Function/Application

The anemometer is used to measure air flow rates, volumetric flow rates and wind speeds. Integrated sensors constantly register the ambient temperature, relative humidity and calculate the dew point temperature. The USB interface additionally permits realtime logging on a PC.

  1. Dew point/wet-bulb temperature
  2. Ambient temperature °C / °F
  3. Relative humidity % rH
  4. Auto Off function
  5. Low battery charge
  6. USB data transfer
  7. Units of area
  8. Measured value factor x10
  9. Units of wind speed
  10. Units of volumetric flow
  11. MIN/MAX
  12. Hold measured value
  13. Functions

  1. ON/OFF
  2. 1/4″ tripod connection
  3. Impeller
  4. Illuminated LC display
  5.  Function
  6. Hold / dew point/wet-bulb temperature
  7. Display lighting / USB transfer
  8. Unit of measurement
  9. MIN-/MAX display

Safety instructions

  • The device must only be used in accordance with its intended purpose and within the scope of the specifications.
  • The measuring tools and accessories are not toys. Keep out of reach of children.
  • Do not expose the device to mechanical stress, extreme temperatures, moisture or significant vibration.

Calibration

The meter needs to be calibrated and tested on a regular basis to ensure it produces accurate measurement results. We recommend carrying out calibration once a year.

Inserting the batteries

Open battery compartment and insert batteries corresponding to installation symbols. Ensure correct polarity.

ON/OFF
AUTO-Off (20 min.)

Room climate

When switched on, the ambient temperature and relative humidity are permanently shown on the display. The dew point or wet-bulb temperature can also be set in place of the ambient temperature. Change between the different values by pressing and holding the „DP/WP“ button.
You can set the units °C/°F by pressing and holding the „UNIT“ button.

Please refer to the following instructions for use when determining wind speed or volumetric flow rate:

  • Position the device parallel to the flow source
  • Place the device as close as possible to the flow source
  • Use the MAX function to determine the position with the strongest air flow
  • Avoid direct sunlight during measurement
Wind speed

After switching on by pressing the „MODE“ button, activate the „VEL“ function. Press the „UNIT“ button repeatedly to change the units: m/s (metres per second), km/h (kilometres per hour), mil/h (miles per hour), ft/m (feet per minute), ft/s (feet per second), knots.

Press the „MAX/MIN“ button to display the highest and/or lowest value during a measurement. As its name suggests, the „HOLD“ button enables you to hold the current measured value.

| The „MODE“, „UNIT“ and „MIN/MAX“ functions are deactivated while the „HOLD“ function is activated. These functions are available again after pressing the „HOLD“ button once more.
---|---

Volumetric flow

The outlet area of the flow source must first be defined before determining volumetric flow.


After switching on by pressing the „MODE“ button, activate the function for measuring volumetric flow until „AREA“ appears on the display. The first number begins to flash. Use the „5“ (+) and „SET“ (change decimal place) buttons to enter the determined area. The area can be set both in square metres (m²) as well as in square feet (ft²). The end of the input is signalled by a double beep.

Activate the „FLOW“ function by pressing the „MODE“ button. After selecting the corresponding unit – CMM (cubic metres per minute), CFM (cubic feet per minute) and CMS (cubic metres per second) – press the „UNIT“ button to determine the volumetric flow based on the set area.

| The „MODE“, „UNIT“ and „MIN/MAX“ functions are deactivated while the „HOLD“ function is activated. These functions are available again ! after pressing the „HOLD“ button once more
---|---

MIN/MAX / HOLD

The MAX function is activated by pressing the „MAX/MIN“ button. The measured value currently displayed corresponds to the largest measured value. Press the „MAX/MIN“ button again to activate the MIN function and show the smallest measured value. To deactivate „MAX/MIN“, press the button again until the value is no longer shown on the display.

Press the „HOLD“ button to hold the current measured value on the display.
Press the button again to deactivate this function.

USB transfer

Measured values can be transferred to a PC in realtime via the integrated USB interface. The values can then be stored and documented using the supplied software. First install the software and the corresponding drivers from the CD to the terminal unit. Follow the instructions for the installation routine. Once you have successfully installed the software, connect the measuring instrument to the PC and set up a USB connection.

Start the software and activate the USB function by pressing and holding the „USB“ button. The software now shows the measured values both in numerical as well as in graphic form.

For further information on how to use the software, refer to the Help function that contains a detailed description of the functions.

Technical specifications

Measuring range Resolution Accuracy

Wind speed
0.80…30.00 m/s| 0.01 km/h| ± (2.0% + 50 digits)
1.40…144.0 km/h| 0.01 ft/s| ± (2.0% + 50 digits)
1.30…98.50 ft/s| 0.01 knots| ± (2.0% + 50 digits)
0.80…58.30 knots| 0.01 mil/h| ± (2.0% + 50 digits)
0.90…67.20 mil/h| 1 ft/m| ± (2.0% + 5 digits)
78…5900 ft/m| 1 ft/m| ± (2.0% + 5 digits)
Ambient temperature, dew point, wet-bulb
-10°C…60°C| 0.1°C| ± 1.5°C
Relative humidity
20…80 %rH| 0.1 %rH| ± 3% (25°C)
< 20 and > 80 %rH| 0.1 %rH| ± 5% (25°C)
Measuring range| Resolution| Area
CMM, CFM, CMS
0…99990 m3/min| 1 m3/min| 0…9.999 m2
0…99990 ft3/min| 1 ft3/min| 0…9.999 ft2
0…9999 m3/sec| 1 m3/sec| 0…9.999 m2

Power supply| 1 x 6F22 9V
Operating temperature| 0°C…40°C
Max. relative humidity| 85%
Dimensions (W x H x D)| 85 x 165 x 38 mm
Weight| 200 g


EU directives and disposal

This device complies with all necessary standards for the free movement of goods within the EU.
This product is an electric device and must be collected separately for disposal according to the European Directive on waste electrical and electronic equipment.
Further safety and supplementary notices at: www.laserliner.com/info

SERVICE

Umarex GmbH & Co. KG
– Laserliner –
Möhnestraße 149, 59755 Arnsberg, Germany
Tel.: +49 2932 638-300, Fax: +49 2932 638-333
laserliner@umarex.de

Umarex GmbH & Co. KG
Donnerfeld 2
59757 Arnsberg, Germany
Tel.: +49 2932 638-300, Fax: -333
www.laserliner.com

Documents / Resources

| Laserliner 082.140A AirflowTest-Master Thermo Anemometer [pdf] Instruction Manual
082.140A, AirflowTest-Master Thermo Anemometer, 082.140A AirflowTest-Master Thermo Anemometer
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Laserliner User Manuals

Related Manuals