EATON HLR20-3 Moeller Series HLR Solid State Relay Instructions

June 3, 2024
EATON

EATON-HLR20-3-Moeller-Series-HLR-Solid-State-Relay-
logo

EATON HLR20-3 Moeller Series HLR Solid State Relay

EATON-HLR20-3-Moeller-Series-HLR-Solid-State-Relay-product-
image

Instruction Leaflet

Electric current! Danger to life!
Only skilled or instructed persons may carry out the following operations

Mounting on DIN rail

EATON-HLR20-3-Moeller-Series-HLR-Solid-State-Relay-02

Terminations

1/L1,3/L2,5/L3,2/T1,4/T2,6/T3

HLR20/3… HLR20/3… HLR30/3…
a = 12 mm (0.47″) a = 12 mm (0.47″) UL: a = 11 mm (0.43″)
  IEC: a = 12 mm (0.47″)
2 x 2.5 – 6.0 mm2 1 x 2.5 – 6.0 mm2 1 x 2.5 – 25 mm2
(2 x 14 – 10 AWG) (1 x 14 – 10 AWG) (1 x 14 – 3 AWG)
2 x 1.0 – 2.5 mm2 1 x 1.0 – 4.0 mm2 1 x 2.5 – 16 mm2

(2 x 18 – 14 AWG)
2 x 2.5 – 4.0 mm2| | (1 x 18 – 12 AWG)| | (1 x 14 – 6 AWG)
 (2 x 14 – 12 AWG)| |
2 x 1.0 – 2.5 mm2| 1 x 1.0 – 6.0 mm2| 1 x 4.0 – 25 mm2
(2 x 18 – 14 AWG)
2 x 2.5 – 6.0 mm2| (1 x 18 – 10 AWG)| (1 x 12 – 3 AWG)
 (2 x 14 – 10 AWG)    | |
M4, Posidriv 2| M4, Posidriv 2| M5, Posidriv 2
UL: 2.0 Nm (17.7 lb-in)| UL: 2.0 Nm (17.7 lb-in)| UL: 2.5 Nm (22 lb-in)

→Use 75 °C copper (Cu) conductors
A1(+), A2( – )EATON-HLR20-3-Moeller-Series-HLR-Solid-State-
Relay-09

→Use 60/75 °C copper (Cu) conductors

UL508|
---|---
| I cc max [k A rms ]| max. size [A]| Class| Voltage [V AC]|
__HLR20/3 | __100 | __30 |   J or CC| __max. 600 |
HLR30/3| 100| 40| J| max. 600|