SENVA AQ2D-BC2AAKD Total Sense Series Duct Air Quality Sensor Instruction Manual
- June 1, 2024
- SENVA
Table of Contents
SENVA AQ2D-BC2AAKD Total Sense Series Duct Air Quality Sensor
Duct Air Quality Sensor
Build a complete air quality system for indoor, duct, and outdoor Six environmental sensors: PMx, VOC, CO2, RH, T, barometric pressure BACnet/Modbus or analog outputs with set-point relay
DESCRIPTION
The Total Sense Series Duct AQ sensor provides more data for more advanced ventilation control while drastically reducing installation cost and time on a project. It includes a comprehensive selection of AQ sensing with carbon dioxide (CO2), relative humidity (RH), and temperature plus options for total volatile organic compounds (TVOC), barometric pressure and particulate matter (PM).
APPLICATIONS
- Measure duct air quality to validate filtration systems and deliver fresh air
- Verify effectiveness of IAQ strategies in post covid environment
- Energy management/building control
- Facilitates compliance with ASHRAE 62.1 standard for air quality
- Contributes toward satisfying Feature A08 and T06 under the WELL Building Standard®
Fully configurable display
Built for building automation.
Choose up to 6 air quality indicators
- Industry leading accuracy.
- NDIR CO2 element,+3‰
- +2‰ relative humidity ppm,
Replaceable CO2, RH, and temp sensors
Build a full validation system
RESET monitors are tested and certified for your RESET Air Projects
FEATURES
- NEW! Configuration App with Senva Sync
- Reduce installation costs with multiple sensors in a rugged, easy-mount duct enclosure
- Specify the exact product for your application and made in USA
- Sense unhealthy particulates or TVOC’s in your duct system
- Industry-leading temperature and barometric pressure compensated CO2 sensing with non-dispersive infrared sensing element (NDIR), 15+ year life expectancy on CO2 sensing element; ±30ppm, ±3% of reading
- Tamper-proof
- Field-replaceable RH, Temp, and CO2 sensors ease maintenance
- 7-year limited warranty / 3 years on CO2 sensor – 2 years on all others
ORDERING
- CO sensor only availab le with display for calibration purposes.
- Choose Transmitter option for OLED temperature display and temperature readings over BACnet/Modbus.
The rmistor versions not available to display on OLED or to read over BACnet/Modbus.
Example
(Total Sense Duct mount sensor with BAC ne Mod bus RS-485, Temp, CO2, 2% RH, voe, PM, 1 OK Type 3 Temperature, OLEO Display)
DIMENSIONS
Warning : The datasheet is designed for reference only. Refer to installation instructions that accompany the product and heed all safety instructions. Product improvement is a continuing process at Senva. Changes may occur to products without prior notice.
SPECIFICATIONS
Power Supply| Without Display| 16-30VDC/24VAC(1), 3.5W nominal,
4W max.
---|---|---
analog Outputs (Analog version only)| Quantity| up to .3 outputs
Source| CO2, RH%, Temp, PM, TVOC (selectable)
Scale| 0-5V, 0-10y, 4-20mA (switch selectable, programmable per output)
protocol Output (Communications version only)| Protocol| BACnet MS/TP or
Modbus RTU
Connection| 3-wire RS-485, with isolated ground
Data Rate| 9600, 19200, 38400, 57600, 76800, 115200 (switch selectable)
Address Range| 0-127
Relay Set-point (standard except for PM models)| Type| Solid-state output, 1A
@ 30VAC/DC, N.O.
Source| CO2 setpoint, RH setpoint, Temp setpoint, TVOC setpoint, air quality,
off (selectable)
Polarity| NO/NC (selectable)
‘,–.02 (optional)| Type| Non-dispersive Infrared (NDIR)
Accuracy| ±(30ppm + 3% of reading) (400-2000ppm), -10-50°C, 0-85%RH
| ±(50ppm+ 5% of reading) (2000-S000ppm), -10-50°C, 0-85%RH
±(50ppm+3% of reading) (2000-5000ppm), @ -10-50C (Dual Channel) ±(100ppm+10%
of reading) (5000-10000ppm), @ 0-50C
Resolution| 1 ppm
Range| 0-2000 PPM (Default) (Programmable up to 10,000 PPM)
Response time| 90 seconds to 90% reading
Sample rate| 1s
Temp and Pressure| Compensated. Barometric pressure also readable over
communications
Relative Humidity (optional)| Type| Digital CMOS
---|---|---
Accuracy(2)| ±2% over 0 to 80%RH range
Resolution| 0.05%RH
Response time (3)| 30s
Sample rate| 3s
Operating range| 0 to 100%RH (non-condensing)
Operating conditions (4)| 41 to 140oF (5 to 60° C) @ 20% to 80%RH
Temperature Transmitter (optional)| Type| Silicon Band-gap
Nominal Accuracy| ±0.3° C (operating range)
Maximum Accuracy (2)| ±0.5° C (at 25° C), ±1.0° C
Resolution| 0.01° C
Response time| 30s
Sample rate| 3s
TVOC (optional)| Type| MOS
Gas| Total VOC
Range| 0-10,000 μg/m3
Response Time| <10s
Temp, Pressure| Compensated
Output| 0-2000 μg/m3 (default) Programmable up to 10,000 μg/m3
PMx (optional) CLASS 1 LASER PRODUCT| Type| Optical
Size Range| PM1.0, PM2.5, PM4.0, PM10.0
Scale| 0-1000 μg/m3
Lower detection limit| 0.3 μm
Precision| ±10 μg/m3 (0-100μg/m3); ±10% (100-1000 μg/m3)
Operating Environment| Temperature| -4 to 122oF (-20 to 50oC)
Humidity| 0-95% non-condensing
Enclosure| Material| ABS Plastic
Dimensions| 4.0”h x 4.4”w x 2.1”d (AQD: +6.8” probe)
Compliance| Agency| CE, RoHS
- One side of transformer, secondary is connected to signal common. Dedicated transformer is recommended.
- Models with PM sensor included achieve ±5% accuracy over 0 to 80%RH range and an additional temperature shift of up +0.5° C
- Time for reaching 63% of reading at 25° C and 1 m/s airflow
- Long term exposures to conditions outside normal range at high humidity may temporarily offset the RH reading (+3%RH after 60 hours.)
- Product improvement is a continual process at Senva and product features and specification may change without prior notice. Refer to instructions that accompany the product for installation and wiring.