SENVA CT1W Select Series Room CO2 Transmitters
Product Information
The CT1W Select Series Room CO2 & CO2/T Transmitters from Senva are devices designed to measure CO2 levels in a room or enclosed space. The device uses a non-dispersive infrared (NDIR) sensor to detect the concentration of CO2 in the air. The device comes with a relay output and supports 0-5V, 0-10V, or 4-20mA analog outputs.
Product Specifications
- Power Supply: 24VAC (1) 100mA max / 12-30VDC, 50mA max
- Outputs: CO2 and Temperature (option), Relay, 3-wire 4-20mA, 0-5V or 0-10V (2) (selectable)
- Solid state, 1A@30VAC/DC, N.O.
- Output scaling: CO2 – 0-2000ppm (default), 0-5000ppm or 10,000ppm (selectable)
- Accuracy (Standard): CO2 Sensor Performance
- Accuracy (Dual Channel): Drift with ABC disabled (Standard) – 35ppm/month (3)
- Drift with ABC disabled (Dual Channel): Range – 5ppm/month (3)
- Response time: 60s to 90% of reading
- Output update rate: 1s
- Operating Environment(4)
Important Warnings
Senva products are not designed for life or safety applications. Senva products are not intended for use in critical applications such as nuclear facilities, human implantable device or life support. Senva is not liable, in whole or in part, for any claims or damages arising from such uses.
Product Usage Instructions
Installation
- Locate the sensor in an area away from ventilation sources and heat-generating equipment and appliances. The sensor should be mounted at light switch height in a vertical orientation. Use insulating material behind the sensor to ensure reading accuracy.
- Do not install the sensor in multi-gang electrical boxes with line voltage or other electrical devices.
- For best results, install the sensor in a good location as shown in the manual.
- Wire the sensor as shown in the manual.
- Set DIP switch positions on (the front of the device) to accommodate your application. DIP switch 2 only applies to units with transmitter temperature output selected.
- Apply power to the sensor.
Operation
Press the center MENU button to cycle between the following options:
- SCL Scaling 2 = 2000ppm, 5 = 5000ppm, 10 = 10000ppm
- SPH Setpoint, Hi (Closed above this level)
- SPL Setpoint, Lo (Open below this level)
- ADJ Manual calibration adjustment +/-250ppm
- CAL *Automatic calibration – ON/OFF
The upper arrow and lower arrow will show the current setting and then adjusted values on consecutive presses. For No Display, the output is set to 0-2000ppm and ABC is ON. For continuously occupied areas or greenhouses, it is recommended to turn automatic calibration to ‘off’. CT1R-XXX-D (Dual Channel CO2) products will have calibration ‘off’ by default.
INSTALLATION INSTRUCTIONS
IMPORTANT WARNINGS
- Only qualified trade installers should install this product
- This product is not intended for life-safety applications
- Do not install in hazardous or classified locations
- The installer is responsible for all applicable codes
- De-energize power supply prior to installation or service
PRODUCT APPLICATION LIMITATION
Senva products are not designed for life or safety applications. Senva products are not intended for use in critical applications such as nuclear facilities, human implantable device or life support. Senva is not liable, in whole or in part, for any claims or damages arising from such uses.
INSTALLATION
- IMPORTANT! Locate the sensor in an area away from ventilation sources and heat-generating equipment and appliances. The sensor should be mounted at light switch height in a vertical orientation. Use insulating material behind the sensor to ensure reading accuracy.
NOTE: Do not install sensors in multi-gang electrical boxes with line voltage or other electrical devices.
- Wire sensor as shown above.
- Set DIP switch positions on (the front of the device) to accommodate your application. DIP switch 2 only applies to units with transmitter temperature output selected.
- Apply power to the sensor.
OPERATION
Press the center MENU button to cycle between:
- SCL Scaling “2” = 2000ppm, “5” = 5000ppm, “10” = 10000ppm
- SPH Setpoint, Hi (Closed above this level)
- SPL Setpoint, Lo (Open below this level)
- ADJ Manual calibration adjustment +/-250ppm
- CAL *Automatic calibration – ON/OFF
The upper arrow and lower arrow will show the current setting and then adjusted values on consecutive presses.
- For No Display, the output is set to 0-2000ppm and ABC is ON
- For continuously occupied areas or greenhouses, it is recommended to turn automatic calibration to ‘off’.
- CT1R-XXX-D (Dual Channel CO2) products will have calibration ‘off’ by default.
DIMENSIONS
SPECIFICATIONS
Power supply | AC Supply/DC Supply | 24VAC (1) 100mA max / 12-30VDC, 50mA max |
---|---|---|
Outputs | CO2 and Temperature (option) | 3-wire 4-20mA, 0-5V, or 0-10V (2) |
(selectable)
Relay| Solid state, 1A@30VAC/DC, N.O.
Output scaling| CO2| 0-2000ppm (default), 0-5000ppm or 10,000ppm (selectable)
CO2 Sensor Performance
| Type| Non-dispersive Infrared (NDIR)
Accuracy (Standard)
| ±(30ppm +3% of reading) (400-2000ppm), @-10-50°C
±(50ppm +5% of reading) (2000-5000ppm), @-10-50°C
±(100ppm+10% of reading) (5000-10000ppm), @ 0-50C
Accuracy (Dual Channel)
| ±(30ppm+3% of reading) (0-2000ppm), @ 0-50C
±(50ppm+3% of reading) (2000-5000ppm), @ -10-50C
±(100ppm+10% of reading) (5000-10000ppm), @ 0-50C
Drift with ABC disabled (Standard)| 35ppm/month (3)
Drift with ABC disabled (Dual Channel)| 5ppm/month (3)
Range| 0-2000/5000ppm; Programmable up to 10,000ppm
Response time| The 60s to 90% reading
Output update rate| 1s
| Element Operating Environment(4)| 14 to 122ºF (-10 to 50ºC), 0 to 95% RH
| Accuracy| <±0.2oC
| Resolution| 0.01oC
Temperature Transmitter| Repeatability| 0.04oC
Response time| 2s
| Output update rate| 0.5s
| Element Operating range| -40 to 140oF (-40 to 60oC)
Environmental| Enclosure Rating| IP20/NEMA 1
Max Operating Temp| 14 to 122oF (-10 to 50oC)
Compliance| Agency| CE, RoHS
- One side of the transformer secondary is connected to the signal common. A dedicated transformer is recommended.
- 15-30VDC/24VAC power supply voltage required for 10 Volt output.
- It is not recommended to de-activate ABC (auto-calibration) except for continuously occupied spaces or greenhouses. Drift ratings may vary based on the environment.
- Operation outside of the element operating environment may result in reduced accuracy.
CALIBRATION
Automatic Calibration feature
The sensor will automatically track low ambient CO2 levels and gradually make
adjustments to compensate for sensor drift due to the long-term aging of the
IR light source.
Senva CO2 sensors are factory calibrated to control test gases. No field
calibration is necessary or recommended. However, to facilitate compliance
with job requirements and commissioning procedures, provisions for field
calibration are provided:
- Locate calibration instruments and sensors in close proximity to each other in a controlled environment free of drafts, people, and equipment to reduce the influence on CO2 and temperature.
- Compare the output of the sensor to the calibration instrument, and note the difference. (In 0-10V mode/2000ppm range, 1V =200ppm)
- Using the buttons on the front of the unit, adjust the offset value for CO2 as needed. Factory calibration may be restored by setting the offset back to 0.
In extreme cases where the sensor module has been damaged, a new module may be installed in the field. Consult the factory for replacement modules and instructions.
TROUBLESHOOTING
Symptom| Solution
No output| Check wiring. Ensure the power supply meets requirements.
CO2
reading error
| Verify control panel software is configured for correct output scaling.
Verify the accuracy of the test instrument. Observe installation and
calibration guidelines
Install the insulation foam gasket provided to prevent thermal conduction from
the inside wall.
Perform calibration only if necessary.