STELPRO SSFP SELF-REGULATING FREEZE PROTECTION PREASSEMBLED CABLE
IMPORTANT INSTRUCTIONS
Please read and make sure you understand all instructions and safety warnings. Electrical cables, if not installed correctly or are damaged, can cause a fire, shock and arcing hazard.
- Installation must be in compliance with National Electrical Codes (NEC) and the Canadian Electrical Code (CEC).
- Use 30-mA ground fault protection (GFCI) on each heating cable branch circuit for maximum protection.
- Use only fire-resistant insulation, such as fiberglass or preformed foam. Do not embed heating cable in the insulation.
- Use fiberglass or aluminum adhesive foil tape when attaching cable to pipe. Do not use wire or metal clamps.
- Before installing or servicing, disconnect power at service panel.
- Do not twist cable during installation.
- Do not install this heating cable under roofing material.
- Do not expose this heating cable to temperatures above 185°F (85°C), as this will damage the cable.
- Do not use extension cords.
WARNING : Do not use damaged heating cables, power cord or plug. Remove and replace immediately to prevent a fire, shock or arcing hazard
INSTALLATION PIPE
ACCESSORIES REQUIRED
CABLE SELECTION
Letters A-J in the chart represent all SSFP series models.
PIPE DIA. (IN.)
|
TYPE OF PIPE
| PIPE LENGTH (FT)
---|---|---
5| 10| 15| 20| 25| 30| 35| 40| 45| 50| 55| 60| 65| 70| 75| 80| 85| 90| 95|
100| 110| 120| 130| 140| 150
1/2
| Metal| A| B| C| D| E| E| E| F| F| F| G| G| G| G| G| H| H| H| H| H| I| I| J|
J| J
Plastic| A| B| C| D| E| E| E| F| F| F| G| G| G| G| G| H| H| H| H| H| I| I| J|
J| J
1
| Metal| A| B| C| D| E| E| E| F| F| F| G| G| G| G| G| H| H| H| H| H| I| I| J|
J| J
Plastic| B| B| C| D| E| E| E| F| F| G| G| G| G| G| H| H| H| H| H| I| I| I| J|
J| –
1½
| Metal| A| B| C| D| E| E| E| F| F| F| G| G| G| G| G| H| H| H| H| H| I| I| J|
J| J
Plastic| B| C| D| E| E| F| F| G| G| G| H| H| H| H| I| I| I| J| J| J| –| –| –|
–| –
2
| Metal| A| B| C| D| E| E| E| F| F| G| G| G| G| G| H| H| H| H| H| I| I| J| J|
J| –
Plastic| B| C| E| F| F| G| G| G| H| H| H| I| I| J| J| –| –| –| –| –| –| –| –|
–| –
2½
| Metal| A| B| C| D| E| E| E| F| F| G| G| G| G| G| H| H| H| H| I| I| I| J| J|
J| –
Plastic| B| D| E| F| G| G| G| H| H| I| I| J| J| –| –| –| –| –| –| –| –| –| –|
–| –
|
PRODUCT
|
LENGTH
|
VOLTAGE
---|---|---|---
| CODE FT| VOLTS
A| SSFP1W05L0006| 6| 120
B| SSFP1W05L0012| 12| 120
C| SSFP1W05L0018| 18| 120
D| SSFP1W05L0024| 24| 120
E| SSFP1W05L0036| 36| 120
F| SSFP1W05L0050| 50| 120
G| SSFP1W05L0075| 75| 120
H| SSFP1W05L0100| 100| 120
I| SSFP1W05L0125| 125| 120
J| SSFP1W05L0150| 150| 120
E| SSFP2W05L0036| 36| 240
F| SSFP2W05L0050| 50| 240
G| SSFP2W05L0075| 75| 240
H| SSFP2W05L0100| 100| 240
I| SSFP2W05L0125| 125| 240
J| SSFP2W05L0150| 150| 240
NOTE : For each valve or spigot on the pipe, an additional foot of cable is needed. When the cable is longer than the pipe, spiral the excess cable around the pipe length evenly.
ATTACHING CABLE TO PIPE
- Before installing the cable, make sure that all piping is dry and free of any sharp surfaces and edges.
- Attach heating cable to pipe with straight, spiraling or multiple tracing.
- If the heating cable is the same length as the pipe, run it straight along the bottom of the pipe. If two cables are required, position them in the 4 and 8 o’clock positions. If three cables are required, position them in the 11 o’clock or 1 o’clock positions and 4 and 8 o’clock positions.
- If the cable is less than double the pipe length, spiral the cable over the pipe length.
- Any excess cable remaining at the end of the pipe can be doubled back along the pipe.
- Make sure to include any additional heating cable required for valves, spigots, etc.
- Secure the heating cable to the pipe with fiberglass adhesive tape (SSFR03). Do not use vinyl tape, metallic products or wire. On plastic pipes, secure the full length of cable with aluminum foil tape (SSFR-ALUTAPE).
INSTALLING THERMAL INSULATION
- Before insulating, inspect the cable to make sure that it is free of mechanical damage, such as gouges or cuts, etc.
- Cover the pipe, cables, connections and valves with at least 1/2 in. (12.7 mm) thick fiberglass insulation or equivalent. DO NOT leave the cables exposed. For a protection down to -20 °F/-29 ºC, increase insulation to 1 in. (25.4 mm) thick.
- Use fire-resistant materials such as fiberglass wrap. Make sure the insulation is waterproofed (with polyethylene or other vapor barriers) in areas where water may come in contact with the insulation.
- Place the two warning labels on the outer surface of the pipe insulation where clearly visible and at suitable locations to indicate the presence of electric heating cable.
- After installation is complete, turn the circuit breaker on to power the cable. The water inside the pipe should feel warm within one hour.
INSTALLATION
TOOLS REQUIRED
ACCESSORIES REQUIRED
CABLE SELECTION
-
Determine the total length of cable needed by adding the total roof edge length (ft.) x feet of heating cable per foot of roof edge (see table below) roof edge length x 0.5 (for the roof extension factor), the total gutter length (ft.) and the total downspout length (ft. plus 1).
NOTE : The roof edge length (ft.) x feet of heating cable required per foot of roof edge equals the total roof edge cable length required.
NOTE : The roof extension factor is the length of cable required to reach the cable in the gutter from the
roof edge. -
For shingle roofs, add 1 foot (30 cm) of heating cable for each foot (30 cm) of gutter.
-
Add 1 foot (30 cm) of heating cable per foot (30 cm) of downspout.
-
When the downspout is between the gutter ends, double the length of the downspout to determine the length of cable needed.
-
For roof valleys, measure the distance two thirds of the way up and double it. Add this additional length to the overall cable length.
ROOF OVERHANG
|
LENGTH
OF HEATING CABLE
|
CABLE LOOP HEIGHT
---|---|---
|
SHINGLE ROOF METAL ROOF (24 IN. / 60 CM)
|
SHINGLE ROOF METAL ROOF
None| 1.9 ft / 58 cm| 2.5 ft / 76 cm| 18 in. / 46 cm| 18 in. / 46 cm
12 in. / 30 cm| 2.0 ft / 61 cm| 2.5 ft / 76 cm| 18 in. / 46 cm| 24 in. / 60 cm
24 in. / 61 cm| 2.7 ft / 82 cm| 3.5 ft / 107 cm| 30 in. / 76 cm| 36 in. / 90
cm
36 in. / 91 cm| 3.6 ft / 110 cm| 4.5 ft / 137 cm| 42 in. / 107 cm| 48 in. /
122 cm
48 in. / 122 cm| 4.5 ft / 137 cm| 5.5 ft / 168 cm| 54 in. / 137 cm| 60 in. /
152 cm ****
EXAMPLE (SHINGLE ROOF):
- Roof edge length: 15 ft. (with roof overhang of 1 ft.)
- Gutter length: 15 ft.
- Downspout length: 12 ft.
Length of heating cable required:
- Roof edge length 15 ft. × 2 (see table) = 30 ft.
- Gutter length 15 ft.
- Roof extension 15 ft. x 0.5 = 7.5 ft.
- Downspout length 12 ft. +1 = 13 ft. Total 66 ft.
INSTALLING CABLE
-
Determine the best route for the heating cable on roofs and gutters.
-
Route the heating cable to avoid mechanical damage from ladders, etc.
-
Before installing the heating cable, make sure the roof, gutter and downspouts are free from debris, leaves, pine needles or any combustibles.
-
Check the maximum exposure temperature rating of all roof, gutter and downspouts, and select a heater that will not exceed their temperature ratings.
-
Use a downspout cable hanger bracket (SSFR15) to support the heating cable where it enters a downspout to prevent cable from being damaged by the gutter’s edge. It also can be used as a spacer in wider gutters.
-
Run heating cable over top of hanger and secure it using UV resistant cable ties.
-
Use roof clips for SSFP/SSFR cables (SSFR13 – SSFR14) to attach the heating cable to the roof.
-
For roof valleys, measure two thirds of the distance of the way up and double it. Add this additional length to the overall cable length.
-
Attach the two warning labels (included with the heating cable). The labels must be clearly visible on the premises.
OPERATION AND MAINTENANCE
WARNING : Only qualified persons should service or install the system.
Check yearly for any damage to the heating cable and check any ground fault protection device for proper operation. If any damage to cable is found, DO NOT operate until it is replaced.
ºSTELPRO LIMITED WARRANTY
This limited warranty is offered by °STELPRO Design Inc. (“°STELPRO”) and applies to the following product made by °STELPRO: model SSFP. Please read this limited warranty carefully. Subject to the terms of this warranty, ° STELPRO warrants its products and their components against defects in workmanship and/or materials for the following periods from the date of purchase: 2 years. This warranty applies only to the original purchaser; it is non-transferable and cannot be extended.
CLAIM PROCEDURE
If at any time during the warranty period the unit becomes defective, you must
cut off the power supply at the main electrical panel and contact 1) your
installer or distributor, 2) your service center or 3) °STELPRO’s customer
service department. In all cases, you must have a copy of the invoice and
provide the information written on the product nameplate. °STELPRO reserves
the right to examine or to ask one of its representatives to examine the
product itself or any part of it before honoring the warranty. °STELPRO
reserves the right to replace the entire unit, refund its purchase price or
repair a defective part. Please note that repairs made within the warranty
period must be authorized in advance in writing by °STELPRO and carried out by
persons authorized by °STELPRO. Before returning a product to °STELPRO, you
must have a °STELPRO authorization number (RMA). To obtain it, call the
customer service department at: 1-844-°STELPRO. The authorization number must
be clearly written on the parcel or it will be refused.
CONDITIONS, EXCLUSIONS AND DISCLAIMER OF LIABILITY
This warranty is exclusive and in lieu of all other representations and
warranties (except of title), expressed or implied, and °STELPRO expressly
disclaims and excludes any implied warranty of merchantability or implied
warranty of fitness for a particular purpose. °STELPRO’s liability with
respect to products is limited as provided above. °STELPRO shall not be
subject to any other obligations or liabilities whatsoever, whether based on
contract, tort or other theories of law, with respect to goods or services
furnished by it, or any undertakings, acts or omissions relating thereto.
Without limiting the generality of the foregoing, °STELPRO expressly disclaims
any liability for property or personal injury damages, penalties, special or
punitive damages, damages for lost profits, loss of use of equipment, cost of
capital, cost of substitute products, facilities or services, shutdowns,
slowdowns, or for other types of economic loss or for claims of a dealer’s
customers or any third party for such damages. °STELPRO specifically disclaims
all consequential, incidental and contingent damages whatsoever. This warranty
does not cover any damages or failures resulting from: 1) a faulty
installation or improper storage; 2) an abusive or abnormal use, lack of
maintenance, improper maintenance (other than that prescribed by °STELPRO) or
a use other than that for which the unit was designed; 3) a natural disaster
or an event out of °STELPRO’s control, including, but not limited to,
hurricanes, tornadoes, earthquakes, terrorist attacks, wars, overvoltage,
flooding, water damages, etc. This warranty does not cover any accidental or
intentional losses or damages, nor does it cover damages caused by negligence
of the user or owner of the product.
Moreover, it does not cover the cost of disconnection, transport, and installation. The warranty is limited to the repair or the replacement of the unit or the refund of its purchase price, at the discretion of °STELPRO. Any parts replaced or repaired within the warranty period with the written authorization of °STELPRO will be warranted for the remainder of the original warranty period. This warranty will be considered null and void and °STELPRO will have the right to refuse any claims if products have been altered without the written authorization of °STELPRO and if the nameplate numbers have been removed or modified. This warranty does not cover scratches, dents, corrosion or discoloration caused by excessive heat, chemical cleaning products and abrasive agents. It does not cover any damage that occurred during the shipping. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages and some of them do not allow limitations on how long an implied warranty lasts, so these exclusions or limitations may not apply to you. This warranty gives you specific legal rights and you may have other rights which vary from state to state or from province to province.