BARTEC 19269-5 Wireless Relative Humidity and Temperature Sensor Instruction Manual

June 3, 2024
BARTEC

BARTEC 19269-5 Wireless Relative Humidity and Temperature Sensor

Installation Instruction

Note on instructions
When working in hazardous areas, the safety of personnel and equipment depends on compliance with the relevant safety regulations. The people in charge of installation and maintenance bear a special responsibility. It is essential that hey have an exact knowledge of the applicable rules and regulations.

The instructions provide a summary of the most important safety measures and must be read by everyone working with the product so that they will be familiar with the correct handling of the product.
The instructions have to be kept for future reference and must be available throughout the expected life of the product.

Description
The Intrinsically Safe Wireless Relative Humidity and Temperature Sensors, EXaminer® RHT,from BARTEC Technor are independent standalone sensors that communicates via 5.0.
The sensors can be mounted as a stand-alone unit or fitted into Ex enclosures. The EXaminer® RHT measures relative humidity and the temperature where it is installed. The sensor is powered by non-chargeable, non-serviceable batteries. When the battery is empty the sensor must be replaced. The EXaminer® RHT operates wireless and has no other interface options.

As shown in Figure 3 the EXaminer® RHT is one unit, consisting of the electronic housing, an Oring and a counter nut. All electrical and electronic parts are integrated in the unit. The
EXaminer® RHT comes in two main version where the housing is made of either SS316L or
POM. The SS316L version has an Ex db ib, Ex db eb ib or Ex tb certification while the POM version has an Ex eb ib, Ex ib and Ex tb certification.
Both versions come with a M32x1,5 male thread.

Type EXaminer® RHT

Explosion protection

ATEX
Ex type of protection 0470

  • II 2 G Ex db ib IIC T4 Gb
  • II 2 G Ex eb ib IIC T4 Gb
  • II 2 G Ex ib IIC T4 Gb
  • II 2 D Ex ib IIIC T113°C Db
  • II 2 D Ex ib tb IIIC T113°C Db

EU Type Examination Certificate
Presafe 19 ATEX 20726 X

IECEx

  • Ex type of protection
  • Ex db ib IIC T4 Gb
  • Ex eb ib IIC T4 Gb
  • Ex ib IIC T4 Gb
  • Ex ib IIIC T113°C Db
  • Ex ib tb IIIC T113°C Db

Certificate of Conformity
IECEx PRE 19.0087X
Ambient temperature range
-40°C ≤ Ta ≤ +80°C

Ingress Protection
IP66

Technical data

Supply data
Un : Battery powered, internal battery
In : NA
P : NA

Production year
As stated on the marking label of the product

Serial number
As stated on the marking label of the product

Marking label
Please refer to notes on the marking label

Text label
SEE INSTALLATION INSTRUCTION
Depending on the technical execution

Other applicable documents

  • Reference is made to the 19568-6 User-
    Guide Examiner® RHT App.

The retention of these documents is mandatory.

Instrinsically Safe Product, BARTEC EXaminer® RHT
Read these installation instructions carefully before mounting, installation, commissioning and maintenance.

Notes on the marking label
Specific conditions of use which are important for the installation, the use or the maintenance of the product will be unabbreviated adopted into this manual.

In case of loss always mention the type and serial/ batch number at BARTEC office.

Type Code [EXaminer®] Ex type of protection
RHT 100 D S BT Ex db ib IIC T4 Gb
RHT 100 DT S BT Ex db ib IIC T4 Gb Ex tb IIIC T113°C Db
RHT 100 E P BT Ex eb ib IIC T4 Gb
RHT 100 ET P BT Ex eb ib IIC T4 Gb Ex tb IIIC T113°C Db
RHT 100 I P BT Ex ib IIC T4 Gb
RHT 100 IT S BT Ex ib tb IIIC T113°C Db
RHT 100 T P BT Ex tb IIIC T113°C Db
RHT 100 T S BT Ex tb IIIC T113°C Db

The number ‘100’ signifies the shape of the sensor body.

  • The letter ‘D’ signifies Ex db ib sensor.
  • The letter ‘E’ signifies Ex eb ib sensor.
  • The letter ‘I’ signifies Ex ib sensor.
  • The letter ‘T’ signifies Ex tb sensor.
  • The letter ‘S’ signifies sensor body in SS316L.
  • The letter ‘P’ signifies sensor body in POM.
  • The letter ‘BT’ signifies communication.

Safety Instructions

The technical data, which are on the marking label need to be maintained just like all possible warning (caution) texts on the outside of the product.
On the basis of the Category or EPL marking you’ll have to verify that the product is installed in the correct zone.

Zone Category EPL Suitability
0 1G only Ga only ü
1 2G Gb ü
2 3G or 2G Gc or Gb ü
20 1D only Da only û
21 2D Db ü
22 3D or 2D Dc or Db ü

This table gives only information about main Equipment Protection Level which is applicable for the product. The marking label is leading.
The table shows in which zone this product may be installed under application of the belonging EU-Type Examination Certificate or IECEx Certificate of Conformity.
Rebuilds and changes to the product are not permitted.

Use explosion proof products in good shape only, which means; undamaged, healthy maintenance condition.
Take care of all national applicable safety & work instructions and all safety instructions mentioned in this manual whenever work is necessary to Ex products.

For installation requirements we redirect you to:
EN 60079-14: 2014 or IEC 60079-14: 2013.

Marking
Particularly important points in these instructions are marked with a symbol:

DANGER indicates a hazardous situation which,if not avoided, will result in death or serious injury.

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE is used to address practices not related to personal injury.

Note
Important instructions and information on effective, economical and environmentally compatible handling.

Conformity to standards
The explosion proof control panels have been examined according following standards (depending on technical execution and application more than one standard may be applicable).

Main standards

  • EN 60079-0:2018 / IEC 60079-0:2017 Ed 7.0
  • EN 60079-1:2014 / IEC 60079-1:2014-06 Ed 7.0
  • EN 60079-7:2015/A1:2018 / IEC 60079-7:2015
  • Ed 5.0
  • EN 60079-11:2012 / IEC 60079-11:2011 Ed 6.0
  • EN 60079-31:2014 / IEC 60079-31:2013 Ed 2.0

Technical data
Page 1 of these installation instructions describes the exact technical execution. Below follows an overview of possible variants and the general technical data.

Marking according EN-IEC 60079-0
The marking on page 1 is leading.
Type(s) of Protection against ignition

  • Ex db ib IIC T4 Gb
  • Ed eb ib IIC T4 Gb
  • Ex ib IIC T4 Gb
  • Ex ib IIIC T113°C Db
  • Ex ib tb IIIC T113°C Db

Gas group
This product is certified for gas: IIC.

Dust group
This product is certified for dust: IIIC.

Temperature class or maximum surface temperature
The temperature class for this product is: T4 /T113°C to T153°C.

Equipment Protection Level
The EPL for this product is: Gb and or Db

Ingress Protection degree
The product has an IP66 rating according to EN/ IEC 60529. One must ensure that the O-ring is intact and placed correctly when mounted into an equipment to ensure this IP rating.

Ambient temperature range

  • 40°C to +80°C for Ex db ib and Ex ib.
  • -40°C to +70°C for Ex eb ib.
  • -40°C to +40°C to +80°C for Ex ib / ib tb.

Maximum ambient temperature range

  • -40°C to +80°C for Ex db ib and Ex ib.
  • -40°C to +70°C for Ex eb ib.
  • -40°C to +40°C to +80°C for Ex ib / ib tb.}
    Ambient temperature range as indicated on page 1 is leading.

OPTIONAL MARKING FOR GAS:

  • Ex ib IIC T4 Gb -40°C≤Tamb≤+80°C
  • Ex db ib IIC T4 Gb -40°C≤Tamb≤+80°C
  • Ex eb ib IIC T4 Gb -40°C≤Tamb≤+70°C

OPTIONAL MARKING FOR DUST:

  • Ex ib tb IIIC T153°C Db -40°C≤Ta≤+80°C*
  • Ex ib tb IIIC T143°C Db -40°C≤Ta≤+70°C
  • Ex ib tb IIIC T133°C Db -40°C≤Ta≤+60°C
  • Ex ib tb IIIC T123°C Db -40°C≤Ta≤+50°C
  • Ex ib tb IIIC T113°C Db -40°C≤Ta≤+40°C
  • Ex ib IIIC T153°C Db -40°C≤Ta≤+80°C
  • Ex ib IIIC T143°C Db -40°C≤Ta≤+70°C
  • Ex ib IIIC T133°C Db -40°C≤Ta≤+60°C
  • Ex ib IIIC T123°C Db -40°C≤Ta≤+50°C
  • Ex ib IIIC T113°C Db -40°C≤Ta≤+40°C
    Only SS 316 version

Note
For deviating ambient conditions, you are advised to have consultation with BARTEC.

Enclosure material
Acid resistant stainless steel SS316L.
Black POM (polyoxymethylene).

Max. nominal supply voltage
3 V (battery powered)

Battery capacity
3000 mAh

Max. working voltage
3 V (battery powered)

Max. supply cable cross section
Not possible, battery powered

Transport, Storage

NOTE
Damage to the control panel through incorrect transport or incorrect storage.

  • Transport and storage are permissible in original packaging only.

Assembly / Disassembly

WARNING

Risk of injury due to incorrect proceedings.

  • When installing and operating Ex equipment, take care of the applicable safety standards and generally known electrical safety standards.

  • WARNING – POTENTIAL ELECTROSTATIC CHARGING HAZARD.
    Important Note:

  • The EXaminer® RHT cannot be opened and has no physical wiring terminals.
    Communication takes place only through the communication protocol integrated in the electronics of the unit.

Mounting and Installation

Mounting
The EXaminer® RHT can be mounted as a free standing, stand-alone component. It can be mounted in a through hole Ø32, using the counter nut or it can be screwed into a machined and threaded hole M32x1,5 6H also with the use of a counter nut. If it is mounted in an equipment one has to make sure that the Oring is correctly fitted in order to reach an IP66 rating of the installation. Maximum surface roughness Ra should be ≤ 1,6μm. Maximum diameter of a through hole is Ø33.

Fig 1. Cut-out for through hole for the EXaminer® RHT.

Fig 2. Machined threaded hole for the EXaminer® RHT.

Fig 3. Physical dimensions of the EXaminer® RHT (all dimensions in mm).

BARTEC 19269-5 Wireless Relative Humidity and Temperature
Sensor-3

Installation

  • In a free hole:
    Place the EXaminer® RHT in the premade hole, make sure the O-ring is placed correctly (towards the outer surface of the equipment which it is installed into) and secure it with the counter nut. Tighten securely to 15 Nm.

  • In a machined and threaded hole: Screw the EXaminer® RHT in the premade threaded hole, make sure the O-ring is placed correctly (towards the outer surface of the equipment which it is installed into) and secure with the counter nut.

  • Mounting the sensor on components or surfaces with normal operating surface temperature of 70°C for Ex eb ib type alternatively 80°C for Ex db ib / Ex eb ib types or higher must be avoided.

  • Avoid mounting of the sensor in a position that will allow a drop of condensing water to cover the sensing area.

Commissioning

Before commissioning, check that:

  • The product has been installed in compliance with the manufacturer instructions.
  • The product is not damaged.
  • The device functions perfectly.
  • All electric parts of the EXaminer® RHT are factory tested, and no field work is necessary.

Operation

DANGER
Death or serious injury through improper use.

  • The EXaminer® RHT may be operated only within the technical limits that apply to it (see page 1).

  • The EXaminer® RHT itself has no physical operator interface. Data is transferred between the smartphone/tablet/network and the sensor wireless through the communication interface to the EXaminer® App.

  • All electric parts of the EXaminer® RHT sensor are factory tested, and no field work is necessary. Factory settings are normal range 2 min and long range 10 seconds.
    Advertisement interval is 10 s. Settings can be altered on the device by use of the Examiner® Temp Humidity App.

  • The internal battery is not replaceable.
    Battery status is reported by the sensor.
    Battery level above 2.6V is OK. Battery level between 2.6V and 2.2V indicates that the sensor is close to end-of-life. When battery level goes below 2.2V, the sensor has come to end-of-life.
    19568-6 User-Guide Examiner® RHT App will display this as green battery symbol above 2.6V, yellow between 2.6V and 2.2V and red below 2.2V.
    Et end-of-life, the EXaminer® RHT sensor has to be replaced by a new unit.

App menu navigation

  • Reference is made to the 19568-6 User-
    Guide Examiner® RHT App.

Reading data with the Examiner App

  • Reference is made to the 19568-6 User-
    Guide Examiner® RHT App.

Settings

  • Reference is made to the 19568-6 User-
    Guide Examiner® RHT App.
    Updating EXaminer® firmware

  • Contact your distributor.
    Maintenance and Fault Clearance
    Risk of injury due to incorrect proceedings.

  • The national valid regulatory for maintenance, inspection, and repair is applicable for electrical equipment for the use in hazardous areas.

  • Damaged Ex components must be directly replaced by genuine BARTEC parts.

Maintenance cycles
The EXaminer® RHT does not require any specific maintenance at regularly scheduled intervals. One must make sure that the sensor area at the end of the sensor is kept free of dirt and moisture.
In case of malfunction, reference is made to the 19568-6 User-Guide Examiner® RHT App.
Inspection of the EXaminer® RHT is limited to ensuring that encapsulation, seals and mounting are tight and secure. There are no moving parts or adjustments and possible, nor can the housing be opened.

NOTICE
Any attempts made to open the housing, may void the warranty.

Inspection
Follow the national law and regulatory for inspection of explosion proof equipment. This should be done by skilled and qualified personnel only.

Replacing the EXaminer® RHT

  • In case of a fatal error of an EXaminer® RHT, the sensor must be replaced by a new unit. Repair or maintenance are not allowed by unauthorized personnel.

Troubleshooting

  • Troubleshooting involves responding to error messages displayed by the 19568-6
    User-Guide Examiner® RHT App. Error messages that may occur are self- explanatory and intuitive. For further details; reference is made to the 19568-6
    User-Guide Examiner® RHT App. If you require assistance, contact your distributor.

Specific conditions
The sensor shall be marked with the following warning text:

Special conditions – see instructions
EXaminer® RHT Ex db ib version:
“X”- Ex d model is suitable for mounting on appropriate threaded entry (M32x1.5 6H) of flameproof enclosures with max. reference explosion pressure up to 16.5 bar. It must be secured with “counter nut”. Type test for resistance to pressure carried out by means of static pressure test as specified in Cl. 15.2.3.2 of EN 60079-1:2014 at the pressure value 66 bar. “X”- Equipment must be mounted on the metallic enclosure and/or contact with earth must be assured.

EXaminer® RHT Ex eb ib version: “X”- Ex e model must be secured by “counter nut”. Tightening torque of 15 Nm must be applied to maintain the IP grade. The maximum allowed diameter of the plane through hole is ø35 mm. “X”- Equipment must be mounted on the metallic enclosure and/or contact with earth must be assured.
EXaminer® RHT Ex ib and Ex tb version: “X”- Equipment must be mounted on the metallic enclosure and/or contact with earth must be assured.

Disposal
The sensor contains metal, electronic components and plastic parts. Therefore, the statutory requirements for disposing of electronic scrap (WEEE) must be observed (e.g. disposal by an approved disposal company). The sensor is also marked with the wheeled bin symbol for WEEE:

Service Addresses

BARTEC TECHNOR AS
Vestre Svanholmen 24, N 4313 Sandnes
Norway

BARTEC Explosion Proof Appliances (Shanghai) Co., Ltd.
New Building 7, No. 188 Xinjun Ring Road
Caohejing Pujiang Hi-tech Park
CN 201114 Shanghai
China

BARTEC GmbH
Max-Eyth-Str. 16, D 97980 Bad Mergentheim
Germany

BARTEC Middle East FZE
RA-08, HB-01, Jebel Ali Free Zone, Dubai
United Arab Emirates

BARTEC NEDERLAND B.V.
Boelewerf 25, NL 2987 VD Ridderkerk
Netherlands

BARTEC Pte. Ltd.
63 Hillview Avenue, #07-20/23 Lam Soon
Building, SG 669569 Singapore
Singapore

BARTEC US Corp.
650 Century Plaza Drive, Suite D120
Houston, TX 77073
USA

BARTEC Varnost d.o.o.
Cesta 9. Avgusta 59, SI 1410 Zagorje ob Savi
Slovenia

Vestre Svanholmen 24
4313 SANDNES
NORWAY
Tel.: +47 51 844100
Fax: +47 51 844101
[email protected]
www.bartec-technor.no

Reservation Technical data subject to change without notice. Changes, errors and misprints may not be used as a basis for any claim for damages.