WILO Star RS Gas Boiler Circulation Pump Instruction Manual

June 3, 2024
wilo

WILO Star RS Gas Boiler Circulation Pump

WILO Star RS Gas Boiler Circulation Pump-PRO

General Information

These Operating Instructions explain the functions and operation of the pump when installed and ready for use. The figures referred to in the text can be found on the fold-out page at the front.

Use as prescribed
The circulating pump (hereafter referred to simply as a pump or general unit) is used to pump liquids in pipe systems.
The pump must not be used for handling drinking water or food-related liquids.

  • Its main fields of application are:
    • Hot-water heating, various systems,
    • Industrial, closed circulating systems.
  • Specific details:
    • Type ST: for thermal solar systems
    • Type RSG: for geothermal systems
    • Type AC: for air-conditioning units and cold-water distribution.

Terms (Fig. 1)

WILO Star RS Gas Boiler Circulation Pump-1

  1. Suction joint
  2. Condensate outlet
  3. Pump housing
  4. Pressure joint
  5. Terminal box
  6. Cable entry
  7. Speed switch
  8. Ventilation
  9. Rating plate
  10. Motor housing

Rating plate

WILO Star RS Gas Boiler Circulation Pump-12

Connection and electrical data

  • Voltage: 1~230V ±10%

  • Mains frequency: 50Hz
    Power consumption

  • Pmax: Rating plate

  • Motor speed, max.: Rating plate
    Protection

  • category IP: Rating plate

  • Speed setting: 3 stages *

  • Fitting length: 130/180 mm
    Perm. operating

  • pressure, max.: 10 bar
    Perm. medium temperatures

  • min./max.: -10/+110 °C
    Perm. ambient

  • temperatures max.: +40 °C

  • Min. inlet pressure** at suction side at:

    • + 50 °C: 0.05 bar
    • + 95 °C: 0.3 bar
    • + 110 °C: 1.0 bar

For double pumps the additional switchgear S2R 3D is required for time- controlled main/reserve or additional/peak-load operation.
The values are valid up to 300 m above sea level. For higher elevations add: 0.01 bar/100 m. The minimim inlet pressure must be maintained in order to avoid cavitation noise!

Permissible fluids:

  • Heating water acc. to VDI 2035
  • Water and water/glycol mixtures in a ratio up to 1:1. Glycol mixtures require a reassessment of pump hydraulic data in line with the increased viscosity and depending on mixing ratios. Only approved makes of additives with corrosion inhibitors must be used in strict compliance with manufacturers’ instructions.
  • For use of other kinds of fluids consult WILO first

Safety

These instructions contains basic reference which must be strictly adhered. It is therefore imperative for the installer and operator to carefully read these instructions prior to installation and commissioning. Please observe, not only the safety directions under the main heading „safety rules“, but also those added and specially marked under the ensuing headers. Safety marks contained in these instructions Safety rules contained herein which, if not complied with, may be dangerous to persons are specially highlighted by the following danger symbols:

  • Danger from electrical causes:
  • Safety references which, if not complied with, may cause damage to the pump / installation or impair its functions are highlighted by the word:

Staff training
The personnel installing the pump / unit must have the appropriate qualifications for this work.

Dangers from non-observance of safety rules
Non-observance of safety reference may cause personal injury or damage to the pump or installation. Failure to comply with the safety references could invalidate warranty and/or damage claims. In particular, non-compliance may, for example, cause the following dangerous situations:

  • Failure of important pump or unit functions,
  • Causing personal injury due to electrical or mechanical causes.

Safety rules for the operator
Local regulations for the prevention of accidents must be observed. Dangers caused by electrical energy must be excluded. Local or general regulations [e.g. IEC, VDE, etc.] and directives from local energy supply companies are to be followed.

Safety rules for inspection and installation work
The operator must ensure that all inspection and installation work is carried out by authorised and qualified specialists who have carefully studied these instructions. Work on the pump/unit must be carried out only with the machine switched off and at compete standstill.

Unauthorized modification and manufacture of spare parts
Alterations to the pump or installation may only be carried out with the manufacturer’s agreement. The use of original spare parts and accessories authorised by the manufacturer will ensure safety. The use of any other parts may invalidate claims invoking the liability of the manufacturer for any consequences.

Unauthorised operating methods
The operating safety of the pump or installation supplied can only be guaranteed if it is used in accordance with paragraph 1 of the operating instructions. Under no circumstances should the limit values given in the datasheet be exceeded.

Transport/Interim storage

ATTENTION! The pump contains electronic components and must be protected against moisture from outside and mechanical damage (shock/impact) (Fig. 7). It must not be exposed to temperatures outside the range -10 °C to +50 °C. (Fig. 7).

Description of pump/accessories

Products delivered

  • Complete pump
  • 2 flat gaskets,
  • Installation and operating instructions

Pump description

  • In the wet-running pump all rotating parts are surrounded by the flow medium, including the motor rotor.
  • A shaft seal, which would be subject to wear and tear, is not required. The pumping medium lubricates the friction bearing and cools both bearing and rotor.
  • No motor overload protection is required.
  • Even the maximum overload current cannot damage the motor. The motor operates non-overloading.

Speed setting (Fig. 8)

The speed of the pump can be adjusted with a 3-position rotary button. In position 3 the speed is approx. 40…50 % of the maximum speed with the power consumption being reduced to 50 %.

Particular features of the pumps Double pumps
contain two identically constructed pump heads in a common pump housing with integrated change-over flap. Each pump can run in single mode, and both pumps can also run simultaneously in parallel mode. The operating modes are main/reserve operation or incremental/peak-load operation. The pump heads can be selected of different capacities. Double pumps are suitable of adapting a pipe system to suit individual load characteristics. The S2R 3D control unit must be connected to control the different operating modes. The ST… and RSG… pumps are pumps with special hydraulics for use in solar thermal systems (Type ST…) or geothermal systems (Type RSG…). The AC 20/…-I(O) pump is an airconditioning pump with a plasitc (composite) pump housing for use in air- conditioning units and cold-water distribution.

  • In the AC ../..-I:
    (I = inline) pump the pump housing is designed „inline“-, i. e. suction and pressure connections are in line.

  • The AC ../..-O:
    (O = offline) pump is equipped with axial suction and radial discharge connection.

Accessories
Accessories must be ordered separately.

  • Inserts for the pipe connection of the screwed-pipe pump.
  • S2R 3D switchgear for double pump.
  • Thermal insulating units for later insulation of the ST/RSG 25 pump.

Assembly/ Installation

  • Assembly should only take place once all welding and soldering work and the rinsing of the pipe network has been completed. Dirt can have an adverse effect on the functioning of the pump.

  • The pump must be installed in an easily accessible position to facilitate inspection or replacement.

  • It is recommended that shut-off devices be fitted before and after the pump. This will save having to drain and refill the system if the pump needs replacing. The fittings are to be installed so that any water that escapes cannot drip onto the pump motor or terminal box.

  • When installed into the flow pipe of an open-vented system, the open safety vent must be connected to the system on the inlet side of the pump.

  • Pump to be mounted with the shaft in the horizontal plane in such a way that it is not stressed by the pipework. (Installation positions in Fig. 2).WILO Star RS Gas Boiler Circulation Pump-2

  • An arrow on the pump casing indicates the direction of flow (Fig. 3, pos.1).
    WILO Star RS Gas Boiler Circulation Pump-3

  • Secure the pump against twisting by using a spanner (Fig. 4).

  • In order to attain the correct terminal box position the motor housing can be turned once the motor fastening screws have been losened (Fig. 5).WILO Star RS Gas Boiler Circulation Pump-4

Do not damage the flat gasket. If necessary use a new gasket: Ø 86 x Ø 76×2.0 mm EP. For units which are to be insulated, only the pump housing may be insulated. The motor and condensate openings must remain free (Fig. 3, pos. 2).

Electrical connection
Electrical connection must be carried out by a qualified and licensed electrician in strict conformity to ruling national conditions and local regulations (e.g. VDE regulations in Germany).

  • According to Part 1 of the VDE 0730, the pump must be connected to the electrical supply by a solid wire equipped with a plug connection or an all-pole switch. The width of the contact gap must be at least 3 mm.
  • To guarantee protection against dripping water and the strain relief of the PG screwed joint, a connecting cable of suitable external diameter is to be used (e.g. H 05 VV-F 3 G 1.5).
  • When using the pump in units where the water temperature exceeds 90 °C, a connecting cable with corresponding heat resistance must be used.
  • The supply cable must be laid in such a way that it never touches the pipework and/or the pump and motor casing.
  • Check that the mains current and voltage comply with the data on the rating plate.
  • Make mains connection as shown in Fig. 6.
  • The connecting cable can be fed through the PG screwed joint either to the left or right. If necessary, the blind plug and PG screwed joint are to be exchanged. If the terminal box is positioned on the side, always insert the PG screwed joint from below (Fig. 5)
  • Pump/installation must be earthed in compliance with regulations.
  • When connecting automatic switchgear (for double pumps), follow the appropriate Installation and Operating Instructions.

Operation

System filling and venting
The pump may need venting e.g. if the heating and pump are working but the heating element remains cold. If there is air in the pump chamber, the pump will not pump water. Carefully fill the unit with water. Solar thermal systems must be filled with ready for use mixtures. The pump must not be used to mix the medium in the system. The pump is normally vented automatically after a short operatinal period. Short-term dry running will not damage the pump. If it becomes necessary to vent the pump, please observe the following procedure:

  • Switch off pump,
    • Risk of burning if the pump is touched!
    • Depending on the operating condition of the pump and/or installation (fluid temperature) the pump/motor can become very hot.
    • Close the valve on the discharge side.
  • Risk of scalding!
    • Depending on the fluid temperature and the system pressure, if the vent screw is completely loosened hot liquid or vapour can escape or even shoot out at high pressure.
    • Carefully loosen and fully remove the vent plug with a suitable screwdriver (Fig. 9).WILO Star RS Gas Boiler Circulation Pump-11
    • Carefully push pump shaft back several times with a screwdriver.
  • Protect all electrical parts against the leaking water.
  • Switch-on pump.
    • It is possible that the pump blocks with the vent plug open, depending on the system pressure.
  • After 15…30 s tighten the vent plug.
  • Re-open isolating valve,

Speed setting
If the rooms cannot be sufficiently heated, the speed of the pump may be too low. In this case you will need to switch to a higher speed. If, on the other hand, the pump is set at too high a speed, flow noise may occur in the lines and in particular at throttled thermostatic valves. This can be rectified by switching to a lower speed. The speed is changed by means of a rotary button at the terminal box. 3 represents the lowest and 1 the highest speed.

Maintenance
Prior maintenance or repair work switch off the pump and secure against unauthorized switching.

Problems, Causes and Remedies

Motor is switched on but fails to run:

  • Check electrical fuses,
  • Check voltage of pump (observe rating plate data),
  • Check capacitor size (observe rating plate data!).
  • Motor is blocked, e.g. by deposits from the heating water.
  • Remedies: Fully remove vent plug, check and if necessary rectify free running of pump rotor by turning the slotted end of the shaft with a screwdriver (Fig. 9).

Noisy pump operation

  • Cavitation due to insufficient inlet pressure.
  • Remedies: increase system pressure within the permissible range.
  • Check speed setting, if necessary switch to a lower speed

If the fault cannot be rectified, contact your nearest WILO Customer Service.

Spare parts
All rating plate data must be stated when ordering spare parts.

GB EC – Declaration of conformity

Herewith, we declare that this product: Star RSD in its delivered state complies with the following relevant provisions Electromagnetic compatibility – directive Low voltage directive and with the relevant national legislation. Applied harmonized standards, in particular: EN 61000-6-1 If the above mentioned series are technically modified without our approval, this declaration shall no longer be applicable.

WILO SE
Nortkirchenstraße 100
44263 Dortmund
Germany
T +49 231 4102-0
F +49 231 4102-7363
wilo@wilo.com
www.wilo.com

  • Argentina
    WILO SALMSONArgentina S.A.
    C1270ABE Ciudad
    Autónoma de Buenos Aires
    T +54 11 43015955
    info@salmon.com.ar

  • Austria
    WILO Pumpen
    Österreich GmbH
    1230 Wien
    T +43 507 507-0
    office@wilo.at

  • Azerbaijan
    WILO Caspian LLC
    1065 Baku
    T +994 12 5962372
    info@wilo.az

  • Belarus
    WILO Bel OOO
    220035 Minsk
    T +375 17 2503393
    wilobel@wilo.by

  • Belgium
    WILO SA/NV
    1083 Ganshoren
    T +32 2 4823333
    info@wilo.be

  • Bulgaria
    WILO Bulgaria Ltd.
    1125 Sofia
    T +359 2 9701970
    info@wilo.bg

  • Canada
    WILO Canada Inc.
    Calgary, Alberta T2A 5L4
    T +1 403 2769456
    bill.lowe@wilo-na.com

  • China
    WILO China Ltd.
    101300 Beijing
    T +86 10 80493900
    wilobj@wilo.com.cn

  • Croatia
    WILO Hrvatska d.o.o.
    10090 Zagreb
    T +38 51 3430914
    wilo-hrvatska@wilo.hr

  • Czech Republic
    WILO Praha s.r.o.
    25101 Cestlice
    T +420 234 098711
    info@wilo.cz

  • Denmark
    WILO Danmark A/S
    2690 Karlslunde
    T +45 70 253312
    wilo@wilo.dk

  • Estonia
    WILO Eesti OÜ
    12618 Tallinn
    T +372 6509780
    info@wilo.ee

  • Finland
    WILO Finland OY
    02330 Espoo
    T +358 207401540
    wilo@wilo.fi

  • France
    WILO S.A.S.
    78390 Bois d’Arcy
    T +33 1 30050930
    info@wilo.fr

  • Great Britain
    WILO (U.K.) Ltd.
    DE14 2WJ BurtonUpon-Trent
    T +44 1283 523000
    sales@wilo.co.uk

  • Greece
    WILO Hellas AG
    14569 Anixi (Attika)
    T +302 10 6248300
    wilo.info@wilo.gr

  • Hungary
    WILO Magyarország Kft
    2045 Törökbálint
    (Budapest)
    T +36 23 889500
    wilo@wilo.hu

  • Ireland
    WILO Engineering Ltd.
    Limerick
    T +353 61 227566
    sales@wilo.ie

  • Italy
    WILO Italia s.r.l.
    20068 Peschiera Borromeo
    (Milano)
    T +39 25538351
    wilo.italia@wilo.it

  • Kazakhstan
    WILO Central Asia
    050002 Almaty
    T +7 727 2785961
    in.pak@wilo.kz

  • Korea
    WILO Pumps Ltd.
    621-807 Gimhae
    Gyeongnam
    T +82 55 3405800
    wilo@wilo.co.kr

  • Latvia
    WILO Baltic SIA
    1019 Riga
    T +371 67 145229
    mail@wilo.lv

  • Lebanon
    WILO SALMSON
    Lebanon
    12022030 El Metn
    T +961 4 722280
    wsl@cyberia.net.lb

  • Lithuania
    WILO Lietuva UAB
    03202 Vilnius
    T +370 5 2136495
    mail@wilo.lt

  • The Netherlands
    WILO Nederland b.v.
    1551 NA Westzaan
    T +31 88 9456 000
    info@wilo.nl

  • Norway
    WILO Norge AS
    0975 Oslo
    T +47 22 804570
    wilo@wilo.no

  • Poland
    WILO Polska Sp. z.o.o.
    05-090 Raszyn
    T +48 22 7026161
    wilo@wilo.pl

  • Portugal
    Bombas Wilo-Salmson
    Portugal Lda.
    4050-040 Porto
    T +351 22 2080350
    bombas@wilo.pt

  • Romania
    WILO Romania s.r.l.
    077040 Com. Chiajna Jud.
    Ilfov
    T +40 21 3170164
    wilo@wilo.ro

  • Russia
    WILO Rus ooo
    123592 Moscow
    T +7 495 7810690
    wilo@orc.ru

  • Saudi Arabia
    WILO ME – Riyadh
    Riyadh 11465
    T +966 1 4624430
    wshoula@wataniaind.com

  • Serbia and Montenegro
    WILO Beograd d.o.o.
    11000 Beograd
    T +381 11 2851278
    office@wilo.co.yu

  • Slovakia
    WILO Slovakia s.r.o.
    82008 Bratislava 28
    T +421 2 45520122
    wilo@wilo.sk

  • Slovenia
    WILO Adriatic d.o.o.
    1000 Ljubljana
    T +386 1 5838130
    wilo.adriatic@wilo.si

  • South Africa
    Salmson South Africa
    1610 Edenvale
    T +27 11 6082780
    errol.cornelius@
    salmson.co.za

  • Spain
    WILO Ibérica S.A.
    28806 Alcalá de Henares
    (Madrid)
    T +34 91 8797100
    wilo.iberica@wilo.es

  • Sweden
    WILO Sverige AB
    35246 Växjö
    T +46 470 727600
    wilo@wilo.se

  • Switzerland
    EMB Pumpen AG
    4310 Rheinfelden
    T +41 61 83680-20
    info@emb-pumpen.ch

  • Taiwan
    WILO-EMU Taiwan Co. Ltd.
    110 Taipeh
    T +886 227 391655
    nelson.wu@
    wiloemutaiwan.com.tw

  • Turkey
    WILO Pompa Sistemleri
    San. ve Tic. A.S¸.
    34530 Istanbul
    T +90 216 6610211
    wilo@wilo.com.tr

  • Ukraina
    WILO Ukraina t.o.w.
    01033 Kiew
    T +38 044 2011870
    wilo@wilo.ua

  • Vietnam
    Pompes Salmson Vietnam
    Ho Chi Minh-Ville Vietnam
    T +84 8 8109975
    nkm@salmson.com.vn

  • United Arab Emirates
    WILO ME – Dubai
    Dubai
    T +971 4 3453633
    info@wilo.com.sa

  • USA
    WILO-EMU USA LLC
    Thomasville,
    Georgia 31792
    T +1 229 5840097
    info@wilo-emu.com

  • USA
    WILO USA LLC
    Melrose Park, Illinois 60160
    T +1 708 3389456
    mike.easterley@
    wilo-na.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals