SENVA TotalSense Series Indoor Air Quality Sensors Instruction Manual
- June 9, 2024
- SENVA
Table of Contents
- IMPORTANT WARNINGS
- FEATURES
- PRODUCT IDENTIFICATION
- INSTALLATION
- DIMENSIONS
- SETUP – WIRING
- SETUP – ANALOG
- SETUP – COMMUNICATIONS
- ADVANCED SETUP
- SETUP – DISPLAY
- FEATURE – AIR QUALITY
- FEATURE – PIR OCCUPANCY
- TVOC OPERATION
- CO2 CALIBRATION
- TROUBLESHOOTING
- SENVA TECHNICAL SUPPORT
- SPECIFICATIONS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TotalSense Series Indoor Air Quality Sensors
Instruction Manual
TotalSenseTM Series
Indoor Air Quality Sensor
BACnet/Modbus/Analog
IMPORTANT WARNINGS
- Only qualified trade installers should install this product
- This product is not intended for life-safety applications
- Do not install in hazardous or classified locations
- The installer is responsible for all applicable codes
- De-energize power supply prior to installation or service
PRODUCT APPLICATION LIMITATION:
Senva products are not designed for life or safety applications. Senva
products are not intended for use in critical applications such as nuclear
facilities, human implantable device or life support. Senva is not liable, in
whole or in part, for any claims or damages arising from such uses.
FEATURES
The TotalSense series design allows customization for a sensorthat meets
project requirements for monitoring temperaturecarbon dioxide (CO2), total
volatile organic compounds (TVOC), particulate matter (PM), relative humidity
(RH), passive-infrared occupancy sensor (PIR), and ambient light.
The product can be ordered as a stand-alone CO2, RH, Temp, TVOC, PM, or PIR
sensor as well as almost any combination ofsensors. Resistive-set-point
sliders and pushbuttons are alsoavailable to meet the requirements for any
job. All models come standard with programmable set-point relay (except onPM
models) and barometric pressure compensation for CO2.
Choose the analog version to receive up to three selectable and programmable
analog outputs or utilize the communications version to access a myriad of
data through Modbus RTU or BACnet MS/TP. Communications version comes standard
with ambient light sensing.
To verify the features see the ‘Product Identification’ section of the
installation manual or use the configuration tool at senvainc.com orscan the
QR code on the right.http://tny.sh/AQ2Web
PRODUCT IDENTIFICATION
†
Additional Setpoint sliders and offset resistors available upon request
‡ Slider and pushbutton options not available with PM sensor
INSTALLATION
-
IMPORTANT! Locate the device in an area away from ventilation sources and heat generating equipment and appliances. The device should be mounted at light switch
height in a vertical orientation. Use insulating material behind the device to ensure reading accuracy.
NOTE: Do not install the device in multi-gang electrical boxes with line voltage or other electrical devices. -
Wire according to application. See “Setup- Wiring” section for details.
-
Install backplate to wall or junction-box using screws provided. If using optional trim ring, click the TotalSense into it and secure using 1 screw. Then, mount it to wall or junction box.
-
Apply power.
-
To configure communications or analog voltage scaling, configure DIP switches according to “Setup – Analog” or “setup – Communications” sections.
To configure the device using the color OLED screen, reference the “Setup – Display” section.
DIMENSIONS
A concealment ring is provided to hide oversized cutouts or to mount using a European sized junction box.
SETUP – WIRING
The following diagrams show terminal locations for each version of the
TotalSense. The number of options selected will determine which of the
terminals are included on each device. For example, if only one sensor is
chosen, only 1 pair of analog terminals will be present. Each device will have
4-8 terminals on the left side, 0-4 on the top, and 0-4 on the right side.
Analog Wiring *These
terminals may not be populated depending on which model is ordered.
Communications Wiring
NOTE: A 120 Ω
termination resistance may be added in parallel with the RS-485 +/- by moving
the very top DIP switch (DIP 1) to the left position. See “DIP Configuration”
section for more information.
SETUP – ANALOG
Switch 1 with two DIP switches will be provided with every device and Switch 2
with an additional 12 DIP switches will be provided with communications
devices. The following diagram shows how each setting can be configured using
the provided switches.
Comms DIP Settings
For analog voltage output, select either 0-5V (left) or 0-10V (right) outputs.
These analog ranges can be adjusted using the color OLED display. Adjustments
made using the OLED display will override this DIP switch setting.
SETUP – COMMUNICATIONS
Comms DIP Settings
DIP | Left | Right |
---|---|---|
1 | N/A | Termination Resistor |
2 | Modbus | BACnet |
DIP | Function | Left | Right |
---|---|---|---|
1 | MAC6 | 0 (off) | 1 (on) |
2 | MAC5 | 0 | 1 |
3 | MAC4 | 0 | 1 |
4 | MAC3 | 0 | 1 |
5 | MAC2 | 0 | 1 |
6 | MAC1 | 0 | 1 |
7 | MAC0 | 0 | 1 |
8 | BAUD2 | 0 | 1 |
9 | BAUD1 | 0 | 1 |
10 | BAUD0 | 0 | 1 |
11 | D/P/S1 | 0 | 1 |
12 | D/P/S0 | 0 | 1 |
DIP | Function | ||
--- | --- | ||
7-Jan | MAC Address/Modbus Address 0-127 (binary) | ||
10-Aug | Baud Rate |
0(000)=9600
1(001)=19200
2(010)=38400
3(011)=57600
4(100)=76800
5(101)=115200
12-Nov| Data/Parity/Stp
0(00)=8N1
1(01)=8N2
2(10)=8O1
3(11)=8E1
DIP switches 1-7 can be arranged in 127 binary configurations to set the MAC address (BACnet) or the Modbus address. Similarly, the baud rate can be set by DIP switches 8-10 and the data/parity/stop bit can be set by DIP switches 11 and 12.
ADVANCED SETUP
| |
---|---|---
http://tny.sh/AQ2DisplayGuide| http://tny.sh/AQ2BACnet|
http://tny.sh/AQ2Modbus
SETUP – DISPLAY
Example screen:
TotalSense devices ordered with color OLED display can be configured from the
display or over communications (if applicable). The default screen layout will
vary depending on which model is ordered. Each of the 5 sections can be
customized. See “Display Navigation Guide” for more information.
Screen Lock:
If the screen is locked, a lock icon will show when any button is pressed. To
unlock, hold the UP and DOWN arrows for 5 seconds. To disable the lock
feature, see “Display Navigation Guide”.
Changing Settings:
To change any setting, press ENTER to see the setup menu and navigate to the
desired parameter type and press ENTER again to choose. The example below
shows how to adjust the center reading on the display. The dashed blue line
shows the desired selections and the blue buttons show how to navigate.
Changing a value:
To adjust a numerical setting, set each digit individually and press ENTER to
move the cursor from left to right. When all digits are set, the value will be
saved when ENTER is pressed again.
FEATURE – AIR QUALITY
If Air Quality is selected to be displayed or if the Air quality Ring option
is selected, the device will monitor each CO2, VOC, PM, RH, and Temp sensor
present and will display accordingly.
The average air quality is calculated as follows:
1.Each sensor’s current reading is rated according to the below thresholds and
given an air quality index (AQI). For each sensor, a good rating is given an
AQI of 90, fair is given an AQI of 60 and poor is given an AQI of 0.
2.The average air quality is calculated and a total air quality rating is
assigned based on the following thresholds. These thresholds can be adjusted
using communications or in the “Air Quality Settings” menu from the display.
a. Good ≥ 75
b. 55 < Fair < 75
c. Poor ≤ 55
| GOOD (AQI 90)| FAIR (AQI 60)| POOR (AQI 0)
---|---|---|---
PM2.5| <35 ug/m3| 35-55 ug/m3| >55ug/m3
TVOC| <1000 ug/m3| 1000-3000 ug/m3| >3000 ug/m3
CO2| <1200 PPM| 1200-2000 PPM| >2000 PPM
Temp| 64-79°F| <64°F, >79°F|
RH| 30-60%| <30%, >60%| <10%, >90%
FEATURE – PIR OCCUPANCY
If PIR option is selected, the PIR (Passive Infrared) sensor will trigger
anytime it detects motion. If used to activate the relay or as a
communications data point, an off-delay can be programmed using the display or
through communications.
The below shows the distance at which the sensor will trigger a motion event
based on its adjustable sensitivity rating. A motion event, for the purpose of
this graph, is considered the movement of a person or large object.
FEATURE – AIR QUALITY RING
An Air Quality (AQ) Ring may be selected in place of a display.
The AQ ring will glow green, yellow, or red according to the detected levels
of CO2, PM, VOC, RH, and Temp. See “Feature – Air Quality” section for
thresholds.
The AQ Ring may be disabled or brightness may be adjusted if the
communications model is selected. Additionally, it may be set to only display
yellow or red when air quality has degraded to fair or poor levels. See
TotalSense “BACnet/Modbus User Guide” for more information.
AQ Ring will turn on and off at a 5 second interval if a sensing error occurs.
See “Troubleshooting” section for information.
FEATURE – SETPOINT RELAY
All TotalSense models come standard with a setpoint relay except those ordered
with a PM sensor.
The relay source determines which reading or status will activate the relay.
This can be set or adjusted using the display or communications. See ‘Display
Navigation Guide’ or the applicable protocol guide for details.
Each source selection has a range listed below. To set turnon and turn-off
thresholds, a percentage of this range can be entered into each corresponding
parameter. On display versions, the calculated value will show as the
percentage is adjusted.
Each time a new source is selected, a default relay threshold will be set
based on which technology is chosen. These autoset values are listed in the
table below.
Source Selection| Range| Default Turn-on
Threshold| Calculated Turn-on
value| Default Turn-off
Threshold| Calculated Turn-off
value
---|---|---|---|---|---
CO2| 0-10,000 PPM| 8.%| 800 PPM| 7.%| 700 PPM
RH| 0-100% RH| 60%| 60% RH| 55%| 55% RH
Temp*| -40 – 122 °F| 74%| 80°F| 73%| 78°F
TVOC| 0-10000 pg/
m3| 4%| 400 pg/m3| 4.%| 350 pg/m3
To calculate threshold % for a given temperature, use the following equation:
% Threshold = (T+40)/162100
Where T is the temperature in oF
FEATURE – LID LOCKS
All TotalSense models come standard with locks to keep the lid from being
removed, to stop unwanted tampering. There is a Lock located at all 4 lid
snaps.
TVOC OPERATION
Training Mode
The TVOC sensor has artificial intelligence (AI) that allows it to sense and
understand different environments. This AI will take 48 hours to acclimate to
an environment once installed. The 48 hours will happen after every device
reboot.
During this time, the sensor will go into “training mode” and will continue to
display and output a TVOC value. the staus of the TVOC can be found in the
device settings menu.
Manual Calibration
No manual field calibration is necessary. To maintain accuracy, the TVOC
sensor will be required to be exposed to fresh air at least once every 2 days.
This can be accomplished by increasing airflow in an area or by opening a
window.
Scaling:
Senva’s TVOC sensor uses an Ethanol reading to determine a raw TVOC value.
Additionally, conversion from µg/m3 uses the molecular weight of Ethanol. To
scale based on a different gas baseline, user may enter a scaling factor in
TVOC Settings on the display or using communications.
CO2 CALIBRATION
Automatic Calibration feature:
The CO2 sensor will automatically baseline CO2 levels and gradually make
adjustments to compensate for sensor drift due to long-term aging of the IR
light source. In applications where CO2 levels are continuously elevated, or
spaces are occupied day and night, it is recommended to use our dual channel
CO2 sensor with automatic calibration disabled.
Senva CO2 sensors are factory calibrated to controlled test gases. No field
calibration is necessary or recommended. However, to facilitate compliance
with job requirements and commissioning procedures, provisions for field
calibration are provided:
- Locate calibration instrument and sensor in close proximity to each other in a controlled environment free of drafts, people, and equipment to reduce influence on CO2 and temperature.
- Compare output of sensor to calibration instrument, and note difference. (In 0-10V mode/2000ppm range, 1V =200ppm)
- Refer to the “Setup-Display” section to adjust offset value for CO2 as needed. Factory calibration may be restored by setting offset back to 0.
In extreme cases where the sensor module has been damaged, a new module may be installed in the field. Consult factory for replacement module and instructions.
TROUBLESHOOTING
Symptom | Solution |
---|
Alarm Icon on home
screen or blinking AQ
Ring| The device has experienced an error with one of the sensors. Navigate to
“Advanced Settings” > “Diagnostics” screen to view more information. All zeros
will be displayed if no error ispresent. See “Display Navigation Guide”, or
the applicable communications guide or consult factory for troubleshooting
help or replacement element.
No output| Check wiring. Ensure power supply meets requirements.
Reading
error| Verify control panel software is configured for correct output scaling.
Verify accuracy of test instrument. Observe installation and calibration
guidelines.
Verify unit is located away from sources of hot/ cold.
Verify sensing element is inserted properly.
Perform calibration only if necessary.
SENVA TECHNICAL SUPPORT
Need further assistance? Call our toll-free number for live technical support: 866-660-8864 or feel free to email us at support@senvainc.com
SPECIFICATIONS
Power Supply| Without Display
With LED Ring or Display| 16-30VDC/24VAC (1) , 3.5W nominal, 4W max.
24-30 VDC/24VAC (1) , 4.3W nominal, 5W max
---|---|---
Interface| Color OLED (optional)
Air Quality Ring| 1.5” Organic LED Display, 128×128 PX, color
Color changing (red/yellow/green) LED ring
Analog Outputs (Analog
version only)| Quantity Source Scale| Up to 3 outputs
CO2, RH%, Temp, Temp slider, TVOC (selectable)
0-5V, 0-10V, 4-20mA (switch selectable, programmable per output)
Protocol Output (Communications version
only)| Protocol Connection Data Rate
Address Range| BACnet MS/TP or Modbus RTU
3-wire RS-485, with isolated ground
9600, 19200, 38400, 57600, 76800, 115200 (switch selectable) 0-127
Relay Set-point (standard
except for PM models)| Type Source
Polarity| Solid-state output, 1A @ 30VAC/DC, N.O.
CO2 setpoint, RH setpoint, Temp setpoint, TVOC setpoint, PIR motion, air
quality, off (selectable)
NO/NC (selectable)
CO2 (optional)| Type
Accuracy
Resolution
Range
Response time Sample rate
Temp and Pressure| Non-dispersive Infrared (NDIR)
±(30ppm + 3% of reading) (400-2000ppm), -10-50ºC, 0-85%RH
±(50ppm+ 5% of reading) (2000-5000ppm), -10-50ºC, 0-85%RH
5000ppm consult factory 1 ppm
0-2000 PPM (Default) (Programmable up to 0,000 PPM)
90 seconds to 90% reading
1s Compensated. Barometric pressure also readable over communications
Relative Humidity (optional)| Type Accuracy(2) Resolution
Response time
(3)
Sample rate
Operating range Operating conditions
(4)| Digital CMOS
±2% over 0 to 80%RH range
0.05%RH
30s
3s
0 to 100%RH (non-condensing)
-4 to 140oF (-20 to 60° C) @ RH>90%; -4 to 176oF @ RH=50%
Temperature Transmitter (optional)| Type
Nominal Accuracy
Maximum Accuracy (2) Resolution
Response time
Sample rate| With RH option
Silicon Band-gap
±0.3° C (operating range)
±0.5° C (at 25° C), ±1.0° C 0.01° C
30s
3s
Without RH option
NTC Thermistor
±0.5° C (operating range)
±1.0° C (at 25° C), ±2.0° C
0.05° C
30s
100ms
TVOC (optional)| Type
Gas
Range
Response Time
Output| MOS
Total VOC
0-32,000 μg/m3
<10s
0-2000 μg/m3 (default) Programmable up to 32,000 μg/m3
PMx (optional) CLASS 1 LASER PRODUCT| Type
Size Range Scale
Lower detection limit
Precision| Optical
PM1.0, PM2.5, PM4.0, PM10.0
0-1000 μg/m3
0.3 μm
±10 μg/m3 (0-100μg/m3); ±10% (100-1000 μg/m3)
PIR (optional)| Type
Axis X field of view
Axis Y field of view| Passive Infrared
140o, 15 ft (4.5m)
76o, 15 ft (4.5m)
Ambient Light| Type
Scale| Phototransistor
0-100 fc (lm/ft2), readable over communications
Operating Environment| Temperature
Humidity| 32 to 122oF (0 to 50oC)
0-95% non-condensing
Enclosure| Material
Dimensions| ABS Plastic
5.67”h x 3.00”w x 1.07”d
Compliance| Agency| CE, RoHS
- One side of transformer, secondary is connected to signal common. Dedicated transformer is recommended.
- Models with PM sensor included achieve ±5% accuracy over 0 to 80%RH range and an additional temperature shift of up +0.5° C
- Time for reaching 63% of reading at 25° C and 1 m/s airflow
- Long term exposures to conditions outside normal range at high humidity may temporarily offset the RH reading (+3%RH after 60 hours.)
Issued12/17/2021 Document #152-0401-0E
senvainc.com
1-866-660-8864 (F)
1-503-296-2529
9290 SW Nimbus Ave.
Beaverton Oregon 97008
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>