Ingersoll Rand TEM6A0B24H21SB Variable Speed Convertible Air Handler
![Ingersoll-Rand-TEM6A0B24H21SB-Variable-Speed-Convertible-Air-Handler-PRODUCT
- Copy](https://manuals.plus/wp-content/uploads/2023/03/Ingersoll-Rand- TEM6A0B24H21SB-Variable-Speed-Convertible-Air-Handler-PRODUCT-Copy.png)
Note: The TEM6 series air handler is designed for installation in a closet, utility room, alcove, basement, crawlspace or attic. These versatile units are applicable to air conditioning and heat pump applications. Several models are available to meet the specific requirements of the outdoor equipment. Field installed electric resistance heaters are available.
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
Outline Drawing
PRODUCT DIMENSIONS
Air Handler Model| A| B| C| D| E| F| H| Flow Control| Gas Line Braze
TEM6A0B24H21SB| 46.77| 18.50| 16.50| 16.75| 4.68| 7.33| 20.09| TXV| 3/4
All dimensions are in inches
Product Specifications
MODEL | TEM6A0B24H21SB |
---|---|
RATED VOLTS/PH/HZ | 208-230/1/60 |
RATINGS (a) | See O.D. Specifications |
INDOOR COIL — Type | Plate Fin |
Rows — F.P.I. | 4 – 14 |
Face Area (sq. ft.) | 3.44 |
Tube Size (in.) | 3/8 |
Refrigerant Control | TXV |
Drain Conn. Size (in.)(b) | 3/4 NPT |
DUCT CONNECTIONS | See Outline Drawing |
INDOOR FAN — Type | Centrifugal |
Diameter-Width (In.) | 10 X 8 |
No. Used | 1 |
Drive – No. Speeds | Direct – 16 |
CFM vs. in. w.g. | See Fan Performance Table |
No. Motors — H.P. | 1 – 1/3 |
Motor Speed R.P.M. | Variable |
Volts/Ph/Hz | 208-230/1/60 |
F.L. Amps | 2.8 |
--- | --- |
FILTER | |
Filter Furnished? (c) | No |
REFRIGERANT | R-410A |
Ref. Line Connections | Brazed |
Coupling or Conn. Size — in. Gas | 3/4 |
Coupling or Conn. Size — in. Liq. | **** |
3/8
DIMENSIONS| H x W x D
Crated (In.)| 48–1/4 x 22–1/2 x 25–1/2
Uncrated| 46–3/4 x 18-1/2 x 21-1/8
WEIGHT|
Shipping (Lbs.) / Net (Lbs.)| 126/117
- (a) These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.
- (b) 3/4” Male Plastic Pipe (Ref: ASTM 1785–76)
- (c) Remote filter required.
Minimum Airflow CFM
TEM6A0B24H21SB
Heater| Minimum Heater Airflow CFM
| With Heat Pump| Without Heat Pump
BAYHTR1504BRKC, BAYHTR1504LUGB BAYHTR1505BRKC, BAYHTR1505LUGB| 660| 600
BAYHTR1508BRKC, BAYHTR1508LUGB| 780| 600
BAYHTR1510BRKC, BAYHTR1510LUGB| 780| 600
BAYHTR1517BRKA| 1050| 850
BAYHTR3510LUGC| 780| 600
BAYHTR3517LUGA| 900| 850
TEM6A0B24H21SB Airflow Performance with Auxiliary Heat
Airflow Settings
| Dip Switch Settings| ****
Nominal Airflow
| ****
See following tables for heater application:
– Pressure Drop for Electrical Heaters
– Minimum Heating Airflow Matrix (on unit nameplates)
Switch 7| Switch 8
Low| ON| ON| 601
Med-Lo| OFF| ON| 661
Med-Hi| ON| OFF| 781
High| OFF| OFF| 973
Heater Pressure Drop Table
Airflow CFM
| Number of Racks| | Heater Racks
---|---|---|---
1| 2| 3| 4| Heater Model| No. of Racks
Air Pressure Drop — Inches W.G.| BAYHTR1504| 1
1800| 0.02| 0.04| 0.06| 0.14| BAYHTR1505| 1
1700| 0.02| 0.04| 0.06| 0.14| BAYHTR1508| 2
1600| 0.02| 0.04| 0.06| 0.13| BAYHTR1510| 2
1500| 0.02| 0.04| 0.06| 0.12| BAYHTR1516| 3
1400| 0.02| 0.04| 0.06| 0.12| BAYHTR1517| 3
1300| 0.02| 0.04| 0.05| 0.11| BAYHTR3510| 3
1200| 0.01| 0.04| 0.05| 0.10| BAYHTR3517| 3
1100| 0.01| 0.03| 0.05| 0.09| BAYHTR3515| 3
1000| 0.01| 0.03| 0.04| 0.09| BAYHTR1522| 4
900| 0.01| 0.03| 0.04| 0.08| BAYHTR1525| 4
800| 0.01| 0.03| | | |
700| 0.01| 0.02| | | |
600| 0.01| 0.02| | | |
Subcooling Adjustment
System Matched with:| Indoor Unit Model No.| Outdoor Model No.|
Subcooling
---|---|---|---
16 SEER HP — 2 ton| TEM6A0C36H31| 4TWR6024H1000A
4TWX6024H1000A
4A6H6024H1000A
| 13 Degrees
15 SEER HP — 2 ton| TEM6A0B24H21 TEM6A0B30H21| 4TWR5024G1000A
4A6H5024G1000A
| 14 Degrees
15 SEER HP — 3 ton| TEM6A0B30H21 TEM6A0C36H31 TEM6A0C42H41| 4TWR5036G1000A
4A6H5036G1000A
| 14 Degrees
All other matches must be charged per the nameplate charging instructions
Performance and Electrical Data
Table 1. Air Flow Performance
TEM6A0B24H21SB COOLING AIRFLOW PERFORMANCE, WET COIL, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE (TONS)| SPEED SETTING| AIRFLOW SETTING| DIP SWITCH SETTING|
AIRFLOW POWER| EXTERNAL STATIC PRESSURE
SW1| SW2| SW3| SW4| 0.1| 0.3| 0.5| 0.7| 0.9
1.5
| LOW| 353 CFM/
ton
| ON| ON| OFF| ON| CFM
Watts
| 533
52
| 497
78
| 461
104
| 425
130
| 390
157
NORMAL| 401 CFM/
ton
| ON| ON| OFF| OFF| CFM
Watts
| 611
65
| 580
95
| 548
125
| 517
155
| 486
185
HIGH| 451 CFM/
ton
| ON| ON| ON| OFF| CFM
Watts
| 684
81
| 668
115
| 644
148
| 611
182
| 570
215
2
| LOW| 343 CFM/
ton
| OFF| ON| OFF| ON| CFM
Watts
| 687
82
| 672
115
| 648
149
| 614
182
| 571
215
NORMAL| 390 CFM/
ton
| OFF| ON| OFF| OFF| CFM
Watts
| 789
104
| 798
145
| 780
183
| 735
216
| 663
246
HIGH| 439 CFM/
ton
| OFF| ON| ON| OFF| CFM
Watts
| 884
135
| 887
177
| 882
230
| 845
274
| 751
290
2.5
| LOW| 300 CFM/
ton
| ON| OFF| OFF| ON| CFM
Watts
| 752
92
| 749
123
| 729
167
| 691
211
| 636
241
NORMAL
(a)
| 340 CFM/
ton
| OFF| OFF| OFF| OFF| CFM
Watts
| 859
128
| 861
172
| 863
211
| 830
242
| 727
268
HIGH| 383 CFM/
ton
| ON| OFF| ON| OFF| CFM
Watts
| 963
172
| 973
223
| 995
263
| 967
291
| 844
308
(a) Factory Default Setting
Table 2. Air Flow Performance
TEM6A0B24H21SB HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE (TONS)| SPEED SETTING| AIRFLOW SETTING| DIP SWITCH SETTING|
AIRFLOW POWER| EXTERNAL STATIC PRESSURE
SW1| SW2| SW3| SW4| 0.1| 0.3| 0.5| 0.7| 0.9
1.5
| LOW| 394 CFM/
ton
| ON| ON| OFF| ON| CFM
Watts
| 599
58
| 571
88
| 539
117
| 502
146
| 462
175
NORMAL| 448 CFM/
ton
| ON| ON| OFF| OFF| CFM
Watts
| 680
72
| 665
109
| 641
145
| 610
178
| 572
209
HIGH| 493 CFM/
ton
| ON| ON| ON| OFF| CFM
Watts
| 748
89
| 746
118
| 682
163
| 545
208
| 326
240
2
| LOW| 393 CFM/
ton
| OFF| ON| OFF| ON| CFM
Watts
| 785
97
| 790
128
| 773
175
| 735
223
| 674
253
NORMAL| 446 CFM/
ton
| OFF| ON| OFF| OFF| CFM
Watts
| 904
131
| 902
179
| 912
219
| 894
253
| 809
281
HIGH| 491 CFM/
ton
| OFF| ON| ON| OFF| CFM
Watts
| 980
167
| 972
216
| 990
268
| 974
308
| 863
324
2.5
| LOW| 350 CFM/
ton
| ON| OFF| OFF| ON| CFM
Watts
| 866
125
| 870
162
| 866
215
| 833
263
| 750
286
NORMAL
(a)
| 398 CFM/
ton
| ON| OFF| OFF| OFF| CFM
Watts
| 995
171
| 988
222
| 1005
271
| 986
309
| 872
325
HIGH| 437 CFM/
ton
| ON| OFF| ON| OFF| CFM
Watts
| 1099
220
| 1086
274
| 1098
328
| 1065
362
| 918
353
(a) Factory Default Setting
- See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
- Heater model numbers may have additional suffix digits.
Table 3. Electrical Data
TEM6A0B24H21SB HEATER DATA
Heater Model No.
| ****
No. of Circuits/ Phases
| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload
Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity|
Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 2.5 | 3| 15| | | 2.5 | 3| 15
BAYHTR1504BRKC BAYHTR1504LUGB| 1/1| 3.84| 13100| 16.0| 23| 25| 2.88| 9800|
13.8| 20| 20
BAYHTR1505BRKC BAYHTR1505LUGB| 1/1| 4.80| 16400| 20.0| 28| 30| 3.60| 12300|
17.3| 25| 25
BAYHTR1508BRKC BAYHTR1508LUGB| 1/1| 7.68| 26200| 32.0| 43| 45| 5.76| 19700|
27.7| 38| 40
BAYHTR1510BRKC BAYHTR1510LUGB| 1/1| 9.60| 32800| 40.0| 53| 60| 7.20| 24600|
34.6| 46| 50
BAYHTR1517BRKA
Circuit 1 (a)
| ****
2/1
| 9.60| 32800| 40.0| 53| 60| 7.20| 24600| 34.6| 46| 50
BAYHTR1517BRKA
Circuit 2
| 4.80| 16400| 20.0| 25| 25| 3.60| 12300| 17.3| 22| 25
BAYHTR3510LUGC| 1/3| 9.60| 32800| 23.1| 32| 35| 7.20| 24600| 20.0| 28| 30
BAYHTR3517LUGA| 1/3| 14.40| 49100| 34.6| 46| 50| 10.80| 36900| 30.0| 40| 45
- = Motor Amps
(a) MCA and MOP for circuit 1 contains the motor amps
Features and Benefits
- Painted metal cabinet with captured foil face insulation
- 2% or less air leakage
- R-4.2 Insulating Value
- Multi-Position UP/Down Flow, Horizontal Left /Right
- ALL Aluminum Coil with Enhanced Patented Coil Fin
- Electric Heaters with polarized plug connections (sold as accessory)
- R-410A Thermal Expansion Valve
- Variable Speed ECM Motor
- Low Voltage Pigtail Connections
- Draw Through Design
- Horizontal Drain Pan
- Single Color
- Fused 24V Power
- 3 year warranty
- 10–year warranty registered
- Optional extended warranty available
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results.
Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.We are committed to using environmentally conscious print practices.
TEM6A0B24-SUB-1C-EN 08 Jan 2018 Supersedes TEM6A0B24-SUB-1B-EN (August 2017)