Fieldpiece JL3KM2 Link System Dual Port Manometer Probe Kit Instruction Manual
- June 1, 2024
- Fieldpiece
Table of Contents
Fieldpiece JL3KM2 Link System Dual Port Manometer Probe Kit Instruction
Manual
JL3KM2
Quick Start
- Install the Fieldpiece Job Link® System app on your mobile device and sign up for an account if you’re a new user.
- Remove the single screw of the yellow battery cover and install 2 x AAA batteries.
- Press for 1 second to power on.
- Open Measurements in the Job Link app and favorite the probe in the tool manager.
- Tap to zero.
- View live measurements on your mobile device up to 1000 feet (305 meters) away.
What’s Included
- Job Link® System Manometer Probe
- 2 x AAA Batteries
- Tubing with brass fitting
- Bulk tubing
- Gas adapter
- Static pressure tip
- Operator’s manual
- 1 Year limited warranty
Description
The JL3MN Job Link® System Manometer Probe sends static pressure or gas pressure measurements directly to the Fieldpiece Job Link app up to 1000 feet (305 meters) away. Use two JL3MN probes to do even more.
Because they are untethered, you don’t need long hoses to measure differential pressures.
Measure and view real-time return static, supply static, and total external static pressure all at once. Use your static pressure tip with short tubing for accurate static pressure measurements. Measure real-time inlet and manifold pressures with 2 Job Link manometers. Mount your manometer to equipment for hands free use in tight spaces. The powerful rotating magnet holds tight even when the hose is tugged or the equipment shakes. Slide the switch and the app immediately knows which side of the system you’re going to place your manometer probe.
Maintenance
CLEANING: Clean the exterior with a damp cloth. Do not use detergents or solvents. Do not apply pressurized air into the connection port.
BATTERIES: When the LED slow-blinks Red, the batteries must be replaced. Ensure the power is OFF. Remove the single screw from the yellow battery cover. Install 2 x AAA batteries.
You can also monitor battery life in the Job Link app tool manager.
SENSOR CARE: Store JL3MN in a protective cover when not in use to prevent debris or foreign contaminants from entering the barb tip. Do not pressurize the probe above its max specification.
WARNING
Prevent damage, do not drill holes blindly into a plenum that houses the
evaporator or heat exchanger.
Do not place any part of the manometer on hot surfaces such as exhaust fumes.
Doing so can cause personal injury, damage equipment, and void warranty.
Do no apply more than 11.6 psi.
Specifications
Operation
Press for 1 second to power ON/OFF.
Tap to zero measurements.
LED Color Indications
Green slow blink: normal operation
Red slow blink: batteries need to be replaced
Supply or Return Side Switch
The Job Link® System app knows which side you have selected for each probe.
Select P1 or P2 and place it on the system appropriately.
Static Pressure
Static pressure testing ensures if the equipment is operating within factory
specifications.
Gas Pressure
Prevent symptoms like rough starts or overheating your heat exchanger by
checking your gas pressure.
-
See manufacturer’s specification for target inlet and outlet fuel or gas pressures.
-
Shut off main gas supply power to furnace.
-
Zero your JL3MN while at ambient pressure with tubing attached before taking measurements.
-
Remove outlet pressure tap screw and insert the brass screw fitting of the hose into the outlet pressure tap of the gas regulator.
NOTE: Some pressure taps have a 5/16” boss instead of an insert screw. In this case, use the included 5/16” adapter tube. Loosen the tap screw about 1 revolution and slide the tube over the boss. -
If you suspect high or low inlet pressure to the regulator, connect the JL3MN to the inlet tap.
-
Put furnace into operation and begin to take measurements.
Auto Power Off (APO)
The probe will automatically power off after 2 hours. To disable APO until
powered off, while power is on tap twice. The LED will briefly blink red. To
enable APO, while power is on tap twice. The LED will briefly shine red.
Certifications and Module IDs
FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: To assure continued compliance, any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment. (Example – use only shielded interface cables when connecting to computer or peripheral devices).
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This device complies with Industry Canada licence-exempt RSS-247 standard. Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
IC Radiation Exposure Statement: This equipment complies with IC RSS-102 radiation exposure limit set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 0.5 cm between the radiator and your body. Fieldpiece Instruments 1636 West Collins Avenue, Orange, CA 92867
IFETEL Statement
The operation of this equipment is subject to the following two conditions: (1) this device or device may not cause harmful interference, and (2) this device or device must accept any interference, including interference that may cause undesired operation.
Limited Warranty
This probe is warranted against defects in material and workmanship for one
year from date of purchase from an authorized Fieldpiece dealer.
Fieldpiece will replace or repair the defective unit, at its option, subject
to verification of the defect.
This warranty does not apply to defects resulting from abuse, neglect, accident, unauthorized repair, alteration, or unreasonable use of the instrument.
Any implied warranties arising from the sale of a Fieldpiece product, including but not limited to implied warranties of merchantability and fitness for a particular purpose, are limited to the above. Fieldpiece shall not be liable for loss of use of the instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim of such damage, expenses, or economic loss.
State laws vary. The above limitations or exclusions may not apply to you.
Obtaining Service
For international customers, warranty for products purchased outside of the
U.S. should be handled through local distributors. Visit our website to find
your local distributor.
© Fieldpiece Instruments, Inc 2024; v17.5
Read More About This Manual & Download PDF:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>