STIEBEL ELTRON 189800 Air Quality Sensor FEQ for Ventilation Unit Instruction Manual
- June 5, 2024
- STIEBEL ELTRON
Table of Contents
ELTRON 189800 Air Quality Sensor FEQ for Ventilation Unit
Instruction Manual
General information
The chapter “Operation” is intended for appliance users and heating
contractors.
The chapter “Installation” is intended for heating contractors.
Note
- Read these instructions carefully before using the appliance and retain them for future reference.
- Pass on the instructions to a new user where appropriate.
- Observe the operating and installation instructions of the associated ventilation unit.
Safety instructions
Structure of safety instructions
KEYWORD Type of risk
Here, possible consequences are listed that may result from failure to
observe the safety instructions.
Steps to prevent the risk are listed.
Symble | Type of Risk |
---|---|
Electrocution |
Keywords
KEYWORD | Meaning |
---|---|
DANGER | Failure to observe this information will result in serious injury or |
death.
WARNING| Failure to observe this information may result in serious injury or
death.
CAUTION| Failure to observe this information may result in nonserious or minor
injury.
Other symbols in this documentation
Note
General information is identified by the symbol shown on the left.
- Read these texts carefully.
Symbol | Meaning |
---|---|
Material damage |
(Appliance and consequential losses, environmental pollution)
| Appliance disposal
This symbol indicates that you have to do something. The action you need to
take is described step by step.
Units of measurement
Note
All measurements are given in mm unless stated otherwise.
Safety
Intended use
This device is intended to adjust the fan stage automatically or manually. Any
other use beyond that described shall be deemed inappropriate. Correct use
includes the observation of these instructions as well as those of the
connected ventilation unit.
This device can be used with the following ventilation units:
- LWZ70E, LWZ 170 E plus, LWZ 370 plus
- TVZ70€E, TVZ 170 E plus, TVZ 370 plus
Test symbols
See the type plate on the inside of the front cover.
Appliance description
This device is intended to adjust the fan stage automatically or manually. The device incorporates a filter change indicator that is subject to the hours run.
- Operating mode key
- Air quality LED indicator
- Rotary selector for selecting the required air quality
- LEDstrip for indicating the selected operating mode
Note
All LEDs flash simultaneously to indicate that the filter in the ventilation
unit needs to be changed.
Party mode | Fan stage 3 |
---|---|
Normal mode | Fan stage 2 |
Setback mode | Fan stage 1 |
Standby mode | The ventilation unit is in standby mode. Subject to the |
appliance type and settings, the fans are either idle or generate the minimum
airflow.
Automatic mode| The ventilation unit changes from setback mode to standard
mode when the air quality is poor. The air quality indicator illuminates.
Note
After the power supply has been switched on, the device will be in automatic
mode.
Select from the various operating modes by repeatedly touching the operating
mode key.
The LED strip indicates the selected operating mode.
Adjusting the air quality
You determine the air quality you perceive as optimal by switching the air
quality rotary selector higher step by step.
The device incorporates an air quality sensor, that reacts to gases and vapors
that can oxidize, such as carbon monoxide, methane, isobutane, hydrogen, and
ethanol. Such gases may be generated by smoking, cooking, or when a larger
number of people congregate in one room, for example.
The air quality indicator illuminates when the constituents in the air exceed
the selected value.
Maintenance
Filter change
The device is equipped with an integral timer function to indicate when the
filter in the ventilation unit should be changed.
All LEDs will flash simultaneously if a filter change is required.
Note
The filter change intervals determined by the device are guidelines only and
may deviate from the actual level of filter contamination.
Observe the filter change indicator of the connected ventilation unit.
Subject to the selected operating mode, the filter may need changing every 2
to 6 months. In the case of permanent party mode, the device will signal a
need for a filter change after only 2 months. If the unit operates primarily
in setback mode, the interval will stretch to a maximum of 6 months.
In standby mode, the device stores the remaining time up to the next filter
change and will restart with that value when the unit starts up again.
Subject to the selected operating mode, the filter may need changing every 2
to 6 months. In the case of permanent party mode, the device will signal a
need for a filter change after only 2 months. If the unit operates primarily
in setback mode, the interval will stretch to a maximum of 6 months.
In standby mode, the device stores the remaining time up to the next filter
change and will restart with that value when the unit starts up again.
Note
Following a filter change, hold down the operating mode key for at least 3
seconds, in order to reset the filter change timer function.
Safety
Only a qualified contractor should carry out the installation, commissioning,
maintenance, and repair of the appliance.
General safety instructions
We guarantee trouble-free function and operational reliability only if the
device is used in conjunction with the associated original ventilation units.
Instructions, standards, and regulations
Note
- Observe all currently applicable regulations and requirements.
Preparations
Installation site
The device is suitable for mounting on a surface box or on level surfaces.
Note
Select an installation location inside the lead room that is suitable for
capturing the air constituents.
Preparing the device for installation
Rotary selector
Carefully lever out the rotary selector using a small screwdriver.
Locking screw
- Undo and remove the locking screw.
- Initially pull away the front cover from the r.h. side and then entirely.
Assembly
WARNING Electrocution
The device is supplied with power via the connecting cable that links it to
the ventilation unit. There is a risk that you could touch ‘live’ parts during
the installation.
- Therefore isolate the ventilation unit from its power supply.
Fixing holes
Using the fixing holes, you can secure the base either on a surface box or in
a suitable location on a wall.
Mounting on surface box
Note
- Mounting on a surface box requires that both surface box screws are on the vertical plane.
- Undo both surface box screws.
- Position the base on the surface box. Whilst doing this, insert the surface box screws through the base fixing holes.
- Align the base and tighten the screws.
Wall mounted installation
Material damage
When drilling fixing holes, check for the possible presence of cables that may
run underneath the plaster.
Note
- To secure the base, use rawl plugs and screws that are appropriate for the type of wall construction.
Power supply
Note
- Keep the cable core ends of the power cable as short as possible to prevent them protruding beyond the terminal area, and avoid contact with the PCB elements.
Wiring diagram
1 Power input | 4 Standby mode |
---|---|
2 Earth | 5 Party mode |
3 Not assigned | 6 Normal mode |
Note
- When assigning terminals, observe the operating and installation instructions of the connected ventilation unit.
- Apply the stripped wires in accordance with the wiring diagram.
- Route the cores of the power cable in front of the terminal Strip to save space.
- Guide the front cover on the I.h. side at a slant into the groove of the base.
- Push the front cover onto the base.
- Insert the locking screw and tighten it.
- Push on the rotary selector.
Commissioning
Commissioning
- Switch on the power supply to the ventilation unit.
Note
After the power supply has been switched on, the device will be in automatic
mode.
- Check for correct function.
Appliance handover
- Explain the device’s functions to the users and familiarise them with its operation.
- Instruct the user on the filter change indicator.
- Make users aware of potential dangers and what to do in the case of a fire.
- Hand over these instructions.
Shutting down
Note
The device is supplied with power via the connecting cable that links it to
the ventilation unit.
- Isolate the ventilation unit from the power supply.
Recommissioning
See chapter “Commissioning”.
Specification
Electrical data Min. DC voltage | V | 12 |
---|---|---|
Max. DC voltage | V | 48 |
Rated current | mA | 50 |
Versions
……| | Plastic casing
Casing
Colour| | white
IP rating| | IP20
Dimensions Height| E
E|
75
Width| | 75
Depth| mm| 25
Connecting cable Minimum cross-section| mm2|
0,5
Maximum length| m| 30
| |
Guarantee
The guarantee conditions of our German companies do not apply to appliances
acquired outside of Germany. In countries where our subsidiaries sell our
products, a guarantee can only be issued by those subsidiaries. Such a
guarantee is only granted if the subsidiary has issued its own terms of the
guarantee. No other guarantee will be granted.
We shall not provide any guarantee for appliances acquired in countries where
we have no subsidiary to sell our products.
This will not affect warranties issued by any importers.
Environment and recycling
We would ask you to help protect the environment. After use, dispose of the various materials in accordance with national regulations.
STIEBEL ELTRON GmbH & Co. KG
Dr.-Stiebel-Str. 33 | 37603 Holzminden
Tel. 05531 702-0 | Fax 05531 702-480
info@stiebel-eltron.de
www.stiebel-eltron.de
tecalor GmbH
Luchtringer Weg 3 | 37603 Holzminden
Tel. 05531 99068-700 | Fax 05531 99068-712
info@tecalor.de
www.tecalor.de
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>