LCN Benchmark® AU9100 Series
Low Energy Operators
Installation Manual
LCN Low Energy Operators should be installed in accordance with the current Allegion LCN installation instructions.
Commissioning and Servicing of installed units must be carried out by an Allegion Approved, Authorised Technician
1 GENERAL
The LCN Benchmark® 9100 Series is an automatic electromechanical swing door operator for use on hinged, centre pivoted, and offset pivoted doors. The controller is a microprocessor based system, tracking the door position at any time during the cycle. When activated the Benchmark® 9100 drives the door to the full open position creating the potential energy in the spring. When closing the electrical power is reduced and the door closes by controlling the potential energy release in the spring force. The activating circuit opens the door from any position on the closing swing. During power failure the Benchmark® 9100 acts as a manual door closer (size 3). Door opening and closing cycles, including opening speed, back check speed, hold open time delay, closing speed, and latch position are all adjustable.
WARNING! Always disconnect main power to the operator prior to servicing or cleaning
2 REPLACEMENT PARTS AND SYSTEM COMPONENTS
3 PRE-INSTALLATION SITE AND PRODUCT CHECK
3.1 Check that the product model is correct for the required application
3.2 Check that all parts listed for the installation are received
3.3 Check architectural drawings and final approved shop drawings for
position of frame and structural openings
3.4 Check header and frame dimensions and required clearances
3.5 Ensure door weight is less than 90Kgs. For heavier doors consult
supplier
3.6 Check that a 240 Volt, single phase, 60 Hz, fused supply (5 amp fuse
maximum) is available at the side of the jamb within approximately 1 Meter of
the header. Approved type conduit is recommended for 240V systems
3.7 If an electric lock is to be connected to the system, the maximum
current draw is 2 Amps. The switching relay contact is a maximum resistive
current of 2 Amps.
3.8 The supply must be a dedicated circuit from the main circuit breaker
panel and must not be connected into building lighting circuit with
fluorescent lights
4 OPERATOR INSTALLATION
4.1 Remove control box from mounting bracket, then remove Motor/Gearbox from bracket
4.1 Remove control box from mounting bracket, then remove Motor/Gearbox
from bracket
4.2 Prepare header frame Pull system …………………See Page 5
Push system…………………See Page 6
NOTE
For push units with a reveal greater than 150 mm refer to installation
sheet included in the extended arm Packaging.
4.3 Install operator-mounting bracket on the header/frame.
4.4 Install motor/gearbox on operator mounting bracket, then install control
box on bracket Go to wiring page 7
Pull System
Framed Header and Door Preparation
5 WIRING
CAUTION
- Make sure all wires are properly dressed and secured to prevent interference
- Route all wiring away from moving parts, sharp edges, and heat sources
- Use copper conductors only
- Do not modify the factory wiring or connect into existing electrical circuits or devices
5.1 Refer to the appropriate wiring diagram for the standard control box (Page 22) or the diagram supplied for custom applications. And connect the following cables
- Ground cable (Ground the operator properly with the earth from main supply
- Hall effect Cable (do not wrap the hall effect cable around the motor cable)
- Motor power cable (do not wrap the motor cable around the hall effect cable)
- Control box power cable
5.2 Connect Activate, Safety, Key switch, and lock accessories as needed.
Refer to the accessory instruction/s for any accessories used. Do not connect
any remote activating device to the door unless it is located within line of
sight of the door
5.3 When wiring is complete go to “Arm and cover installation” on page 8
6 ARM AND COVER INSTALLATION
WARNING
- Keep hands, clothing, wires, tools, ETC away from the operator motor when the operator is turned on
6.1 Make sure the operator power switch is turned OFF
6.2 Install a jumper across the control box MAIN ACT T28 and COMMON T27
6.3 Turn the operator power switch on. The operator motor will activate
and drive to the full open position.
6.4 Attach the arm to the operator spindle loosely with the 8-mm socket
head screw (for push systems ensure adjusting boss is inserted correctly).
6.5 Attach the arm to the door
6.5.1 For push systems attach the push arm shoe to the door
6.5.2 For pull systems, slide the pull arm roller into the track, insert a track cap on each end of the track, and attach the track to the door.
6.6 Adjust the arm
6.6.1 For pull systems, remove the locking screw from the arm
6.6.2 For the push system remove the locking screw from the arm
6.7 Keep the door in the full open position and adjust the arm length as
necessary to align the door at 90 degrees from closed. When the arm is
adjusted to the correct length, tighten up the 8mm socket head screw that
secures the arm to the operator spindle and ensure this is secure, then
tighten the arm locking screw
6.8 Turn off the power operator switch. The door closes
6.9 Remove the jumper from the control box T27, T28
6.10 Test the operator (See operational check” on page 11) and continue
with step 6. 10
6.11 Adjust the operator as required( see “Operator Adjustment” on page
12) and continue with step
6.12 Snap optional end cap insert (from screw bag) into the end cap
opposite the on/off switch.
6.13 Install the cover assembly on the operator
6.14 Release the operator for service ( see “Release for Service” on page
14)
7 OPERATIONAL CHECK
7.1 Set the Key switch to Auto (1 Way) and turn on the operator power
switch
7.2 Activate the operator using the activation device, the operator will
perform one sizing cycle
Sizing cycle: Occurs after a legitimate activation signal is received,
after power has been turned on. During the size cycle, the door opens and
closes one time.
7.2.1 If the door does not open at all during sizing cycle
7.2.2 Check door for binding
7.2.3 If an electromechanical lock is being used, check that the lock
disengages before the operator opens the door.
7.2.4 Check fuses, Circuit breakers, and connections.
7.2.5 Adjust the operator and check door operation (See “Operator
Adjustment on page xx)
Opening speed 75%
Back check speed 75%
Hold open time delay Minimum
Latch position Maximum
Closing speed 50%
SW1, 2, 3, 4 OFF
If the door does not open fully during size cycle check the door for binds
Increase the back check speed slightly and check door operation continue increasing back check speed until door opens fully
7.3 If the door slams open decrease the back check speed slightly and
check door operation. Continue decreasing back check speed until the door
opens without slamming
7.4 After the sizing cycle is complete and the door is closed, apply a
maintained activation signal and check that the door remains open while the
signal is applied.
7.5 If a door safety device is being used:
7.6 Door open safety
When the door is in the closed position activate the safety device, then try
to activate the door the door should remain closed.
Activate the door, as the door is opening activate the safety device the door
should stop, and then slowly drive to the full open position.
7.7 Door close safety
Activate the door then maintain activation of the safety device, the door
should open and remain open.
As the door is closing, activate the safety device, the door should re-open to
the open position, time out and then close.
7.8 When the door is operating properly, continue with step 6.10 on page
9
8 OPERATOR ADJUSTMENT
See table below and diagrams on page 18 for operator feature adjustment. After
adjustment, cycle the door
several times and check for proper operation, then continue with step 6.11 on
page 9.
NOTE
Adjust operator for the slowest operation practical in accordance with the
latest AS_5007 standards for powered doors for pedestrian access and egress.
Opening speed 5 sec’s or more
Closing speed 3 sec’s or more
9 RELEASE FOR SERVICE
9.1 Remove all tools, installation equipment, and debris from the
vicinity of the door.
9.2 Install all safety, traffic control, and instruction labels on the
door as required by the latest AS_5007 Standard. Failure to do this leaves the
installer LIABLE for any accident that might occur. This must be done.
9.3 Verbally instruct the owner or person in charge of the proper
operation of the door.
9.4 Instruct the owner or person in charge to routinely inspect the door
for the following
- Occasional damage
- Developing problems
- Minor preventative maintenance
9.5 Instruct the owner or people in charge who and where to call for service and maintenance when required.
IMPORTANT
Make sure to install all safety, traffic control and instruction decals on the
door as required
10 LCN AU9100 (Briton 2500) V4 SOFTWARE
10.1 OPERATION
10.1.1 Sizing
From start up (size) the door will activate from morning entry (24Hrs,T9, T10) regardless of key switch position, 1 Way input (T27,T28) with key switch in one way. 2 Way input (22, T23) with key switch in two way, or key switch Hold Open. The first movement will be in the open direction – The speed of the sizing cycle is automatic and cannot be set from a potentiometer the door drives opened to the full open position where the system sets the counter to full open. The door closes at close speed then latch up to closed position where the system sets the counter for closed position. From these two parameters opened and closed position the system calculates all the other parameters it requires for normal operation i.e. latch position back check position etc.
- Notes
If the encoder is connected for opposite direction or faulty or disconnected the door will operate erratically continuously opening ½ way closing latching and re-opening. This will continue to occur until power is switched off
10.1.2 Auto Reverse on open
The auto reverse open is set from the backcheck position pot. This sets the level of current required to trip the door as it is opening.
Normal operation
Key switch, activation, morning entry/fire alarm, locking, and safety.
10.1.3 Standard operation
Upon a legitimate activation signal the door accelerates up to open speed, monitoring the current load on the drive output. (If the current reaches a level above the set datum the door will stop and close). The door travels at the set speed (Potentiometer setting) until it reaches the set backcheck position, where the speed (Potentiometer setting) is decreased to back check speed. When the door stops at hold open position the system sets the hold open speed and holds the door open until activation and or timer is cleared. The door will then close at close speed, (Potentiometer setting) up to latch position (Potentiometer setting). Where the speed is decreased by driving the motor in the open direction (fixed setting), the power is set such that the spring will overcome this power and continue to allow the door to close up to the closed position. During the open cycle the safe opening (T1, T2) is active and the Safety side Adj Pot sets the angle at which the sensor is redundant, this can be set from Closed up to back check position. During the closing cycle the safe closing (T5, T6) is active and the Activate side Adj pot sets the angle the sensor is redundant, this can be set from Opened up to a few degrees of closed position.
General
24Hr operates the door regardless of key switch position the door will drive
open and remain in the open position as long as the contact is made (Program 4
is the exception) Key switch position OFF no activation or safety operates.
Electric lock operates when door closed dependant upon function selection
Electric lock operation is set from the function selector the time delay is
fixed Key switch Position 1 Way the activation from internal Activate (T27,
T28) safety operates. Electric lock operates when door closed dependant upon
function selection Key switch Position 2 way the activation from internal
Activate (T27, T28) and external Activation (T22, T23) safety operates.
Electric lock does not operate when door closed Key Switch H.O The door
operates to the open position and remains in the open position safety is by
passed (If safety activated the door will open slowly)
10.2 FUNCTION SELECTION
10.2.1 Standard (0)
Operates as a standard door with electric lock operating in OFF and 1 WAY
- Eyetech Activation T5, T6 (Closing Cycle)
- Eyetech Safety T1, T2 (Opening Cycle)
- F/A T9, T10
- 1 Way T27, T28
- 2 Way T22, T23
- Door open T14
- Key switch off T12
- T8 Not Used
10.2.2 Lock in OFF Only (1)
Operates as a standard door with electric lock operating in OFF only.
This selection will give a fast activation in Auto or 1 Way from closed as
there is no delay for lock operation.
10.2.3 Lock in 1 Way Only (2)
Operates as a standard door with electric lock operating in 1 Way only
10.2.4 PNG in OFF (3)
Operates as a standard with Push & Go operating in key switch OFF
10.2.5 Door closes and Unlocks in Fire Alarm (4)
Operates as a standard Fire Alarm Normally closed if open circuit door closes and will remain Unlocked
10.3 FUNCTION CHART
10.4 CONTROL BOX SETUP