service ports in tight spaces using the angled 1/4″ fitting. The
rubberized protective housing is both ergonomic and rugged for daily use.
Flip the switch to red or blue and the app immediately knows which side of the
system you’re going to place your pressure probe.
The perfect balance of size and capability gives you exactly what you need to
diagnose systems day in and day out quickly and confidently.
Maintenance
CLEANING: Clean the exterior with a damp cloth. Do not use detergents or
solvents.
BATTERIES: When the LED slowly blinks Red, the batteries must be
replaced. Ensure the power is OFF. Remove the single screw from the yellow
battery cover. Install 2 x AAA batteries. You can also monitor battery life in
the Job Link® app tool manager.
GASKET: The black rubber gasket that seals the pressure probe to the
service port may become worn over time potentially causing a leak. This
results from overtightening or connecting to damaged service port fittings.
- Use needle-nose pliers or a similar tool to unscrew the Schrader valve depressor from the gasket.
- Remove and replace the worn gasket.
- Screw the depressor back into the gasket.
Specifications
Minimum Device Requirement:
BLE 4.0 devices running iOS® 7.0 or Android™ 5.0 (Latest compatibility at
www.fieldpiece.com)
Sensor Type: Relative pressure
Connector Type: Standard 1/4″ NPT female flare fitting (angled)
Measurement Range:
29” HgV to 580 psig, 74 cmHgV to 0 to 4000 kPa
Accuracy:
29” HgV to 0” HgV: ±0.2” HgV; 74 cmHgV to 0 cmHgV: ±1 cmHgV 0 to 200 psig: ±1
psig; 0 to 1378 kPa: ±7 kPa 200 to 580 psig: ±2 psig; 1378 to 4000 kPa: ±14
kPa
Maximum Overload Pressure: 800 psig (5500 kPa)
Battery Type: 2 x AAA, NEDA 24A, IEC LR03
Battery Life: 150 hours typical alkaline. LED blinks red when battery
replacement is needed.
Auto Power Off: 2 hours (APO can be disabled)
Wireless Range: 1000 feet (305 meters) line of sight. Obstructions affect
distance.
Radio Frequency: 2.4 GHz
Operating Environment: -4°F to 122°F (-20°C to 50°C) at <75% RH
Storage Temperature: -4°F to 140°F (-20°C to 60°C), 0 to 80% RH (with
batteries removed)
Temperature Coefficient: 0.1 x (specified accuracy) per 1.8°F (-4°F to
64°F, 82°F to 122°F), per 1°C (-20°C to 18°C, 28°C to 50°C)
Weight: 0.39 lbs (177 g)
Water Resistant: Designed to IP55
US Patent:
www.fieldpiece.com/patents
Operation
Press for 1 second to power ON/OFF.
LED Color Indications
Green slow blink: normal operation
Red slow blink: batteries need to be replaced
High or Low Side Switch
The Job Link® system app knows which side you have selected for each probe.
Select the Suction line or Liquid line and place it on the system
appropriately. ** (Data logging will be available shortly after the time of
printing. Look for updates.)
Use the Job Link® system mobile app to program the JL3PR to log measurements
starting at a specific time of day for up to 7 days.
Auto power off disables.**
- Make sure JL3PR is powered OFF.
- Open the Job Link® system mobile app.
- Press for 5 seconds to enter data logging mode. The LED will shine solid green.
- Set up the probe’s data logging parameters within the app. The LED will blink green while the app is sending setup instructions. The LED will slow blink blue when waiting for the programmed start time to occur.
- Place the JL3PR on the system.
- When the programmed start time is reached, the LED will very slowly blink green to indicate data logging has begun.
- When the programmed span has finished, the LED blinks and powers of.
- Repeat steps 1-3 and uses the app to extract your data log from the JL3PR.
Auto Power Off (APO )
The pressure probe will automatically power off after 2 hours. To disable APO
until powered off, while power is on tap twice. The LED will briefly blink
red. To enable APO, while power is on tap twice. The LED will briefly shine
red.
Auto Calibration
Automatically calibrate your JL3PR by ensuring the sensor is open to the
atmosphere when you power ON the probe.
Limited Warranty
This probe is warranted against defects in material and workmanship for one year from the date of purchase from an authorized Fieldpiece dealer. Fieldpiece will replace or repair the defective unit, at its option, subject to verification of the defect. This warranty does not apply to defects resulting from abuse, neglect, accident, unauthorized repair, alteration, or unreasonable use of the instrument. Any implied warranties arising from the sale of a Fieldpiece product, including but not limited to implied warranties of merchantability and fitness for a particular purpose, are limited to the above. Fieldpiece shall not be liable for loss of use of the instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim of such damage, expenses, or economic loss. State laws vary. The above limitations or exclusions may not apply to you.
Obtaining Service
For international customers, warranty for products purchased outside of the
U.S. should be handled through local distributors. Visit our website to find
your local distributor.
Certifications and Module IDs
EN 300 328 | **** Regulatory Compliance Mark |
---|---|
2ALHR003 | Waste Electrical and |
Electronic Equipment
00263-18-10972| Restriction of Hazardous
Substances Compliant
IC: Industry Canada
22518-BT003| IFETEL: Federal Telecom Institute
RCPFI2A18-0235
FCC Statement
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
FCC Caution : To assure continued compliance, any changes or
modifications not expressly approved by the party responsible for compliance
could void the user’s authority to operate this equipment.
(Example – use only shielded interface cables when connecting to computer or
peripheral devices).
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This device complies with Industry Canada license-exempt RSS-247 standard.
Operation is subject to the following two conditions: (1) this device may not
cause interference, and (2) this device must accept any interference,
including interference that may cause undesired operation of the device.
IC Radiation Exposure Statement: This equipment complies with IC RSS-102
radiation exposure limit set forth for an uncontrolled environment. This
equipment should be installed and operated with a minimum distance 0.5 cm
between the radiator and your body.
Fieldpiece Instruments 1636 West Collins Avenue, Orange, CA 92867
IFETEL Statement
The operation of this equipment is subject to the following two conditions: (1) this device or device may not cause harmful interference, and (2) this device or device must accept any interference, including interference that may cause undesired operation.
ANATEL Statement
This equipment is not subject to the protection from harmful interference and may not cause interference with duly authorized systems.
© Fieldpiece Instruments, Inc 2021; v17 Designed in USA
MADE IN TAIWAN
Documents / Resources
|
Fieldpiece JL3PR Job Link System Pressure
Probe
[pdf] Instruction Manual
JL3PR, Job Link System Pressure Probe, JL3PR Job Link System Pressure Probe,
Link System Pressure Probe, System Pressure Probe, Pressure Probe
---|---
|
Fieldpiece JL3PR Job Link System Pressure
Probe
[pdf] User Manual
JL3PR Job Link System Pressure Probe, JL3PR, Job Link System Pressure Probe
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>