SENVA AQ2 Duct and Outdoor Air Quality Sensor BACnet Instruction Manual
- June 10, 2024
- SENVA
Table of Contents
- SENVA AQ2 Duct and Outdoor Air Quality Sensor BACnet
- FEATURES
- PRODUCT IDENTIFICATION
- INSTALLATION
- SETUP – WIRING
- SETUP – ANALOG
- SETUP – COMMUNICATIONS
- SETUP – DISPLAY
- FEATURE – AIR QUALITY
- FEATURE – SETPOINT RELAY
- TVOC OPERATION
- DIMENSIONS
- CO2 CALIBRATION
- TROUBLESHOOTING
- SPECIFICATIONS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SENVA AQ2 Duct and Outdoor Air Quality Sensor BACnet
IMPORTANT WARNINGS
- Only qualified trade installers should install this product
- This product is not intended for life-safety applications
- Do not install in hazardous or classified locations
- The installer is responsible for all applicable codes
- De-energize power supply prior to installation or service
PRODUCT APPLICATION LIMITATION:
Senva products are not designed for life or safety applications. Senva
products are not intended for use in critical applications such as nuclear
facilities, human implantable device or life support. Senva is not liable, in
whole or in part, for any claims or damages arising from such uses.
FEATURES
The TotalSense series design allows customization for a sensor that meets
project requirements for monitoring temperature, carbon dioxide (CO2), total
volatile organic compound (TVOC), particulate matter (PM), relative humidity
(RH). The product can be ordered as a stand-alone CO2, RH, Temp, TVOC, PM
sensor as well as almost any combination of sensors. All models come standard
with programmable set-point relay and barometric pressure compensation for
CO2.
Choose the analog version to receive up to three selectable and programmable
analog outputs or utilize the communications version to access a myriad of
data throug Modbus RTU or BACnet MS/TP.
To verify the features see the ‘Product Identification’ section of the installation manual or use the configuration tool at senvainc.com or scan the QR code on the right.
PRODUCT IDENTIFICATION
For Outdoor product Dual channel CO2 is only available.
INSTALLATION
AQD (Duct) Installation
- Drill a 3/4” hole in duct. Install sensor using gasket and screws provided. The pickup tube will ensure adequate air flow regardless of air flow direction.
- Mount unit to duct with supplied screws. Continue to step 3 under general installation.
AQO (Outdoor) Installation
-
Select an outdoor location under an eave on north side of building away from direct sunlight and rain exposure.
-
Mount product to building with supplied screws. Continue to step 3 under general installation.
General (both) Installation -
If installing with a conduit adapter, remove and replace the factory-installed cable gland.
-
Wire analog (or RS485 for BACnet version) outputs as needed.
-
Apply power to sensor.
-
Tighten cable gland firmly around wires. If installing with a conduit adapter, seal wire entry to prevent conduit air from affecting sensor readings or operation.
-
Close lid and tighten screw. Cover must be securely installed to prevent moisture from entering enclosure.
SETUP – WIRING
The following diagrams show terminal locations for each version of the TotalSense. The number of options selected will determine which of the terminals are included on each device. For example, if only one sensor is chosen, only 1 pair of analog terminals will be present. Each device will have 4-8 terminals on the left side, 0-4 on the top, and 0-4 on the right side.
Analog Wiring
*These terminals may not be populated depending on which model is ordered.
Communications Wiring
NOTE: A 120 Ω termination resistance may be added in parallel with the RS-485 +/- by moving the very top DIP switch (DIP 1) to the left position. See “DIP Configuration” section for more information.
SETUP – ANALOG
Switch 1 with two DIP switches will be provided with every device and Switch 2 with an additional 12 DIP switches will be provided with communications devices. The following diagram shows how each setting can be configured using the provided switches.
For analog voltage output, select either 0-5V (left) or 0-10V (right) outputs. These analog ranges can be adjusted using the color OLED display. Adjustments made using the OLED display will override this DIP switch setting
SETUP – COMMUNICATIONS
Comms DIP Settings
DIP | Left | Right |
---|---|---|
1 | No Termination | Termination Resistor |
2 | Modbus | BACnet |
DIP | Function | DOWN |
--- | --- | --- |
1 | MAC6 | 0 (off) |
2 | MAC5 | 0 |
3 | MAC4 | 0 |
4 | MAC3 | 0 |
5 | MAC2 | 0 |
6 | MAC1 | 0 |
7 | MAC0 | 0 |
8 | BAUD2 | 0 |
9 | BAUD1 | 0 |
10 | BAUD0 | 0 |
11 | D/P/S1 | 0 |
12 | D/P/S0 | 0 |
DIP | Function | |
--- | --- | |
1-7 | MAC Address/ Modbus Address 0-127 (binary) | |
8-10 | Baud Rate |
0(000)=9600
1(001)=19200
2(010)=38400
3(011)=57600
4(100)=76800
5(101)=115200
11-12| Data/Parity/Stp
0(00)=8N1
1(01)=8N2
2(10)=8O1
3(11)=8E1
DIP switches 1-7 can be arranged in 127 binary configurations to set the MAC address (BACnet) or the Modbus address. Similarly, the baud rate can be set by DIP switches 8-10 and the data/parity/stop bit can be set by DIP switches 11 and 12.
ADVANCED SETUP
SETUP – DISPLAY
Example screen:
TotalSense devices ordered with color OLED display can be configured from the
display or over communications (if applicable). The default screen layout will
vary depending on which model is ordered. Each of the 5 sections can be
customized. See “Display Navigation Guide” for more information.
Screen Lock:
If the screen is locked, a lock icon will show when any button is pressed. To unlock, hold the UP and DOWN arrows for 5 seconds. To disable the lock feature, see “Display Navigation Guide”.
Changing Settings:
To change any setting, press ENTER to see the setup menu and navigate to the
desired parameter type and press ENTER again to choose. The example below
shows how to adjust the center reading on the display. The dashed blue line
shows the desired selections and the blue buttons show how to navigate
.
Changing a value:
To adjust a numerical setting, set each digit individually and press ENTER to
move the cursor from left to right. When all digits are set, the value will be
saved when ENTER is pressed again
FEATURE – AIR QUALITY
If Air Quality is selected to be displayed the device will monitor each CO2,
VOC, PM, RH, and Temp sensor present and will display accordingly.
The average air quality is calculated as follows:
- Each sensor’s current reading is rated according to the below thresholds and given an air quality index (AQI). For each sensor, a good rating is given an AQI of 90, fair is given an AQI of 60 and poor is given an AQI of 0.
- The average air quality is calculated and a total air quality rating is assigned based on the following thresholds. These thresholds can be adjusted using communications or in the “Air Quality Settings” menu from the display.
- a. Good ≥ 75
- b. 55 < Fair < 75
- c. Poor ≤ 55
GOOD (AQI 90) | FAIR (AQI 60) | POOR (AQI 0) | |
---|---|---|---|
PM2.5 | <35 ug/m3 | 35-55 ug/m3 | >55ug/m3 |
TVOC | <1000 ug/m3 | 1000-3000 ug/m3 | >3000 ug/m3 |
CO2 | <1200 PPM | 1200-2000 PPM | >2000 PPM |
Temp | 64-79oF | <64oF, >79oF | |
RH | 30-60% | <30%, >60% | <10%, >90% |
FEATURE – SETPOINT RELAY
All TotalSense Duct and Outdoor models come standard with a setpoint relay.
The relay source determines which reading or status will activate the relay.
This can be set or adjusted using the display or communications. See ‘Display
Navigation Guide’ or the applicable protocol guide for details.
Each source selection has a range listed below. To set turn-on and turn-off
thresholds, a percentage of this range can
be entered into each corresponding parameter. On display versions, the
calculated value will show as the percentage is adjusted.
Each time a new source is selected, a default relay threshold will be set
based on which technology is chosen. These auto-set values are listed in the
table below.
Source Selection| Range| Default Turn-on Threshold| Calculated Turn-on value|
Default Turn-off Threshold| Calculated Turn-off value
---|---|---|---|---|---
CO2| 0-10,000 PPM| 8.0%| 800 PPM| 7.0%| 700 PPM
RH| 0-100% RH| 60%| 60% RH| 55%| 55% RH
Temp*| -40 – 122 oF| 74%| 80oF| 73%| 78oF
TVOC| 0-1000 μg/m3| 3.5%| 35 μg/m3| 3%| 30 μg/m3
PM| 0-32000 μg/m3| 1.25%| 400 μg/m3| 1.09%| 348.8 μg/m3
*To calculate threshold % for a given temperature, use the following equation:
% Threshold = (T+40)/162*100 Where T is the temperature in oF
TVOC OPERATION
Training Mode
The TVOC sensor has artificial intelligence (AI) that allows it to sense and
understand different environments. This AI will take 48 hours to acclimate to
an environment once installed. The 48 hours will happen after every device
reboot.
During this time, the sensor will go into “training mode” and will continue to
display and output a TVOC value. The staus of the TVOC can be found in the
device settings menu.
Manual Calibration
No manual field calibration is necessary. To maintain accuracy, the TVOC
sensor will be required to be exposed to fresh air at least once every 2 days.
This can be accomplished by increasing airflow in an area or by opening a
window.
Scaling:
Senva’s TVOC sensor uses an Ethanol reading to determine a raw TVOC value.
Additionally, conversion from ppb to µg/m3 uses the molecular weight of
Ethanol. To make conversion based on a different gas baseline, user may enter
a scaling factor in TVOC Settings on the display or using communications.
DIMENSIONS
AQ2D Dimensions
AQ2O Dimensions
CO2 CALIBRATION
Automatic Calibration feature:
The CO2 sensor will automatically baseline CO2 levels and gradually make
adjustments to compensate for sensor drift due to long-term aging of the IR
light source. In applications where CO2 levels are continuously elevated, or
spaces are occupied day and night, it is recommended to use our dual channel
CO2 sensor with automatic calibration disabled.
Senva CO2 sensors are factory calibrated to controlled test gases. No field
calibration is necessary or recommended. However, to facilitate compliance
with job requirements and commissioning procedures, provisions for field
calibration are provided:
- Locate calibration instrument and sensor in close proximity to each other in a controlled environment free of drafts, people, and equipment to reduce influence on CO2 and temperature.
- Compare output of sensor to calibration instrument, and note difference. (In 0-10V mode/2000ppm range, 1V =200ppm)
- Refer to the “Setup-Display” section to adjust offset value for CO2 as needed. Factory calibration may be restored by setting offset back to 0.
In extreme cases where the sensor module has been damaged, a new module may be installed in the field. Consult factory for replacement module and instructions.
TROUBLESHOOTING
Symptom | Solution |
---|
Alarm Icon on home screen
| The device has experienced an error with one of the sensors. Navigate to “Advanced Settings” > “Diagnostics” screen to view more information.
All zeros will be displayed if no error is
present. See “Display Navigation Guide”, or the applicable communications guide or consult factory for troubleshooting help or replacement element.
No output| Check wiring. Ensure power supply meets requirements.
Reading error
| Verify control panel software is configured for correct output scaling.
Verify accuracy of test instrument. Observe installation and calibration
guidelines.
Verify unit is located away from sources of hot/ cold.
Verify sensing element is inserted properly.
Perform calibration only if necessary.
SENVA TECHNICAL SUPPORT
Need further assistance? Call our toll-free number for live technical support: 866-660-8864 or feel free to email us at support@senvainc.com
SPECIFICATIONS
SPECIFICATIONS
Power Supply| All Models| 16-30VDC/24VAC(1), 3.5W nominal, 4W max.
Analog Outputs (Analog version only)| Quantity| Up to 3 outputs
Source| CO2, RH%, Temp, PM, TVOC (selectable)
Scale| 0-5V, 0-10V, 4-20mA (switch selectable, programmable per output)
Protocol Output (Communications version only)| Protocol| BACnet MS/TP or
Modbus RTU
Connection| 3-wire RS-485, with isolated ground
Data Rate| 9600, 19200, 38400, 57600, 76800, 115200 (switch selectable)
Address Range| 0-127
| Type| Solid-state output, 1A @ 30VAC/DC, N.O.
Relay Set-point| Source| CO2 setpoint, RH setpoint, Temp setpoint, TVOC
setpoint, air quality, off (selectable)
| Polarity| NO/NC (selectable)
| Type| Non-dispersive Infrared (NDIR)
|
Accuracy (Standard)
| ±(30ppm + 3% of reading) (400-2000ppm), -10-50ºC, 0-85%RH
±(50ppm+ 5% of reading) (2000-5000ppm), -10-50ºC, 0-85%RH
5000ppm consult factory
|
Accuracy (Dual)
| ±(30ppm+3% of reading) (0-2000ppm), @ 0-50C
±(50ppm+3% of reading) (2000-5000ppm), @ -10-50C
±(100ppm+10% of reading) (5000-10000ppm), @ 0-50C
CO2 (optional)| Drift with ABC disabled
(Standard)
| 35ppm/month
Drift with ABC disabled (Dual
Channel)
| 5ppm/month
| Resolution| 1 ppm
| Range| 0-2000 PPM (Default) (Programmable up to 10,000 PPM)
| Response time| 90 seconds to 90% reading
| Sample rate| 1s
| Temp and Pressure| Compensated. Barometric pressure also readable over
communications
| Type| Digital CMOS
| Accuracy(2)| ±2% over 0 to 80%RH range
Relative Humidity (optional)| Resolution| 0.05%RH
Response time (3)| 30s
Sample rate| 3s
| Operating range| 0 to 100%RH (non-condensing)
| Operating conditions (4)| 41 to 140° F (5 to 60° C) @ 20% to 80% RH
| Type| Silicon Band-gap
±0.3° C (operating range)
±0.5° C (at 25° C), ±1.0° C
0.01° C
30s 3s
| Nominal Accuracy
Temperature Transmitter (optional)| Maximum Accuracy (2)
Resolution
| Response time
| Sample rate
| Type| MOS
| Gas| Total VOC
TVOC (optional)| Range| 0-10,000 μg/m3
| Response Time| <10s
| Output| 0-2000 μg/m3 (default) Programmable up to 10,000 μg/m3
| Type| Optical
PMx (optional)
CLASS 1 LASER PRODUCT
| Size Range| PM1.0, PM2.5, PM4.0, PM10.0
Scale| 0-1000 μg/m3
Lower detection limit| 0.3 μm
| Precision| ±10 μg/m3 (0-100μg/m3); ±10% (100-1000 μg/m3)
Operating Environment| Temperature| -4 to 122oF (-20 to 50oC)
Humidity| 0-95% non-condensing
Enclosure| Material| ABS Plastic
Dimensions| 4.0”h x 4.4”w x 2.1”d (AQD: +6.8” probe) (AQO: +2.8” solar shield)
Compliance| Agency| CE, RoHS
- One side of transformer, secondary is connected to signal common.
- Models with PM sensor included achieve ±3% accuracy over 0 to 80%RH range and an additional temperature shift of up +0.5° C
- Time for reaching 63% of reading at 25° C and 1 m/s airflow
- Long term exposures to conditions outside normal range at high humidity may temporarily offset the RH reading (+3%RH after 60 hours.)