Pulsar AWOP-325PR Distribution Junction Box Instruction Manual
- June 4, 2024
- Pulsar
Table of Contents
Pulsar AWOP-325PR Distribution Junction Box
Specifications
- Model: AWOP-325PR
- Version: 1.0
- Type: Distribution Junction Box
- Cable Size : 3×2.5mm²
- Edition: 5 from 05.02.2024
- Supersedes Edition: 4 from 21.05.2019
- Technical Assessment: National Technical Assessment CNBOP-PIB-KOT-2019/0109-3704
- Performance Verification: CNBOP-PIB 063-UWB-0174
- Enclosure Protection Class: IP20
- Material: DC01 1mm steel plate, colour RAL 3001 (red)
- Dimensions: 190 x 80 x 30 mm (WxHxD)
- Temperature Range: Suitable for installation
- Weight: Net/gross weight
Product Usage Instructions
Description
The junction box for fire alarm systems is designed for connecting fire
protection devices in cable installation systems with fire resistance
according to the DIN 4102-12 standard.
Installation
The junction box should be mounted directly to a concrete base class min.
B20 or natural stone using two steel pins of adequate fire resistance. Cables
should be mounted using handles at intervals of 600 mm.
Mounting Instructions
- Bushings and expansion bolts should be recessed at least 30 mm into the concrete.
- Tension on the pin should not exceed 500 N.
- Ensure the functional class of cable assemblies containing the junction box will not be affected by falling building elements.
Cable Installation
- Lead installation cables through appropriate bushings.
- Mount cables with cable holders inside the enclosure.
WEEE Label
Do not dispose of waste electrical and electronic equipment with normal
household waste. Follow the European Union WEEE Directive for proper disposal.
Distribution Junction Box 3×2,5mm
- Edition: 5 from 05.02.2024
- Supersedes edition: 4 from 21.05.2019
National Technical Assessment CNBOP-PIB-KOT-2019/0109-3704 3rd edition of 23
May 2019.
National assessment and verification of constancy of performance CNBOP-PIB
063-UWB-0174
Description
The junction box for fire alarm systems is designed for connecting fire
protection devices in cable installation systems with fire resistance
according to the DIN 4102-12 standard, where the uninterruptible power supply
or transmission of the signal in case of fire is required.
The junction box is designed to guarantee the mechanical ability to keep the
cable routes capable of guaranteeing the uninterruptible power supply and
transmission of telecommunication signals in the fire zone.
The junction box can be used for the power supply of fire protection
equipment, such as ventilators and smoke vents, fire alarm control panels,
emergency warning systems, etc. The junction box enables to connect and split
3 wires cable.
Elements of the junction box
Component
No.
| Description
---|---
[1]| Mounting holes for mounting to a surface.
[2]| Cable glands.
[3]| Protection connector PE.
[4]| Connection sockets.
Technical parameters
Voltage | 450 V AC max |
---|---|
Diameter of installation cable | Max. 10mm |
Cross-section of the cable | Max. 2,5mm2 |
Protection class | IP20 |
Enclosure | DC01 1mm steel plate, color RAL 3001 (red) |
Dimensions | 190 x 80 x 30 [mm] (WxHxD) |
Temperature range during installation | -25ºC to +60ºC |
Mounting | 136mm Φ5,5 mm |
Net/gross weight | 0,52 / 0,55 [kg] |
Installation
The junction box for fire alarm systems should be mounted directly to the
concrete base class min. B20 or natural stone. Other building materials of
adequate strength and of fire resistance class of at least R90 are also
approved for use.
The junction box for fire alarm systems should be mounted to the ceiling or
wall using two steel pins of adequate fire resistance. The cables should be
mounted using handles at intervals of 600 mm. The mounting distance between
the cables (handles) and the edge of the junction box is maximally 100 mm.
Pay attention to the following boundary conditions:
- a) The bushings and expansion bolts should be recessed at least 30 mm into the concrete.
- b) Tension on the pin should not exceed 500 N.
- c) Alternatively, pins with well-documented fire protection design can also be used.
- d) It should be ensured that the functional class of the cable assemblies containing junction boxes for fire alarm systems will not be adversely affected by falling building elements
Installation cables should be led through the appropriate bushings and then mounted with cable holders located inside the enclosure.
WEEE LABEL
Waste electrical and electronic equipment must not be disposed of with normal
household waste. According to European Union WEEE Directive, waste electrical
and electronic equipment should be disposed of separately from normal
household was
MORE INFORMATION
- Pulsar sp. j.
- Siedlec 150, 32-744 Łapczyca, Poland
- Tel. (+48) 14-610-19-45
- e-mail: sales@pulsar.pl
- http://www.pulsar.pl
FAQ
- Q: What is the maximum voltage supported by the junction box?
- A: The junction box supports a maximum voltage of 450 V AC.
- Q: What is the recommended mounting material for the junction box?
- A: The junction box should be mounted to a concrete base class min. B20 or natural stone. Other building materials of adequate strength and fire resistance are also approved.