KOHLER KOH10DC-7600 Power Reserve Energy Storage System User Manual
- June 4, 2024
- Kohler
Table of Contents
KOHLER KOH10DC-7600 Power Reserve Energy Storage System
Residential Energy Storage System
The KohlerR Power Reserve energy storage system can maintain power to critical items such as refrigerators, computers, TVs, lights, and garage doors when the grid goes down or for autonomous off- grid applications. The system can also provide automated cost saving through energy rate arbitrage and system power flow control.
Models
- KOH10DC-7600 • KOH10AC-7600
- KOH15DC-7600 • KOH15AC-7600
- KOH20DC-7600 • KOH20AC-7600
Standard Features
- LiFePO4 battery chemistry
- Up to 4 kW solar DC input, 80- 500 VDC. 4 MPPTs
- Up to 6 kW of continuous power output off- grid
- Outdoor-rated NEMA 3R rated enclosures
- Always connected, cellular (included) and WiFi
- 10-Year limited warranty, industry best throughput, 70% SOC
Operating Modes
- Backup
- Time- of- Use
- Self- Supply
Communication
- WiFi, LTE- M
Performance Specifications, AC Models
Model | KOH10AC | KOH15AC | KOH20AC |
---|
Battery Input Data
Usable Capacity(kWh)| 10| 15| 20
Battery Type| LiFePO4 (LFP)
Battery Voltage Range (V)| 102.4 (89.6- 115.2)| 153.6 (134.4- 172.8)| 204.8
(179.2- 230.4)
Max. Charging Current (A)| 50
Max. Discharging Current (A)| 50
AC Output Data (On- Grid)
Output Voltage Range (VAC)| 211 to 264 @ 240
Nominal Output Frequency (Hz)| 60
Max Output to Grid (W)| 5760| 7600| 7600
Max Output from Grid (W)| 5760| 9120| 9120
Continuous Output @240V (W)| 5120| 7600| 7600
Continuous Output to Grid (A)| 20.8| 31.7| 31.7
AC Output Data (Back-Up)
Nominal Output Voltage| 120/240
Continuous Output @240V (W)| 5760| 7600| 7600
Peak Output @240V (W)| 5760, 60 sec.| 8460, 60 sec.| 9120, 60 sec.
PV String Input Data
Max AC Input Power (W)| 7600
Efficiency
PV Max. Efficiency| 97.6%
CEC Efficiency| 96.1%
Battery Charged by PV, Max. Efficiency| 98.1%
Battery Charge/Discharge to AC, Max. Efficiency| 96.6%
General Data
Operating Temperature Range| – 20° to 55° C (- 4° to 131° F)
Relative Humidity Operating| 0- 95%
Altitude| 3000m
Noise (dB)| <45
Operating Modes| Backup, TOU, Self- Supply
Rating| NEMA 3R
Standby Self- Consumption (W)| <20
Communication Protocol| Modbus / CAN
Cycle Life| 6,000 at 100% DOD
DC Protection| Main Contactor / Fuse
Mounting| Wall and Floor Mount (battery enclosure feet must rest on the floor)
[ MPPT = Maximum Power Point Tracking
Performance Specifications, DC Models
Model | KOH10DC | KOH15DC | KOH20DC |
---|
Battery Input Data
Usable Capacity(kWh)| 10| 15| 20
Battery Type| LiFePO4 (LFP)
Battery Voltage Range (V)| 102.4 VDC (89.6- 115.2 VDC| 153.6 VDC (134.4- 172.8
VDC)| 204.8 VDC (179.2- 230.4 VDC)
Max. Charging Current (A)| 50
Max. Discharging Current (A)| 50
AC Output Data (On- Grid)
Output Voltage Range (VAC)| 211 to 264 @ 240
Nominal Output Frequency (Hz)| 60
Max Output to Grid (W)| 7600 | 7600| 7600
Max Output from Grid (W)| 9120 | 9120| 9120
Continuous Output to Grid (A)| 20.8| 31.7| 31.7
AC Output Data (Back-Up)
Nominal Output Voltage, L- N, L1- L2 (VAC)| 120/240
Continuous Output @240V (W)| 5120| 7600| 7600
Peak Output @240V (W)| 5760, 60 sec| 8640, 60 sec| 9120, 60 sec
PV String Input Data
Max DC Input Power (W)| 11400
Max DC Input Voltage (V)| 600
MPPT Range (V) [| 80- 550
Start- up Voltage (V)| 95
MPPT Range for Full Load (V) [| 230- 500
Nominal DC Input Voltage (V)| 380
Max. Input Current (A)| 12.5
Max. Short Current (A)| 15.2
MPP Trackers (quantity) [| 4
Efficiency
PV Max. Efficiency| 97.6%
PV CEC Efficiency| 97.2%
Battery Charged by PV, Max. Efficiency| 98.1%
Battery Charge/Discharge to AC, Max. Efficiency| 96.6%
General Data
Operating Temperature Range| – 20° to 55° C (- 4° to 131° F)
Relative Humidity Operating| 0- 95%
Altitude| 3000m
Noise (dB)| <45
Communication (Built- in)| 4G Cellular Communication, WiFi
Operating Modes| Backup, TOU, Self- Supply
Rating| NEMA 3R
Standby Self- Consumption (W)| <20
Communication Protocol| Modbus / CAN
Cycle Life| 6,000 at 100% DOD
DC Protection| Main Contactor / Fuse
Mounting| Wall and Floor Mount (battery enclosure feet must rest on the floor)
- For the DC10 model, limits without PV (nighttime) are equal to the limits shown for AC10. [ MPPT = Maximum Power Point Tracking
Product Specifications
Weights and Dimensions (AC and DC)
Model, kWh| 10| 15| 20
Weight| 240 kg (530 lb )| 329 kg (725 lb )| 420 kg (925 lb)
Size, Battery Enclosure| 700 x 1270 x 230 mm (27.5 x 50 x 9 in.)| 1524 x 1270
x 230 mm (60 x 50 x 9 in.)| 1524 x 1270 x 230 mm (60 x 50 x 9 in.)
Size, Inverter| 415 x 791 x 175 mm (16.3 x 31.1 x 6.9 in.)
Size, Auto-transformer| 345 x 275 x 175 mm (13.6 x 10.9 x 6.9 in.)
Compliance
Inverter
Grid Regulation| UL1741 SA (CA Rule 21), UL9540, HECO Rule 14, IEEE 1547, IEEE
1547.1, CSA 22.2
Safety Regulation| UL 1741, CSA 22.2 No. 107- 01, UL 1998, UL1699B
EMC| FCC Part 15 Class B
Battery
Battery| UL 1973, UL 1642
Energy Storage System| UL9540
Communication Protocol| Open ADR 2.0b, Open ADR
Battery Performance Specifications
Battery Input Data
Usable Capacity| 10, 15, 20 kWh
Initial Capacity (nominal)| 2.56 kWh per pack
Battery Chemistry| LiFePO4 (LFP)
Max Charge Current| 50 A
Max Discharge Current| 50 A
Efficiency
Battery Charged by PV Efficiency| 98.10%
Battery Round Trip Efficiency| 96.60%
**** Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohlerr Power Systems dealer for availability.