wilo Star-Z 15 Circulation Pump Instruction Manual
- October 27, 2023
- wilo
Table of Contents
Wilo Star-Z 15 Circulation Pump
Overview
Safety
About these instructions
- Read through these instructions completely before attempting installation. Non-observance of the safety instructions can result in risk of injury to persons and damage to pump/ unit.
- When the installation work is complete, pass on the instructions to the end user.
- Keep the instructions near the pump. They can be used as a reference if problems occur later.
- We accept no liability for damage resulting from failure to follow these instructions.
Safety information
The following safety information is very important:
- Danger: Indicates a danger to life due to electrical voltage.
- Warning: Indicates a possible danger to life or injury.
- Caution: Indicates possible risks to the pump or other items.
- NOTE : Highlights tips and information.
Qualification
The pump may only be installed by qualified personnel. The power may only be connected by aqualified electrician.
Regulations
The current version of the following regulations must be observed when installing the equipment:
- Accident prevention regulations
- DVGW worksheet W551 (in Germany)
- VDE 0370/part1
- Other local regulations (e.g. IEC, VDE, etc.)
Conversion and spares
The pump must not be technically modified or converted. Only use original spares.
Transport
- Unpack and check the pump and all accessories upon receipt. Report any damage in transit immediately.
- Despatch the pump in the original packing only.
Power supply
There is a danger of an electric shock when dealing with electricity. Therefore:
- switch off the power before working on the pump and make sure that it cannot be switched on again accidentally.
- Do not kink or nip the power cable or let it come into contact with heat sources.
- The pump has IP 42 drip-proof protection. Protect the pump against water spray. Do not immerse in water or other fluids.
Specifications
Type key
Star-Z| Series:
Standard drinking water circulation pump, glandless pump
---|---
15| Nominal width DN of the connecting pipe (mm)
A = with shut-off valves C = with shut-off valves
and ready to connect with plug clock timer
Press| with Viega crimped connection
Connections
Data
See nameplate or Wilo catalog for further information
Scope of delivery
- Pump
- Thermal insulation shell
- Sealing rings
- Installation and operating instructions (not illustrated)
Principle of operation
Application
The pump is intended for pumping drinking or processing water in a circulation system.
Functions
Timing function
The Star-Z 15 C version also has a cable connection with plug clock timer.
Valves
The Star-Z 15 C, Star-Z 15 A and Star-Z 15 APress versions are equipped with a
non-return valve (1) on the discharge side and with a stop valve (2) on the
intake side.
To replace the motor head (3, it is sufficient to close the stop valve at the
rotating slot (4). The motor head can then be simply unscrewed.
Installation
Mechanical installation
Danger: Before starting work, make sure that the pump has been disconnected from the power supply.
Installation site
Provide a weatherproof, frost-free, dust-free and well-ventilated room for the installation. Choose an installation site that is easily accessible.
Caution: Dirt can cause pump failure.
Flush the pipe system before installation.
NOTE: In the case of the Star-Z 15 C, Starz 15 A and Star-Z 15 APress versions, the stop valve and non-return valve are pre-installed. In the case of the Star-Z 15 version, these valves have to be installed.
-
Prepare the installation site so that the pump can be installed without being exposed to mechanical stresses.
-
Choose the right installation position – only as shown in (Fig. A).
-
The arrow on the back of the housing indicates the direction of flow.
-
Release the cap nut – unscrew it completely if necessary
Caution: Do not damage the housing seal.Replace damaged seals. -
Turn the motor head so that the cable screw connection points downwards.
Caution: If the position is wrong, water can penetrate and destroy the pump. -
Tighten the cap nut again.
-
Turn slot (1) with a screwdriver so that it is parallel to the direction of flow (only in the case of the Star-Z 15 C, Star-Z 15 A and Star-Z 15 APress versions).
NOTE: To close, turn the slot so that it is across the direction of flow. -
Fit the thermal insulation shell.
-
Connect the pipework.
Caution:
In the case of the versions with check valve and non-return valve, these are
already pre-assembled with a tightening torque of 15 Nm (hand-tight). If the
tightening torque is too high, this will destroy the valve screw connection
and the O-ring. When installing the valve, use a wrench to prevent it from
turning! In the case of the Star-Z 15 APress version, only use Viega pressure
clamps. Other pressure clamps would destroy the pump.
Electrical connections
Danger: Only a qualified electrician is
allowed to work on the electrical connection.Before making the connection,
make sure
that the connecting cable is dead.
- Install a permanent connecting cable with at 5–8 mm outside diameter with a plug device or all-pole switch (with at least 3 mm contact opening width).
- Open the connection box.
- Guide the connecting cable through the cable connection and strip approximately 5 mm.
- Secure the cores with the cable clips: L phase, N neutral, and earth.
- Tighten the cable connection firmly.
- Close the connection box.
Filling and ventilation
- Fill the system.
- The pump rotor space vents automatically after a short time in operation. The pump will not be damaged if it runs dry briefly.
Set the time
The timer of the Star-Z 15 C versions can be set as follows:
- Turn the time selection wheel (1) in the direction of the arrow to set the current time.
- Switch the timer on (2) and off (3) on the time selection wheel as required.
To clean
Clean the outside of the pump with a lightly moistened cloth only. Do not use detergents.
To replace the motor head
Warning: When removing the motor head or pump, hot fluid may spurt out
under high pressure. Allow the pump to cool down beforehand.
Close the stop valves before removing the pump
Replacing the motor head.
Order the service motor from the trade.
Fault
Pump does not start.
| Cause| Remedy
---|---|---
Interruption in the power supply, short- circuit or defective fuses.| Have the
power supply checked by a qualified electrician.
Timing function has switched off automati- cally (Star-Z 15 C version only).|
Check the plug clock timer setting.
Motor is blocked, e.g. through deposits from the water mains.| Have the pump
removed by a qualified person
Check that the impeller can move by turning it and rinse out the dirt that
has accumulated.
Pump makes noises.| Motor scraping, e.g. through deposits from the water mains
Running dry, too little water.| Check the shut-off valves, they must be fully
open.
NOTE:
If you cannot remedy the fault, contact the trade.
EC – Declaration of conformity
Herewith, we declare that this product: Star-Z 15 in its delivered state complies with the following relevant provisions:
Electromagnetic compatibility – directive
Low voltage directive
Applied harmonized standards, in particular:
- EN 60335-2-51,
- EN 61000-3-2,
- EN 61000-3-3,
- EN 61000-6-2,
- EN 61000-6-4.
Dortmund, 08.12.2004
Erwin Prieß
Quality Manager
Wilo – International (Subsidiaries)
France
WILO S.A.S.
78390 Bois d’Arcy
T +33 1 30050930
info@wilo.fr
Belgium
WILO SA/NV
1083 Ganshoren
T +32 2 4823333
info@wilo.be
Canada
WILO Canada Inc.
Calgary, Alberta T2A 5L4
T +1 403 2769456
bill.lowe@wilo-na.com
China
WILO China Ltd.
101300 Beijing
T +86 10 80493900
wilobj@wilo.com.cn
The Netherlands
WILO Nederland b.v.
1948 RC Beverwijk
T +31 251 220844
info@wilo.nl
Spain
WILO Ibérica S.A.
28806 Alcalá de Henares
(Madrid)
T +34 91 8797100
wilo.iberica@wilo.es
USA
WILO-EMU USA LLC
Thomasville, Georgia 31792
T +1 229 5840097
info@wilo-emu.com
USA
WILO USA LLC
Melrose Park, Illinois 60160
T +1 708 3389456
mike.easterley@wilo-na.com
United Arab Emirates
WILO ME – Dubai
Dubai
T +971 4 3453633
info@wilo.com.sa
Russia
WILO Rus ooo
123592 Moscow
T +7 495 7810690
wilo@orc.ru
Austria
WILO Handelsges. m.b.H.
1230 Wien
T +43 5 07507-0
office@wilo.at
References
- E-MU - Home
- Commercial Distributor & Supply Company | North American
- 100% WIR | Crisol Holding GmbH
- Wilo pump manufacturers in your area since 1872 | Wilo
- Wilo Corporate - Pioneering for You | WILO
- Wilo - Pumpenhersteller in Ihrer Nähe seit 1872 | Wilo
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>