Danfoss FIA 15-300 Strainer Installation Guide
- June 1, 2024
- Danfoss
Table of Contents
Danfoss FIA 15-300 Strainer
Specifications
Model | Torque (Nm) | Torque (LB-ft) |
---|---|---|
DN 15-20 | 22 | 16 |
DN 25-32-40-50 | 44 | 32 |
DN 65 | 75 | 53 |
DN 80 | 44 | 32 |
DN 100 | 75 | 53 |
DN 125-150 | 183 | 135 |
DN 200-300 | 370 | 272 |
Installation
- Note: At delivery the filter housing is not equipped with filter element or accessories.
- The filter must be installed with the top cover downwards, and the flow must be directed towards the top cover as indicated by the arrow on the filter housing. The filter element must be inserted after welding.
- The filter is designed to withstand a high internal pressure. However, the piping system should be designed to avoid liquid traps and reduce the risk of hydraulic pressure caused by thermal expansion. It must be ensured that the filter is protected from pressure transients like liquid hammer in the system.
- Recommended flow direction: The filter must be installed with the flow towards the top cover as indicated by the arrow on the side of the valve body. Flow in the opposite direction is not acceptable.
- Welding: The top cover should be removed before welding to prevent damage to the gasket between the filter body and top cover. Only materials and welding methods compatible with the valve housing material must be welded to the valve housing. The filter should be cleaned internally to remove welding debris on completion of welding and before the valve is reassembled.
Maintenance
- When mounting the filter bag, which is held in place by a filter holder, the utmost care must be taken to place the filter bag correctly in the filter as shown in the diagram. The flow must go into the filter bag cavity and out or else the bag will not function properly.
- Before servicing the filter valves, isolate it from the system and remove all refrigerant by evacuation to zero pressure. Check for refrigerant pressure before unscrewing and removal of the top cover. The filter element should be removed without the use of tools.
- Cleaning: Clean the filter element using an appropriate solvent by flushing and brushing. The use of strong acids is not recommended. The filter element should be wiped or blown dry before inspection. If the element is damaged or the sediments cannot be removed, the filter element should be replaced.
FAQ
What should be done if the filter housing arrives without a filter element or accessories? The filter housing is not equipped with a filter element or accessories at delivery. These should be installed as per the installation instructions provided. How should the filter be installed in terms of flow direction? The filter must be installed with the flow towards the top cover as indicated by the arrow on the side of the valve body. Flow in the opposite direction is not acceptable. Is there a specific welding procedure to follow? Yes, the top cover should be removed before welding to prevent damage to the gasket. Materials and welding methods compatible with the valve housing material must be used, and the filter should be cleaned internally after welding. How can the filter bag be correctly mounted? When mounting the filter bag, care must be taken to place the filter bag correctly in the filter as shown in the diagram. The flow must enter the filter bag cavity and exit properly to ensure functionality. What are the steps for cleaning the filter element? The filter element should be cleaned using an appropriate solvent by flushing and brushing, without the use of strong acids. It should be wiped or blown dry before inspection, and if damaged, it should be replaced.
Please note that due to the limitations of this format, visual diagrams and specific details from images such as precise measurements, figures, and detailed installation instructions are described textually but are not visually represented. For complete visual representations, refer to the original images or documents.
Installation
Refrigerants
Applicable to all common refrigerants, including R717 and non-corrosive
gases/liquids dependent on sealing material compatability.
The filter is only recommended for use in closed circuits. For further
information please contact Danfoss.
Pressure and temperature range
-60 °C/+150 °C (-76 °F/+302 °F)
FIA 15-300:
- The filters are designed for a max. working pressure of 40 bar (580 psig)
- FIA 15-65 (special), FIA-SS 15-65:
- The filters are designed for a max. working pressure of 52 bar (754 psig)
- FIA 80-200 (special), FIA-SS 80-200:
- The filters are designed for a max. working pressure of 50 bar (725 psig)
- FIA 15-300, FIA 15-200 (special), FIA-SS: The filters are designed for a max. working pressure of 40 bar (580 psig)
Note:
At delivery the filter housing is not equipped with filter element or
accessories
The filter must be installed with the top cover downwards, and the flow must be
directed towards the top cover as indicated by the arrow on the filter housing
(fig. 1). The filter element must be inserted after welding.
The filter is designed to withstand a high internal pressure. However, the
piping system should be designed to avoid liquid traps and reduce the risk of
hydraulic pressure caused by thermal expansion. It must be ensured that the
filter is protected from pressure transients like “liquid hammer” in the
system.
Recommended flow direction
The filter must be installed with the flow towards the top cover as indicated by
the arrow on the side of the valve body (fig. 1). Flow in the opposite
direction is not acceptable.
Welding
The top cover should be removed before welding (fig. 2) to prevent damage to
the gasket between the filter body and top cover. Only materials and welding
methods, compatible with the valve housing material, must be welded to the
valve housing. The filter should be cleaned internally to remove welding debris
on completion of welding and before the valve is reassembled.
Removing the top cover can be omitted provided that:
The temperature in the area between the valve body and top cover during
welding does not exceed +150 °C/+302 °F. This temperature depends on the
welding method as well as on any cooling of the filter body during the welding
itself.
(Cooling can be ensured by, for example, wrapping a wet cloth around the filter
body.) Make sure that no dirt, welding debris etc. get into the filter during
the welding procedure.
The filter housing must be free from stresses (external loads) after
installation.
Filters must not be mounted in systems where the outlet side of the filter is
open to atmosphere. The outlet side of the filter must always be connected to
the system or properly capped off, for example with a welded-on end plate.
Assembly
Remove welding debris and any dirt from pipes and filter body before assembly.
Check that the filter element has the right size before it is inserted in the
top cover And check that there is no damage on the gasket.
Place the filter element (pos. D) from underneath. The element has a slight
force fit into the housing, no gaskets or O-rings are used.
If magnets have been chosen as accessory, these should be fitted on the top
cover before replacing the cover.
Tightening
Tighten the top cover with a torque wrench, to the values indicated in the
table (fig. 3).
If the drain valve has been chosen as accessory, the drain plug should be
replaced by the drain valve.
Colours and identification
The FIA valves are painted with a red oxide primer in the factory. Stainless
steel valves are not painted. Precise identification of the valve is made via
the ID plate on the top cover, as well as by the stamping on the valve body.
The external surface of the valve housing must be prevented against corrosion
with a suitable protective coating after installation and assembly.
Protection of the ID plate when repainting the valve is recommended.
FIA-SS filters are not painted and do not require any protective coating.
Maintenance
Mounting of accessory:
Filter bag (fig. 4)
A 50µ filter bag (pos. E), especially for commissioning of the plant, can
replace the normal filter element.
When mounting the filter bag, which is held in place by a filter holder, the
utmost care must be taken to place the filter bag correctly in the filter as
shown in fig. 4. The flow must go into the filter bag cavity and out or else the
bag will not function properly.
Above described function will only be valid depending that the proper flow
direction of the filter valve has been used.
Dismantling the valve (fig. 3)
Before servicing the filter valves, isolate it from the system and remove all
refrigerant by evacuation to zero pressure. check for refrigerant pressure
before unscrewing and removal of the top cover.
The filter element should be removed without any use of tools
Cleaning
Clean the filter element using an appropriate solvent by flushing and brushing.
The use of strong acids cannot be recommended. the filter element should be
wiped or blown dry before inspection. If the element is damaged or the
sediments cannot be removed, the filter element should be replaced.
Assembly
Remove any dirt from the body before the valve is assembled.
Replacement of gasket
It is recommended to always change the gasket for the top cover (pos. C) and
drain plug.
Check that the filter element is correctly placed before remounting the top
cover and bolts (pos. A).
Tightening (fig. 3)
Tighten the top cover bolts (pos. A) with a torque wrench according to the
table in fig. 3
Use only original Danfoss parts, including gaskets for replacement. Materials
of new parts are certified for the relevant refrigerant.
In cases of doubt, please contact Danfoss. Danfoss accepts no responsibility
for errors and omissions. Danfoss Industrial Refrigeration reserves the right
to make changes to products and specifications without prior notice.
Danfoss A/S
Climate Solutions • danfoss.com • +45 7488 2222
Catingues descriptions, advertisements, etc. and whether mael available in
writing orally, electronically, online design, weird, should be considered
more informative techies ical branding it and to manuals, extent, explicit
reference is made in a quotation or order confirmation. Danfoss cannot accept
any responsibility for possible errors in catalogues, brochures, videos and
other material. Danfoss reserves the right to alter its products without
notice. This also applies to products ordered but not delivered provided that
such alterations can be made without changes to form, fit or function of the
product.
All trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
© Danfoss | Climate Solutions | 2022.06
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>