Wilo-Star-Z 15 Bronze Hot Water Circulator Pump Instruction Manual

October 27, 2023
wilo

Wilo-Star-Z 15 Bronze Hot Water Circulator Pump

Safety

About these instructions

  • Read through these instructions completely before attempting installation. Non-observance of the safety instructions can result in risk of injury to persons and damage to pump/unit.
  • When the installation work is complete, pass on the instructions to the end user.
  • Keep the instructions near the pump. They can be used as a reference if problems occur later.
  • We accept no liability for damage resulting from failure to follow these instructions.

Safety information

The following safety information is very important:

Danger : Indicates a danger to life due to electrical voltage.
Warning : Indicates a possible danger to life or injury.
Caution : Indicates possible risks to the pump or other items.
NOTE : Highlights tips and information.

Qualification: The pump may only be installed by qualified personnel. The power may only be connected by aqualified electrician.

Regulations

The current version of the following regulations must be observed when installing the equipment:

  • Accident prevention regulations
  • DVGW worksheet W551 (in Germany)
  • VDE 0370/part1
  • Other local regulations (e.g. IEC, VDE, etc.)

Conversion, spares
The pump must not be technically modified or converted. Only use original spares.

Transport
Unpack and check the pump and all accessories upon receipt. Report any damage in transit immediately. Despatch the pump in the original packing only.

Power supply
There is a danger of an electric shock when dealing with electricity. Therefore:

  • switch off the power before working on the pump and make sure that it cannot be switched on again accidentally.
  • Do not kink or nip the power cable or let it come into contact with heat sources.
  • The pump has IP 42 drip-proof protection. Protect the pump against water spray. Do not immerse in water or other fluids.

Specifications

Type key

Star-Z| Series:

Standard drinking water circulation pump, glandless pump

---|---
15| Nominal width DN of the connecting pipe (mm)
A = with shut-off valves C = with shut-off valves

and ready to connect with plug clock timer

Press| with Viega crimped connection

Connections

Wilo-Star-Z 15 Bronze Hot Water Circulator Pump 1

Data

Mains voltage 1 ~ 230 V / 50 Hz
Protection class IP 42
Nominal width of connecting pipes R 1/2                               Æ 15mm
Fitting length 84 mm (type A                       166 mm

138 mm)

Maximum permissible operating pressure| 10 bar
Permitted fluid tempera- ture range| 20°C to 65°C,

in short-term operation up to 2 hours: 70°C

See nameplate or Wilo catalogue for further information.

Scope of delivery

  1. Pump
  2. Thermal insulation shell
  3. Sealing rings
  4. Installation and operating instructions (not illustrated)

Principle of operation

Application
The pump is intended for pumping drinking or process water in a circulation system.

Functions
Timing function The Star-Z 15 C version also has a cable connection with plug clock timer.

Valves
The Star-Z 15 C, Star-Z 15 A and Star-Z 15 APress versions are equipped with a non-return valve

  1. on the discharge side and with a stop valve
  2. on the intake side. To replace the motor head
  3. it is sufficient to close the stop valve at rotating slot
  4. The motor head can then be simply unscrewed.

Installation

Mechanical installation

Danger : Before starting work, make sure that the pump has been disconnected from the power supply.

Installation site: Provide a weatherproof, frost-free, dust-free and well-ventilated room for the installation. Choose an installation site that is easily accessible.

Caution : Dirt can cause pump failure. Flush the pipe system before installation.

NOTE : In the case of the Star-Z 15 C, Star- Z 15 A and Star-Z 15 APress versions, the stop valve and non-return valve are pre-installed. In the case of the Star-Z 15 version, these valves have to be installed.

  1. Prepare the installation site so that the pump can be installed without being exposed to mechanical stresses.

  2. Choose the right installation position – only as shown in (Fig. A). The arrow on the back of the housing indicates the direction of flow.

  3. Release the cap nut – unscrew it completely if necessary.
    Caution : Do not damage the housing seal. Replace damaged seals.

  4. Turn the motor head so that the cable screw connection points downwards.
    Caution : If the position is wrong, water can penetrate and destroy the pump.

  5. Tighten the cap nut again.

  6. Turn slot (1) with a screwdriver so that it is parallel to the direction of flow (only in the case of the Star-Z 15 C, Star-Z 15 A and Star-Z 15 APress versions).Wilo-Star-Z 15 Bronze Hot Water Circulator Pump 5

  7. Fit the thermal insulation shell.

  8. Connect the pipework
    Caution : In the case of the versions with check valve and non-return valve, these are already pre-assembled with a tightening torque of 15 Nm (hand-tight). If the tightening torque is too high, this will destroy the valve screw connection and the O-ring. When installing the valve, use a wrench to prevent it from turning! In the case of the Star-Z 15 APress version, only use Viega pressure clamps. Other pressure clamps would destroy the pump.

Electrical connections

Danger : Only a qualified electrician is allowed to work on the electrical connection. Before making the connection, make sure that the connecting cable is dead

  1. Install a permanent connecting cable with at 5–8 mm outside diameter with plug device or all-pole switch (with at least 3 mm contact opening width).
  2. Open the connection box.
  3. Guide the connecting cable through the cable connection and strip approximately 5 mm.
  4. Secure the cores with the cable clips: L phase, N neutral, earth.
  5. Tighten the cable connection firmly.
  6. Close the connection box.

Filling and ventilation

  1. Fill the system.
  2. The pump rotor space vents automatically after a short time in operation.The pump will not be damaged if it runs dry briefly.

Set the time
The timer of the Star-Z 15 C versions can be set as follows:

  1. Turn the time selection wheel (1) in the direction of the arrow to set the current time.
  2. Switch the timer on (2) and off (3) on the time selection wheel as required.

To clean : Clean the outside of the pump with a lightly moistened cloth only. Do not use detergents.
To replace the motor head:

Warning : When removing the motor head or pump, hot fluid may spurt out under high pressure.Allow the pump to cool down beforehand. Close the stop valves before removing the pump.

Fault

Pump does not start.

| Cause| Remedy
---|---|---
Interruption in the power supply, short- circuit or defective fuses.| Have the power supply checked by a qualified electrician.
Timing function has switched off automatically (Star-Z 15 C version only).| Check the plug clock timer setting.
Motor is blocked, e.g. through deposits from the water mains.| Have the pump removed by a qualified person. Check that the impeller can move by turning it and rinse out the dirt that has accumulated.
Pump makes noises.| Motor scraping, e.g. through deposits from the water mains
Running dry, too little water.| Check the shut-off valves, they must be fully open.

WILO AG
Nortkirchenstraße 100
44263 Dortmund
Germany
T +49 231 4102-0
F +49 231 4102-7363
www.wilo.com

Documents / Resources

| WILO Wilo-Star-Z 15 Bronze Hot Water Circulator Pump [pdf] Instruction Manual
Wilo-Star-Z 15, Bronze Hot Water Circulator Pump, Wilo-Star-Z 15 Bronze Hot Water Circulator Pump, Hot Water Circulator Pump, Water Circulator Pump, Circulator Pump, Pump
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

wilo User Manuals

Related Manuals