SM136V CoreLine Surface Mounted
|
---|---
| Power (W)| Lumen
output (lm)| Efficacy
(lm/(W)| CCT
(K)| | Class
VII|
---|---|---|---|---|---|---|---
5M136V 405/830 WIA W20L120 OC| 31W| 4000| 129| 3000| 19| II| 4.
5M136V 405/830 WIA W20L150 OC| II| 4.0
5M136V 405/830 WIA W20L120 OC W3| ii| 4.
5M136V 43S/840 WIA W20L120 OC| 4300| 139| 4000| II| 4.
5M136V 435/840 WIA W20L150 OC| II| 4.0
5M136V 43S/840 WIA W20L120 OC W3| II| 4.
• Default setting
unit: mm
| SM136V W20L120| SM136V W20L150
A| 59| 59
B| 1200| 1430
C| 200| 200
D| 69| 69
E| 107| 130
F| 110| 110
G| 110| 110
Inrush current
Electrical characteristics
Imax (A)| 5.
Tref (us)| 56
MCB| No. of luminaires max.
B-10 A| 15
B-13 A| 19
B-16 A| 24
B-20 A| 30
B-25 A| 37
C-10 A| 25
C-13 A| 32
C-16 A| 41
C-20 A| 50
C-25 A| 62
ATTENTION OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES
-
The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.
-
The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced.
-
During installation or maintaining the luminaire please use gloves to avoid spots on the cover.
• To remove dirt and spots use the following:
• Dust: use microfiber cloths only. -
Fingerprints, etc.: use a cleaner for synthetic materials with antistatic properties.
-
Luminaires are not suitable for covering with thermally insulating material
-
The luminaire must not be used or stored in a corrosive environment where hazardous materials such as Sulphur, Chlorine, Phthalates, etc, are present. – Only to be installed outside arm’s reach.
-
If the external flexible cable or cord of this luminaire is damaged, it shall be exclusively replaced by the manufacturer or his service agent or a similarly qualified person in order to avoid a hazard.
This product contains a light source of energy efficiency class≺D≻
Storage, installation, use, operation, and maintenance of the products need to
be performed exactly according to the instructions in this manual and/or other
instructions as may be provided by us to guarantee safe use of the product
over its entire lifetime. Failure to adhere to these instructions will
invalidate your entitlement to a warranty. Bolts with an indication of torque
strength on the drawing need to be tightened using a calibrated torque wrench.
Pre-assembled bolts need to be retightened again to the required torque
specification to assure maximum strength over a lifetime.
SR compatibility – For SR-based luminaires, only SR-Certified
components/sensors are to be used (see also:
http://www.lighting.philips.co.uk/oem-emea/products/driving-connected-
lighting). The functional compatibility of two (SR-certified)
components/sensors to be used in combination, as well as the override
possibility of any line-switch function used in an SR-based luminaire, is to
be released by the master component/sensor supplier. If using a NEMA 7-pin
socket on an SR-based luminaire, a full system verification is required. Not
following this advice can/will cause a risk of damage and non-compliance for
which Signify cannot take any responsibility.
Please inform yourself about the local waste disposal, separation, and
collection system for electrical and electronic products and packaging. Please
act according to your local rules and do not dispose of your old product and
packaging with your normal household waste. The correct disposal of the
packaging, your product, and/or batteries will help prevent potential negative
consequences for the environment and human health. Batteries should be
disposed of separately from the municipal waste stream via designated
collection facilities. When disposing of a product that contains non-user-
replaceable batteries, the non-user replaceable batteries shall be removed by
a professional.
Disconnect before servicing
Luminaire has basic insulation between Low Voltage supply and control
conductors
The control gear and/or the external flexible cable contained in this
luminaire shall only be replaced by the manufacturer or his service agent or a
similarly qualified person. The light source contained in this luminaire is
not replaceable, in case of damage replace the luminaire. © 2021 Signify
Holding.
All rights reserved. This document contains information relating to the
product portfolio of Signify which information may be subject to change. No
representation or warranty as to the accuracy or completeness of the
information included herein is given and any liability for any action in
reliance thereon is disclaimed. The information presented in this document is
not intended as any commercial offer and does not form part of any quotation
or contract. Philips and the Philips Shield Emblem have registered trademarks
of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding
or their respective owners.
Signify Holding.
The Netherlands
2021-07-12a
Version July 2021
© 2021 Signify Holding. All rights reserved
Data subject to change without notice
Keep for future reference:
www.lighting.philips.com
References
- Identity Digital | Create authentic digital identities with the world's largest and most relevant domain extension portfolio.
- Welcome | Philips lighting
- Driving connected lighting | Philips lighting
- Sustainable LED lighting solutions | Philips lighting
- Sustainable LED lighting solutions | Philips lighting
- Driving connected lighting | Philips lighting
- Products
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>