CERBERUS PYROTRONICS MS-series Manual Stations Wiring Owner’s Manual

June 9, 2024
CERBERUS PYROTRONICS

CERBERUS PYROTRONICS MS-series Manual Stations Wiring

Installation Instructions

MANUAL FIRE ALARM STATION Series MH-5 and MS-5 (Low Voltage) MAIN SWITCH

Cerberus Pyrotronics 8 Ridgedale Avenue Cedar Knolls, New Jersey 07927

Notes:

  1. On all configurations above, in-and-out wires of zone loop must be separately connected as shown. Do not wrap wire around any terminal.
  2. In some models it is necessary to remove the terminal block in order to cut the jumper and resistor for the alternate configuration.

CONTACT RATINGS – All Normally Open
All contacts are rated at 28V max by Factory Mutual

First Action Swi1ch – Model MS-518 250 VAC/VDC, 3A
First Ac1ion Swi1ch – All other models 125 VAC/VDC, .75A
Main Switch Models MS-52C, -5 12C, and -514 C 28 VAC/VDC, .12A
Main Switch Models MS-57 and -517C 125 VAC/VDC, 3A

250 VAC/VDC, 1A

Main Switch – All other models| 125 VAC/VDC. .75A
Key Switch – All models| 125 VAC/VDC, 3A

250 VAC/VDC, 1A

• Except Firs t Action Switch Model MS-5 18 . where contacts are Normally Closed| .

Except First Action Switch Model MS-518, where contacts are Normally Closed.

MOUNTING DATA

Mounting Instructions

  1. Place the bottom of the box between 4/2 and 6 feet above the floor.
  2. Distribute the manual fire alarm boxes throughout the protected area so that they are unobstructed, readily accessible, and located in the normal exit path from the area. (See NFPA 101 or local codes.)
  3. Provide additional boxes on each floor to obtain a maxi- mum horizontal travel distance of 200 feet to the nearest box. (See NFPA 101 or local codes.)

firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CERBERUS PYROTRONICS User Manuals

Related Manuals