SENVA P6-4000-1LX Universal Pressure Sensor Instruction Manual

June 10, 2024
SENVA

SENVA-logo

SENVA P6-4000-1LX Universal Pressure Sensor

Product Information

The P6 Universal Pressure Sensor is a highly efficient device that provides accurate and reliable pressure measurements. It comes with four selectable ranges (0-5/15/40 W.C.) and features a pressure sensor, wiring terminal block, and pressure barbs. The sensor has a display and configuration switches to adjust the device settings. It also has an output selection switch to choose the appropriate analog output (4-20mA 2-Wire or 3-Wire configurations or 5V/10V).
The sensor is not designed for use as the sole device for life or safety applications. It is not recommended to be used in critical applications such as nuclear facilities, human implantable devices, or life support as a systems approach to safety is necessary for these types of applications.

Product Usage Instructions

  1. Duct Installation:
    • Remove added duct probe from the bag.
    • Screw the Duct probe into the back of the enclosure.
    • Connect tubing from high (+) pressure port to duct probe.
    • Drill a 1/4 hole in the duct. Install the sensor using the gasket and screws provided.
  2. General Installation:
    • Screw mount sensor directly to duct or panel using self-tapping screws.
    • Move the output selection switch to select the appropriate analog output (4-20mA 2-Wire or 3-Wire configurations or 5V/10V).
  3. Move the rotary range selection dial to the desired pressure range position.
  4. Use the configuration switches to adjust the device settings.
  5. Plumb Airlines to sensor hose barbs (Accepts 1/8 & 1/4 ID tubing). High (+) and low (-) ports are labeled on the sensor.
  6. Wire sensor for voltage or current output as shown in the wiring diagrams.
  7. Recommendation: Apply power to the sensor. With no pressure applied, press the ZERO SET button for 2 seconds. (For best results, temporarily connect high and low pressure ports together while zeroing.)

DISCRIPTION

SENVA-P6-4000-1LX-Universal-Pressure-Sensor-fig-
\(1\)

  1. Zero Button
  2. Range Selection Dial
  3. Output Selection Switch
  4. Configuration Switches
  5. Display
  6. Pressure Sensor
  7. Wiring Terminal Block
  8. Pressure Barbs

PRODUCT APPLICATION LIMITATION:

Senva products are not designed to be used as the lone device for life or safety applications. Senva products are not intended for use in critical applications such as nuclear facilities, human implantable devices or life support. Senva believes a systems approach to safety is necessary for these types of applications. Senva is not liable, in whole or in part, for any claims or damages arising from such uses.

IMPORTANT WARNINGS

  • Only qualified trade installers should install this product
  • This product is not intended for life-safety applications
  • Do not install in hazardous or classified locations
  • The installer is responsible for all applicable codes
  • De-energize the power supply prior to installation or service
  • Forming a “drip-loop” (allowing the tubing to dip below the level of the sensor hose barbs) is recommended to protect the sensor from damage caused by condensation

INSTALLATION

Duct Installation:

  1. Remove added duct probe from the bag.
  2. Screw the Duct probe into the back of the enclosure.
  3. Connect tubing from high (+) pressure port to duct probe
  4. Drill a 1/4” hole in the duct. Install the sensor using the gasket and screws provided.

General Installation:

  1. Screw mount sensor directly to duct, or in the panel using self-tapping screws.
  2. Move output selection switch to select appropriate analog output (4-20mA 2 -Wire or 3-Wire configurations or 5V/10V
    Vout| Iout(mA)| _ ___**Position**
    ---|---|---
    0-5VDC| 3-Wire| Top
    0-10VDC| 3-Wire| Middle
    –| 2-Wire| Bottom
  3. Move the rotary range selection dial to the desired pressure range position
  4. Use the configuration switches to adjust the device settingsSENVA-P6-4000-1LX-Universal-Pressure-Sensor-fig- \(2\)
  5. Plumb airlines to sensor hose barbs(Accepts 1/8” & 1/4” ID tubing). High (+) and low (-) ports are labeled on the sensor.
  6. Wire sensor for voltage or current output as shown in the wiring diagrams.
  7. Recommendation: Apply power to the sensor. With no pressure applied, press the ZERO SET button for 2 seconds. (For best results, temporarily connect high and low pressure ports together while zeroing.)

WIRING DIAGRAMS

SENVA-P6-4000-1LX-Universal-Pressure-Sensor-fig-
\(3\)

TYPICAL APPLICATIONS

SENVA-P6-4000-1LX-Universal-Pressure-Sensor-fig-
\(4\)

  • Velocity: Use a pitot tube and plumb the high (+) port to total pressure (Pt) connection and low (-) port to static pressure (Ps) connection to directly read Pt-Ps = Pv. Apply the correction constant provided by the pitot tube manufacturer
  • Duct Static: Install a static pressure pickup tube approximately 2/3 of the way down the discharge air duct and plumb to a high (+) port for positively pressurized ducts.

Range Selection TableSENVA-P6-4000-1LX-Universal-Pressure-Sensor-fig-
\(6\)

LED STATUS/INDICATION

  • LED indicator will flash every 5 seconds for normal operation.
  • LED indicator will rapidly flash when applied pressure greater than 110% of selected range.
  • LED indicator will rapidly flash momentarily when zeroing process is complete

SPECIFICATIONS

Power supply

| SPEC| IFICATIONS

12-30VDC/24VAC (1), 30mA max.

---|---|---
Outputs|  | 3-wire 0-5V/10V, 4-20mA loop powered, 3-wire 4-20mA
 |

Max Range (Selectable Ranges)

| 0-5” (0.1/0.25/0.5/1/1.5/2/2.5/3/4/5”wc),

0-1250Pa (25/50/125/250/375/500/625/750/1000/1250 Pa)

0-15” (0.25/0.5/1/2.5/3/4/5/8/10/15”wc)

0-3750Pa (50/125/250/625/750/1000/1250/2000/2500/3750 Pa)

0-40” (1/2.5/5/8/10/15/20/25/30/40”wc)

0-10000Pa (250/625/1250/2000/2500/3750/5000/6250/7500/10000 Pa)

Output scaling|
Operating Temperature| Operating Range Compensated Range| -4oF to 185oF (-20oC to 85oC) 32oF to 122oF (0oC to 50oC)
Media Compatibility|  | Dry, oil-free air. Nitrogen.
Sensor Type| Precision calibrated| MEMS silicon piezoresistive
Response Time| Slow Mode| 8 Seconds
 | Fast Mode| 2 Seconds
Accuracy| Combined linearity and hysteresis| +/- 1.0% of selected range
 | Auto-zero input| Pushbutton and contact closure input
Enclosure| Material| ABS
Dimensions| 4.0”h x 3.7”w x 2.1”d

DIMENSIONS

SENVA-P6-4000-1LX-Universal-Pressure-Sensor-fig-
\(5\)

TROUBLESHOOTING

Symptom Solution
No output Check wiring. Ensure power supply meets requirements.


Pressure reading error

| Verify control panel software is configured for correct output scaling.
Verify switch settings.
Verify tubing is not pinched or leaking.
Possible contamination. Ensure sensor is used only on dry air or nitrogen.

Revised 10/21/2021 Document #152-0374-0D