Fulham FHSHB-347-40W-D HotSpot2 LED Emergency Driver Installation Guide

June 1, 2024
FULHAM

Fulham FHSHB-347-40W-D HotSpot2 LED Emergency Driver

Fulham FHSHB-347-40W-D HotSpot2 LED Emergency Driver

Feature

40W Constant Power EM Output for at least 90 minutes; 170VDC Output (compatibility test w/ drivers required*)

Quick Installation between the fixture and the ceiling with provided hanging bolt hardware and a safety cable

Convenient safety compliance testing with either an integral test button or an optional remote control (98 ft. range)

Built-in Integrated Junction Box for conveniently connecting the UFO’s LED Driver Input & Dimming Wires

Feature Suitable and rated for dry and damp locations, e.g. warehouse applications

Red finish makes fixtures with EM capability easy to see from the ground (to point the testing remote toward the correct fixtures)

Product Overview

  1. Safety Rope Interface
  2. AC Input Wires Interface
  3. Dimming Wires Interface
  4. Integrated Junction Box Cover
  5. Junction Box
  6. LED Driver Input Wires Interface
  7. Sensor Wires Interface
  8. LED Driver Dimming Wires Interface
  9. Charge Indicator & Test Switch
  10. Remote Control Antenna
    Product Overview

Overall Dimens i ons

Diameter| 5.47” (139mm)
Height| (173mm)

General Specifications

Input Voltage/ Frequency 100-347V-, 50/60Hz
Input Current 0.2 Max
Input Power 12w Max
Load Input Power 320W Max. when using 0-10V dimming; 40W Max. when 0-10V

dimming is not used.
The luminaire driver power at min . dimming needs to be less than the EM power 40W.
Please test the compatibility of the FH SH B-34 7-40W-D with the intended luminaire before installation
Output Type| Non-Class 2
Uout| 180V
Output Power| 40W
Output Voltage| 170VDC
Vaux| 12VDC 0.2A
Number of Output Channels| 1Channel
Input Surge Protection| Line – Neutral 3kV, Line & Neutral – Ground 3kV
Pro sections| Output Open Protection
Output Overload Protection
Output Short Circuit Protection
Output Temperature Protection
Emergency Mode| 90 Minutes Min
RFI/EMI| FCC Part15A
Ambient Operating Temperature Rang| 0°C To 50°C(32°F To 122°F)
Sound Rating| A
Battery Type| Lithium
Battery Voltage| 18 v
Pack Capacity| 5000mAh
Battery Rating| 90Wh
Battery Recharge Time| 24 Hours
Battery Discharge Time| Min 1.5 Hours
Remote Control Distance| 98′ (30m) Max.
Application Environment| Wet
Service Life| 50,00 hours
Warranty| 5 years

Customers Support

LogoLogo

Logowww.fulham.com

12705 S. Van Ness Avenue, Hawthorne, CA 90250
Tel: + 1 323-599-5000
Fax: + 1 323-754-9060
order@fulham.com

Logo

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

FULHAM User Manuals

Related Manuals