Pulsar AWOP-325PR Distribution Junction Box Instruction Manual

June 4, 2024
Pulsar

Pulsar AWOP-325PR Distribution Junction Box

Pulsar-AWOP-325PR-Distribution-Junction-Box-PRODCUT

Specifications

  • Model: AWOP-325PR
  • Version: 1.0
  • Type: Distribution Junction Box
  • Cable Size : 3×2.5mm²
  • Edition: 5 from 05.02.2024
  • Supersedes Edition: 4 from 21.05.2019
  • Technical Assessment: National Technical Assessment CNBOP-PIB-KOT-2019/0109-3704
  • Performance Verification: CNBOP-PIB 063-UWB-0174
  • Enclosure Protection Class: IP20
  • Material: DC01 1mm steel plate, colour RAL 3001 (red)
  • Dimensions: 190 x 80 x 30 mm (WxHxD)
  • Temperature Range: Suitable for installation
  • Weight: Net/gross weight

Product Usage Instructions

Description
The junction box for fire alarm systems is designed for connecting fire protection devices in cable installation systems with fire resistance according to the DIN 4102-12 standard.

Installation
The junction box should be mounted directly to a concrete base class min. B20 or natural stone using two steel pins of adequate fire resistance. Cables should be mounted using handles at intervals of 600 mm.

Mounting Instructions

  • Bushings and expansion bolts should be recessed at least 30 mm into the concrete.
  • Tension on the pin should not exceed 500 N.
  • Ensure the functional class of cable assemblies containing the junction box will not be affected by falling building elements.

Cable Installation

  • Lead installation cables through appropriate bushings.
  • Mount cables with cable holders inside the enclosure.

WEEE Label
Do not dispose of waste electrical and electronic equipment with normal household waste. Follow the European Union WEEE Directive for proper disposal.

Distribution Junction Box 3×2,5mm

  • Edition: 5 from 05.02.2024
  • Supersedes edition: 4 from 21.05.2019

National Technical Assessment CNBOP-PIB-KOT-2019/0109-3704 3rd edition of 23 May 2019.
National assessment and verification of constancy of performance CNBOP-PIB 063-UWB-0174

Description

The junction box for fire alarm systems is designed for connecting fire protection devices in cable installation systems with fire resistance according to the DIN 4102-12 standard, where the uninterruptible power supply or transmission of the signal in case of fire is required.
The junction box is designed to guarantee the mechanical ability to keep the cable routes capable of guaranteeing the uninterruptible power supply and transmission of telecommunication signals in the fire zone.
The junction box can be used for the power supply of fire protection equipment, such as ventilators and smoke vents, fire alarm control panels, emergency warning systems, etc. The junction box enables to connect and split 3 wires cable.

Elements of the junction box

Component

No.

| Description
---|---
[1]| Mounting holes for mounting to a surface.
[2]| Cable glands.
[3]| Protection connector PE.
[4]| Connection sockets.

Pulsar-AWOP-325PR-Distribution-Junction-Box-1

Technical parameters

Voltage 450 V AC max
Diameter of installation cable Max. 10mm
Cross-section of the cable Max. 2,5mm2
Protection class IP20
Enclosure DC01 1mm steel plate, color RAL 3001 (red)
Dimensions 190 x 80 x 30 [mm] (WxHxD)
Temperature range during installation -25ºC to +60ºC
Mounting 136mm Φ5,5 mm
Net/gross weight 0,52 / 0,55 [kg]

Installation

The junction box for fire alarm systems should be mounted directly to the concrete base class min. B20 or natural stone. Other building materials of adequate strength and of fire resistance class of at least R90 are also approved for use.
The junction box for fire alarm systems should be mounted to the ceiling or wall using two steel pins of adequate fire resistance. The cables should be mounted using handles at intervals of 600 mm. The mounting distance between the cables (handles) and the edge of the junction box is maximally 100 mm.

Pay attention to the following boundary conditions:

  • a) The bushings and expansion bolts should be recessed at least 30 mm into the concrete.
  • b) Tension on the pin should not exceed 500 N.
  • c) Alternatively, pins with well-documented fire protection design can also be used.
  • d) It should be ensured that the functional class of the cable assemblies containing junction boxes for fire alarm systems will not be adversely affected by falling building elements

Installation cables should be led through the appropriate bushings and then mounted with cable holders located inside the enclosure.

WEEE LABEL
Waste electrical and electronic equipment must not be disposed of with normal household waste. According to European Union WEEE Directive, waste electrical and electronic equipment should be disposed of separately from normal household was

Pulsar-AWOP-325PR-Distribution-Junction-Box-2

MORE INFORMATION

www.pulsar.pl

FAQ

  • Q: What is the maximum voltage supported by the junction box?
    • A: The junction box supports a maximum voltage of 450 V AC.
  • Q: What is the recommended mounting material for the junction box?
    • A: The junction box should be mounted to a concrete base class min. B20 or natural stone. Other building materials of adequate strength and fire resistance are also approved.

Read User Manual Online (PDF format)