FULHAM VPR-22-MU-25-9TW-A LED Luminaire Retrofit Kit
Installation Warnings
-
To reduce the risk of death, personal injury, property damage from fire, electric shock, falling parts, cuts/abrasions,
and other hazards make sure to read all warnings and instructions included with and on the fixture box and all fixture labels. -
Follow these general precautions before installing, servicing, or performing routine maintenance upon this equipment.
-
Commercial installation, service, and maintenance of luminaires should be performed by a qualified licensed
electrician. -
LED Retrofit kit installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
-
To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
-
Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation.
Warnings
- Turn off electrical power at fuse or circuit breaker box before wiring fixture to the power supply.
- Turn off the power prior to performing any maintenance
- Verify that the supply voltage is correct by comparing it with the luminaire label information.
- All wiring connections should be capped with UL approved wire connectors.
Risk of fire or electric shock. The electrical rating of these products are 120-277 VAC, the installer must determine whether they have 120-277 V at the luminaire before installation.
Risk of fire or electric shock. Install this kit only in the luminaires that
have the construction features and dimensions shown in the photographs and /or
drawings.
Risk of fire or electric shock. Luminaire wiring and electrical parts may be
damaged when drilling for installation of LED retrofit kit. Check for enclosed
wiring and components.
Caution
- Avoid direct eye exposure to the light source while it is on.
- Account for small parts and properly dispose of packing material, as these may be hazardous to children.
- Risk of burn. Disconnect power and allow fixture to cool before changing bulb or handling fixture. NOTE: The green ground screw is installed in its proper location.
- Do not Relocate.
NOTE: Please use minimum 90°C rated supply conductors.
NOTE: Specifications and dimensions subject to change without notice.
NOTE: Suitable for Dry and Damp location, Type IC.
Retrofit Kit Components
- A: End Brackets…………………………..2pcs
- B: Side Brackets………………………….2pcs
- C: Retrofit KitHousing…………………..1pcs
- D: #8 x 1/2” Self-Taping Screws…….4pcs
- E: Wire Caps………………………………3pcs
- F: Retrofit Label…………………………..1pcs\
NOTE: The existing fluorescent luminaries housing shall be larger than dimensions described in below table:
General Wiring Diagram
Field-Adjustable Wattage & CCT
Part Number | Power Level | CCT Level |
---|---|---|
VPR22-MU-25-9TW-A | 18W / 22W / 25W | 3500K – 5000K |
VPR24-MU-36-9TW-A | 23W / 30W / 36W | 3500K – 5000K |
Installation
-
Prior to installation, disconnect all incoming power to the fixture. Remove existing hardware (lens/lens frame, parabolic louver, reflector/ballast covers, brackets, lamps/lamp holders). Leave supply and grounding leads. (Fig. 1)
NOTE: Follow all federal and local regulations when disposing of lamps and removed components. -
Install the end brackets to each end of the existing fixture by gently lifting the fixture and placing the end brackets between the fixture and T-grid. (Fig. 2)
-
If you are not pleased with the side gap between the fixture and T-grid, you may install the side brackets between the fixture and T-grid. There are two tabs to allow for placing the side brackets into the slots on the end brackets. (Fig. 3)
-
Secure the end brackets to the existing fixture using the provided #8 x 1/2” self-drilling screws. (Fig. 2A)
-
Place the retrofit kit housing into the slotted keyholes of the end brackets, and the slide it horizontally to the end of the slots. (Fig. 4 & 4A)
-
Hook the safety cables onto the holes positioned on the end brackets. (Fig. 5)
-
Use the provided wire caps to connect the wire leads of the retrofit kit housing to the main power leads.
(Black-Live, White-Neutral, Green-Grounding) (Fig. 5B) -
Place the provided Retrofit Label on the original luminaire housing in a readily visible location for anyone attempting to service the luminaire. (Fig. 5-A)
-
Secure the retrofit kit housing by locking the latches onto the end brackets. (Fig. 6)
Additional Accessories (Sold Separately)
Emergency Battery Back-up: FHSCP-UNV-4W-L
- 4W Constant Power Emergency Back-up
- 500lm
- 90 min.Runtime.
Wiring Diagram 1: 3500K Emergency Output
Wiring Diagram 2: 5000K Emergency Output