HBX THM-0100 Programmable Thermostat Instruction Manual

June 12, 2024
HBX

HBX THM-0100 Programmable Thermostat

HBX THM-0100 Programmable Thermostat

KNOWING YOUR THERMOSTAT

General Technical Data
1 x Dry Contact Output
(120VAC 2 Amp Max)
1 x External Thermistor Input
1 x Power Contact: 10-24V, AC or DC

Dimensions 115 x 80 x 27.5mm
Dimensions

ETL Listings:
Meets CSA C22.2 No. 24
Meets UL Standard 873
ETL Control No. 3068143

Storage: +10C to +40C

All programming steps within the thermostat are achieved by using the three buttons (and combinations thereof) located on the right-hand side of the thermostat.
Navigating the Thermostat

The + button is used to scroll up in menu screens and increase a value within specific options.

The – button is used to scroll down in menu screens and decrease a value within specific options.

Pressing the + or – button on their own for 2 seconds while viewing the main “Status Screen” will allow you to quickly adjust your target temperature. Once you have reached the desired target temperature by using the + and – buttons, waiting five seconds will return the thermostat to the initial “Status Screen” mode.

Setting the Thermostat

Thermostat Modes

Enter the “Special Functions” screen by holding down the + and – buttons simultaneously for 5 seconds (from the “Status Screen”). To select the desired option, use the + and – buttons to toggle and the set button to select.

  1. Type – Select between Heating, Cooling or Setpoint modes.
  2. View All – Select “No” to turn off all “Status Screen” information.
    – Select “Time” to only show time.
    – Select “Target” to only show targets.

The Status Screen

The Adjustment Screen

Holding down the set button for 2 seconds while viewing the “Status Screen” will take you into the “Adjustment Screen” for the respective thermostat (heating, cooling or setpoint).

Once you are in the desired options screen, use the + and – button to scroll up and down. Press down the set button to choose the option (the arrow to the left of your chosen option will turn black when you have entered a specific step), then the + and – buttons to adjust the value. Pressing the set button again allows you to scroll between options once again.

Heating Adjustment Steps :

  1. Room Temp – Set this value to be the desired room target. Range from 32°F to 200°F.

  2. Mode – Choose between Room, Floor or Dual mode. Descriptions as follows:

    2A) Room Mode – Sensor temperature providing feedback for the specific room or zone being controlled by the thermostat.

  3. Sensor 1 – Enable the feedback sensor as None, Floor, Room, Outdoor or Room Average in Floor mode.
    i) None – No external sensor is connected to the thermostat.
    ii) Floor – The external sensor is used to display floor temperature.
    iii) Room – The external sensor is used to control the room temperature.
    iv) Outdoor – The external sensor is used to display outdoor temperature.
    v) Room Average – This setting averages the external sensor and internal sensor to control the room temperature.
    2B) Floor Mode – Sensor temperature providing feedback from the floor surface to the thermostat.
    3B) Differential -When in floor mode, the differential option must be set to define the temperature margin that will instigate a heat demand.
    2C) Dual Mode – Sensor temperature providing feedback for both the air temperature and floor sensor temperatures.

  • Over or under heating may occur in Dual mode *
    3C) Floor Max – Floor Max functions as the maximum floor temperature in Dual mode, and will override the room temperature.
    4C) Floor Min – Floor Min functions as the minimum floor temperature in Dual mode, and will override the room temperature.

    1. Celsius or Fahrenheit – Set the display value as either Celsius or Fahrenheit (This option appears as #5 in Dual Mode).
    2. Backlight – Use this option for dimming or powering down the backlight when not in use (Select On or Off). Visible in Room and Floor modes (This option is not applicable in Dual Mode).
    3. Time – Set the time for your appropriate region or time zone. Visible in Room and Floor modes.

Cooling Adjustment Steps :

  1. Room Temp – Set this value to be the desired room target. Range from 32°F to 200°F.

  2. Sensor 1 – Enable the feedback sensor as None, Floor, Room, Outdoor or Room Average.
    a) None – No external sensor is connected to the thermostat.
    b) Floor – The external sensor is used to display floor temperature.
    c) Room – The external sensor is used to control the room temperature.
    d) Outdoor – The external sensor is used to display outdoor temperature.
    e) Room Average – This setting averages the external sensor and internal sensor to control the room temperature.

  3. Celsius or Fahrenheit – Set the display value as either Celsius or Fahrenheit.

  4. Backlight – Use this option for dimming or powering down the backlight when not in use (Select On or Off).

  5. Time – Set the time for your appropriate region or time zone.

Setpoint Adjustment Steps :

  1. Setpoint – Set this value to be the desired Setpoint target. Range from 32°F to 200°F.
  2. Mode – Select between Heat mode or Cool mode.
  3. Differential – A differential of 10° is 5° above setpoint and 5° below setpoint. Range from 2°F to 60°F.
  4. Lag Time – Set the desired lag time interval. Range from 0 seconds to 240 seconds.
  5. Celsius or Fahrenheit – Set the display value as either Celsius or Fahrenheit.
  6. Time – Set the time for your appropriate region or time zone.

WIRING EXAMPLES

MOUNTING INSTRUCTIONS

Once you have wired the terminal block, the THM-0100 can be mounted on the desired interior wall. The unit should be placed in an area clear of drafts or other heating or cooling sources which may influence the temperature reading of the thermostat.

LIMITED WARRANTY

HBX Controls warrants each of its products to be free from defects in workmanship and materials under normal use and service for a period of 24 months from date of manufacture or 12 months from date of purchase from an HBX Authorized Dealer, if within the above documented period after date of manufacture.
If the product proves to be defective within the applicable warranty period, HBX on its sole discretion will repair or replace said product. Replacement product may be new or refurbished of equivalent or better specifications, relative to the defective product. Replacement product need not be of identical design or model. Any repair or replacement product pursuant to this warranty shall be warranted for not less than 90 days from date of such repair, irrespective of any earlier expiration of original warranty period. When HBX provides replacement, the defective product becomes the property of HBX Controls.
Warranty Service, within the applicable warranty period, may be obtained by contacting your nearest HBX Controls office via the original Authorized Agent and requesting a Return Material Authorization Number (RMA #). Proof of purchase in the form a dated invoice/receipt must be provided to expedite the issuance of a Factory RMA.
After an RMA number has been issued, the defective product must be packaged securely in the original or other suitable shipping package to ensure that it will not be damaged in transit. The RMA number must be visible on the outside of the package and a copy included inside the package. The package must be mailed or otherwise shipped back to HBX with all costs of mailing/shipping/insurance prepaid by the warranty claimant.
Any package/s returned to HBX without an approved and visible RMA number will be rejected and shipped back to purchaser at purchaser’s expense. HBX reserves the right, if deemed necessary, to charge a reasonable levy for costs incurred, additional to mailing or shipping costs.

Limitation of Warranties

If the HBX product does not operate as warranted above the purchasers sole remedy shall be, at HBX’s option, repair or replacement. The foregoing warranties and remedies are exclusive and in lieu of all other warranties, expressed or implied, either in fact or by operation of law, statutory or otherwise, including warranties of merchantability and fitness for a particular purpose/application. HBX neither assumes nor authorizes any other person to assume for it any other liability in connection with the sale, installation maintenance or use of HBX Controls products.
HBX shall not be liable under this warranty; if its testing and examination discloses that the alleged defect in the product does not exist or was caused by the purchasers or third persons misuse, neglect, improper installation or testing, unauthorized attempts to repair or any other cause beyond the range of intended use, or by accident, fire, lightning or other hazard.

Limitation of Liability

In no event will HBX be liable for any damages, including loss of data, loss of profits, costs of cover or other incidental, consequential or indirect damages arising out of the installation, maintenance, commissioning, performance, failure or interruption of an HBX product, however caused and on any theory of liability. This limitation will apply even if HBX has been advised of the possibility of such damage.

Local Law
This limited warranty statement gives the purchaser specific legal rights. The purchaser may also have other rights which vary from state to state in the United States, from Province to Province in Canada and from Country to Country elsewhere in the world.
To the extent this Limited Warranty Statement is inconsistent with local law, this statement shall be deemed modified to be consistent with such local law. Under such local law, certain disclaimers and limitations of this statement may not apply to the purchaser. For example, some states in the United States, as well as some governments outside the United States (including Canadian Provinces), may:
Preclude the disclaimers and limitations in this statement from limiting the statutory rights of a consumer (e.g. United Kingdom);
Otherwise restrict the ability of a manufacturer to enforce such disclaimers or limitations; or grant the purchaser additional warranty rights which the manufacturer cannot disclaim, or not allow limitations on the duration of implied warranties.

Customer Support

Phone: +1 403-720-0028 Fax: +1 403-720-0054
Email: info@lhbxcontrols.com Web: www.hbxcontrols.com

HBX Control Systems Inc.
4516 – 112th Avenue SE
Calgary, AB Canada T2C 2K2