Ingersoll Rand TEM6A0B24H21SB Variable Speed Convertible Air Handler Instruction Manual

June 9, 2024
Ingersoll Rand

Ingersoll Rand TEM6A0B24H21SB Variable Speed Convertible Air Handler

![Ingersoll-Rand-TEM6A0B24H21SB-Variable-Speed-Convertible-Air-Handler-PRODUCT

Note: The TEM6 series air handler is designed for installation in a closet, utility room, alcove, basement, crawlspace or attic. These versatile units are applicable to air conditioning and heat pump applications. Several models are available to meet the specific requirements of the outdoor equipment. Field installed electric resistance heaters are available.

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

Outline Drawing

Ingersoll-Rand-TEM6A0B24H21SB-Variable-Speed-
Convertible-Air-Handler-FIG-1

PRODUCT DIMENSIONS

Air Handler Model| A| B| C| D| E| F| H| Flow Control| Gas Line Braze
TEM6A0B24H21SB| 46.77| 18.50| 16.50| 16.75| 4.68| 7.33| 20.09| TXV| 3/4
All dimensions are in inches

Product Specifications

MODEL TEM6A0B24H21SB
RATED VOLTS/PH/HZ 208-230/1/60
RATINGS (a) See O.D. Specifications
INDOOR COIL — Type Plate Fin
Rows — F.P.I. 4 – 14
Face Area (sq. ft.) 3.44
Tube Size (in.) 3/8
Refrigerant Control TXV
Drain Conn. Size (in.)(b) 3/4 NPT
DUCT CONNECTIONS See Outline Drawing
INDOOR FAN — Type Centrifugal
Diameter-Width (In.) 10 X 8
No. Used 1
Drive – No. Speeds Direct – 16
CFM vs. in. w.g. See Fan Performance Table
No. Motors — H.P. 1 – 1/3
Motor Speed R.P.M. Variable
Volts/Ph/Hz 208-230/1/60
F.L. Amps 2.8
--- ---
FILTER
Filter Furnished? (c) No
REFRIGERANT R-410A
Ref. Line Connections Brazed
Coupling or Conn. Size — in. Gas 3/4
Coupling or Conn. Size — in. Liq. ****

3/8

DIMENSIONS| H x W x D
Crated (In.)| 48–1/4 x 22–1/2 x 25–1/2
Uncrated| 46–3/4 x 18-1/2 x 21-1/8
WEIGHT|
Shipping (Lbs.) / Net (Lbs.)| 126/117

  • (a) These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.
  • (b) 3/4” Male Plastic Pipe (Ref: ASTM 1785–76)
  • (c) Remote filter required.

Minimum Airflow CFM

TEM6A0B24H21SB

Heater| Minimum Heater Airflow CFM
 | With Heat Pump| Without Heat Pump
BAYHTR1504BRKC, BAYHTR1504LUGB BAYHTR1505BRKC, BAYHTR1505LUGB| 660| 600
BAYHTR1508BRKC, BAYHTR1508LUGB| 780| 600
BAYHTR1510BRKC, BAYHTR1510LUGB| 780| 600
BAYHTR1517BRKA| 1050| 850
BAYHTR3510LUGC| 780| 600
BAYHTR3517LUGA| 900| 850
TEM6A0B24H21SB Airflow Performance with Auxiliary Heat


Airflow Settings

| Dip Switch Settings| ****

Nominal Airflow

| ****


See following tables for heater application:

– Pressure Drop for Electrical Heaters

–     Minimum Heating Airflow Matrix (on unit nameplates)

Switch 7| Switch 8
Low| ON| ON| 601
Med-Lo| OFF| ON| 661
Med-Hi| ON| OFF| 781
High| OFF| OFF| 973

Heater Pressure Drop Table


Airflow CFM

| Number of Racks|  | Heater Racks
---|---|---|---
1| 2| 3| 4| Heater Model| No. of Racks
Air Pressure Drop — Inches W.G.| BAYHTR1504| 1
1800| 0.02| 0.04| 0.06| 0.14| BAYHTR1505| 1
1700| 0.02| 0.04| 0.06| 0.14| BAYHTR1508| 2
1600| 0.02| 0.04| 0.06| 0.13| BAYHTR1510| 2
1500| 0.02| 0.04| 0.06| 0.12| BAYHTR1516| 3
1400| 0.02| 0.04| 0.06| 0.12| BAYHTR1517| 3
1300| 0.02| 0.04| 0.05| 0.11| BAYHTR3510| 3
1200| 0.01| 0.04| 0.05| 0.10| BAYHTR3517| 3
1100| 0.01| 0.03| 0.05| 0.09| BAYHTR3515| 3
1000| 0.01| 0.03| 0.04| 0.09| BAYHTR1522| 4
900| 0.01| 0.03| 0.04| 0.08| BAYHTR1525| 4
800| 0.01| 0.03|  |  |  |
700| 0.01| 0.02|  |  |  |
600| 0.01| 0.02|  |  |  |

Subcooling Adjustment

System Matched with:| Indoor Unit Model No.| Outdoor Model No.| Subcooling
---|---|---|---
16 SEER HP — 2 ton| TEM6A0C36H31| 4TWR6024H1000A

4TWX6024H1000A

4A6H6024H1000A

| 13 Degrees
15 SEER HP — 2 ton| TEM6A0B24H21 TEM6A0B30H21| 4TWR5024G1000A

4A6H5024G1000A

| 14 Degrees
15 SEER HP — 3 ton| TEM6A0B30H21 TEM6A0C36H31 TEM6A0C42H41| 4TWR5036G1000A

4A6H5036G1000A

| 14 Degrees
All other matches must be charged per the nameplate charging instructions

Performance and Electrical Data

Table 1. Air Flow Performance

TEM6A0B24H21SB COOLING AIRFLOW PERFORMANCE, WET COIL, NO FILTER, NO HEATER

OUTDOOR UNIT SIZE (TONS)| SPEED SETTING| AIRFLOW SETTING| DIP SWITCH SETTING| AIRFLOW POWER| EXTERNAL STATIC PRESSURE
SW1| SW2| SW3| SW4| 0.1| 0.3| 0.5| 0.7| 0.9



1.5

| LOW| 353 CFM/

ton

| ON| ON| OFF| ON| CFM

Watts

| 533

52

| 497

78

| 461

104

| 425

130

| 390

157

NORMAL| 401 CFM/

ton

| ON| ON| OFF| OFF| CFM

Watts

| 611

65

| 580

95

| 548

125

| 517

155

| 486

185

HIGH| 451 CFM/

ton

| ON| ON| ON| OFF| CFM

Watts

| 684

81

| 668

115

| 644

148

| 611

182

| 570

215



2

| LOW| 343 CFM/

ton

| OFF| ON| OFF| ON| CFM

Watts

| 687

82

| 672

115

| 648

149

| 614

182

| 571

215

NORMAL| 390 CFM/

ton

| OFF| ON| OFF| OFF| CFM

Watts

| 789

104

| 798

145

| 780

183

| 735

216

| 663

246

HIGH| 439 CFM/

ton

| OFF| ON| ON| OFF| CFM

Watts

| 884

135

| 887

177

| 882

230

| 845

274

| 751

290



2.5

| LOW| 300 CFM/

ton

| ON| OFF| OFF| ON| CFM

Watts

| 752

92

| 749

123

| 729

167

| 691

211

| 636

241

NORMAL

(a)

| 340 CFM/

ton

| OFF| OFF| OFF| OFF| CFM

Watts

| 859

128

| 861

172

| 863

211

| 830

242

| 727

268

HIGH| 383 CFM/

ton

| ON| OFF| ON| OFF| CFM

Watts

| 963

172

| 973

223

| 995

263

| 967

291

| 844

308

(a) Factory Default Setting

Table 2. Air Flow Performance

TEM6A0B24H21SB HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATER

OUTDOOR UNIT SIZE (TONS)| SPEED SETTING| AIRFLOW SETTING| DIP SWITCH SETTING| AIRFLOW POWER| EXTERNAL STATIC PRESSURE
SW1| SW2| SW3| SW4| 0.1| 0.3| 0.5| 0.7| 0.9



1.5

| LOW| 394 CFM/

ton

| ON| ON| OFF| ON| CFM

Watts

| 599

58

| 571

88

| 539

117

| 502

146

| 462

175

NORMAL| 448 CFM/

ton

| ON| ON| OFF| OFF| CFM

Watts

| 680

72

| 665

109

| 641

145

| 610

178

| 572

209

HIGH| 493 CFM/

ton

| ON| ON| ON| OFF| CFM

Watts

| 748

89

| 746

118

| 682

163

| 545

208

| 326

240



2

| LOW| 393 CFM/

ton

| OFF| ON| OFF| ON| CFM

Watts

| 785

97

| 790

128

| 773

175

| 735

223

| 674

253

NORMAL| 446 CFM/

ton

| OFF| ON| OFF| OFF| CFM

Watts

| 904

131

| 902

179

| 912

219

| 894

253

| 809

281

HIGH| 491 CFM/

ton

| OFF| ON| ON| OFF| CFM

Watts

| 980

167

| 972

216

| 990

268

| 974

308

| 863

324



2.5

| LOW| 350 CFM/

ton

| ON| OFF| OFF| ON| CFM

Watts

| 866

125

| 870

162

| 866

215

| 833

263

| 750

286

NORMAL

(a)

| 398 CFM/

ton

| ON| OFF| OFF| OFF| CFM

Watts

| 995

171

| 988

222

| 1005

271

| 986

309

| 872

325

HIGH| 437 CFM/

ton

| ON| OFF| ON| OFF| CFM

Watts

| 1099

220

| 1086

274

| 1098

328

| 1065

362

| 918

353

(a) Factory Default Setting

  1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
  2. Heater model numbers may have additional suffix digits.

Table 3. Electrical Data

TEM6A0B24H21SB HEATER DATA


Heater Model No.

| ****

No. of Circuits/ Phases

| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater|  |  |  | 2.5 | 3| 15|  |  | 2.5 | 3| 15
BAYHTR1504BRKC BAYHTR1504LUGB| 1/1| 3.84| 13100| 16.0| 23| 25| 2.88| 9800| 13.8| 20| 20
BAYHTR1505BRKC BAYHTR1505LUGB| 1/1| 4.80| 16400| 20.0| 28| 30| 3.60| 12300| 17.3| 25| 25
BAYHTR1508BRKC BAYHTR1508LUGB| 1/1| 7.68| 26200| 32.0| 43| 45| 5.76| 19700| 27.7| 38| 40
BAYHTR1510BRKC BAYHTR1510LUGB| 1/1| 9.60| 32800| 40.0| 53| 60| 7.20| 24600| 34.6| 46| 50
BAYHTR1517BRKA

Circuit 1 (a)

| ****

2/1

| 9.60| 32800| 40.0| 53| 60| 7.20| 24600| 34.6| 46| 50
BAYHTR1517BRKA

Circuit 2

| 4.80| 16400| 20.0| 25| 25| 3.60| 12300| 17.3| 22| 25
BAYHTR3510LUGC| 1/3| 9.60| 32800| 23.1| 32| 35| 7.20| 24600| 20.0| 28| 30
BAYHTR3517LUGA| 1/3| 14.40| 49100| 34.6| 46| 50| 10.80| 36900| 30.0| 40| 45

  • = Motor Amps

(a) MCA and MOP for circuit 1 contains the motor amps

Features and Benefits

  • Painted metal cabinet with captured foil face insulation
  • 2% or less air leakage
  • R-4.2 Insulating Value
  • Multi-Position UP/Down Flow, Horizontal Left /Right
  • ALL Aluminum Coil with Enhanced Patented Coil Fin
  • Electric Heaters with polarized plug connections (sold as accessory)
  • R-410A Thermal Expansion Valve
  • Variable Speed ECM Motor
  • Low Voltage Pigtail Connections
  • Draw Through Design
  • Horizontal Drain Pan
  • Single Color
  • Fused 24V Power
  • 3 year warranty
  • 10–year warranty registered
  • Optional extended warranty available

Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results.

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.We are committed to using environmentally conscious print practices.

TEM6A0B24-SUB-1C-EN 08 Jan 2018 Supersedes TEM6A0B24-SUB-1B-EN (August 2017)