MASTERVOLT 24-15-2 Mass Charger Instruction Manual
- June 1, 2024
- MASTERVOLT
Table of Contents
Mass Charger
MASS 24/15-2, 24/25-2, 24/25-2 DNV, 24/25-2 large cabinet
FULLY AUTOMATIC BATTERY CHARGER USER AND INSTALLATION MANUAL ****
24-15-2 Mass Charger
For the latest version of this manual, visit our website:
www.mastervolt.com
In case of any discrepancy in the interpretation of different language
versions, the English version shall prevail.
GENERAL INFORMATION
1.1 Use of this manual
This manual contains important safety and operating instructions for the safe
and effective operation, maintenance and possible correction of minor
malfunctions of the Mass Charger.
It is therefore obligatory that every person who works on or with the Mass
Charger is completely familiar with the contents of this manual, and that
he/she carefully follows the instructions and important safety instructions
contained herein.
1.2 Validity of this manual
All of the specifications, provisions and instructions contained in this
manual apply solely to standard versions of the Mass Charger delivered by
Mastervolt. This manual is valid for the following models:
Part no | Model |
---|---|
40020156 | Mass 24/15-2 230V/50-60Hz charger |
40020256 | Mass 24/25-2 230V/50-60Hz charger |
40720266 | Mass 24/25-2 230V/50-60Hz charger DNV |
Enl.Cab. CSI
42720266| Mass Charger 24/25-2 230V large cabinet
These models are further mentioned as “Mass Charger” For other models see
other manuals available on our website: www.mastervolt.com
1.3 Use of pictograms
Safety instructions and warnings are marked in this manual by the following
pictograms:
WARNING!
A WARNING refers to possible injury to the user or significant material damage
to the Mass Charger if the user does not (carefully) follow the procedures.
CAUTION!
Special data, restrictions and rules with regard to preventing damage.
1.4 Identification label
The following picture is only an example! The identification label is located at the right-hand side of the
Mass Charger (see figure 1). Important technical information required for
service, maintenance & secondary delivery of parts can be derived from the
identification label.
CAUTION!
Never remove the identification label.
1.5 Liability
Mastervolt can accept no liability for:
- consequential damage due to use of the Mass Charger;
- possible errors in the manuals and their results.
IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
WARNING!
This chapter describes important safety and operating instructions for use of
a Mass Charger in residential, recreational vehicle (RV) and marine
applications.
2.1 General
-
Before using the Mass Charger, read all instructions and cautionary markings on the Mass Charger, the batteries, and all appropriate sections of the manual.
-
To reduce the risk of electric shock – Do not expose Mass Charger to rain, snow, spray, moisture, excessive pollution and condensing circumstances. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the Mass Charger in a non-ventilated room, overheating may result.
-
Use of an attachment or spare part not recommended or sold by Mastervolt may result in a risk of fire, electric shock, or injury to persons.
-
The Mass Charger is designed to be permanently connected to an AC and DC electrical system. Installation of, and work on the Mass Charger, may be carried out only by a qualified, authorised and trained technician or electrician, consistent with the locally
applicable standards and regulations. -
Make sure that all wiring is properly installed and in good electrical condition; and that wire size is large enough for AC ampere rating of the Mass Charger. Check the wiring on a regular base, at least once a year. Do not use the Mass Charger when the wiring is undersized or damaged.
-
Do not operate the Mass Charger if it has received a sharp blow, been dropped, or otherwise damaged in any way; take it to a qualified serviceman.
-
Except for the connection compartment, see chapter 4, the Mass Charger may not be opened or disassembled. There are no serviceable parts inside the cabinet. Take it to a qualified, authorized and trained serviceman when service or repair is required.
Incorrect reassembly may result in a risk of electric shock or fire. Only qualified, electrician installers are authorized to open the connection compartment. -
To reduce risk of electric shock, disconnect the Mass Charger from both AC and DC electrical system before attempting any maintenance or cleaning. Turning off controls will not reduce this risk.
-
The Mass Charger must be provided with an equipment-grounding conductor to the AC-input ground terminal. Grounding and all other wiring must comply with local codes and ordinances.
-
Short circuiting or reversing polarity will lead to seriousdamage to batteries, Mass Charger, wiring as well as accessories. Fuses can not prevent damage caused by reversed polarity and the warranty will be void.
-
In case of fire, you must use the fire extinguisher which is appropriate for electrical equipment.
-
If applied in a marine application in the United States, external connections to the Mass Charger shall comply with the United States Coast Guard Electrical Regulations (33CFR183, Sub part I).
2.2 Explosive gases
-
WARNING – RISK OF EXPLOSIVE GASES.
WORKING IN VICINITY OF A LEAD-ACID BATTERY IS DANGEROUS. BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION. FOR THIS REASON, IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE USING THE MASS CHARGER, YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY. -
To reduce risk of battery explosion, follow these instructions and those published by battery manufacturer and manufacturer of any equipment you intend to use in vicinity of the battery. Review cautionary marking on these products.
-
DANGER: To reduce the risk of explosion – Never use the Mass Charger in situations where there is danger of gas or dust explosion or an area in which ignitionprotected equipment is
required.
2.3 Warnings regarding the use of batteries
-
Someone should be within range of your voice or close enough to come to your aid when you work near a leadacid battery.
-
Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or eyes.
-
Wear complete eye protection and clothing protection. Avoid touching eyes while working near battery.
-
If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flood eye with running cold water for at least 10 minutes and get medical attention immediately.
-
NEVER smoke or allow a spark or flame in vicinity of a battery or engine.
-
Do not short circuit batteries, as this may result in explosion and fire hazard! Be extra cautious to reduce risk of dropping a metal tool onto a battery. It might spark or short-circuit battery or other electrical part and may cause explosion.
-
Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a battery.
A battery can produce a short-circuit current high enough to weld a ring or the like to metal, causing a severe burn. -
Only use the Mass Charger for charging Lead-acid, NiCad and Li-ion batteries and the supply of users attached to these batteries, in permanent systems. Do not use the Mass Charger for charging dry-cell batteries that are commonly used with home appliances. These batteries may burst and cause injury to persons and damage to property.
-
NEVER charge a frozen battery.
-
Excessive battery discharge and/or high charging voltages can cause serious damage to batteries. Do not exceed the recommended limits of discharge level of your batteries.
-
If it is necessary to remove a battery, always remove the grounded terminal from the battery first. Make sure all accessories are off, so as not to cause an arc.
-
Be sure that the area around the battery is well ventilated while the battery is being charged. Refer to the recommendations of the battery manufacturer.
-
Batteries are heavy! It may become a projectile if it is involved in an accident! Ensure adequate and secure mounting and always use suitable handling equipment for transportation.
2.4 Warning regarding life support applications
The Mass Charger is not sold for applications in any medical equipment
intended for use as a component of any life support system unless a specific
written agreement pertaining to such intended use is executed between the
manufacturer and Mastervolt. Such agreement will require the equipment
manufacturer either to contract additional reliability testing of the Mass
Charger and/or to commit to undertake such testing as a part of the
manufacturing process. In addition, the manufacturer must agree to indemnify
and not hold Mastervolt responsible for any claims arising from the use of the
Mass Charger in the life support equipment.
2.5 Guarantee specifications
Mastervolt guarantees that this unit has been built according to the legally
applicable standards and specifications. Should work take place, which is not
in accordance with the guidelines, instructions and specifications contained
in this user manual, then damage may occur and/or the unit may not fulfil its
specifications. All of these matters may mean that the guarantee becomes
invalid.
The guarantee is limited to the costs of repair and/or replacement of the
product. Costs for installation labor or shipping of the defective parts are
not covered by this guarantee.
OPERATION
3.1 Introduction
The MASS battery charger is a full-automatic high efficiency battery
charger/rectifier, developed and produced by Mastervolt. The MASS series
features a family of advanced quality battery chargers. The Mass Charger not
only charges batteries rapidly and safely, it supplies the connected consumers
at the same time. In addition, the Mass Charger is secured against short
circuit, overload and high temperatures in an industrial environment.
3.1.1 Switching on
The battery charger is switched on by the ON/OFF switch.
One of the front LEDs will light up now and the charging starts immediately.
3.1.2 Switching off
The battery charger is switched off by the ON/OFF switch.
WARNING!
Switching off the Mass Charger does not cut off the connection to the
batteries or the AC-source.
This means that voltages are still available inside the apparatus.
3.2 Theory of operation
The battery charger is equipped with an intelligent 3-stage charge
characteristic which takes care of an optimal charge of your batteries (see
figure 2). When switched on, the Mass Charger always starts at Bulk
phase.To prevent your batteries from overcharging a new cycle
only starts when the battery voltage has been under the level of 12.8/25.6 or
51.2V for longer than 30 seconds or after a hard reset by switching the on/off
switch back and forward.
3.3 Front panel
See figure 3. On the front of the Mass Charger LED 9 to 13 represent the
charging current. The more LEDs are illuminated, the higher the charging
current. LED 1-5 represent the charging state.
Illuminating LEDs | Meaning |
---|---|
Normal operation | LED 6 illuminates green |
1 | Charger on, BULK stage |
1+2 | Uout> 27.6V |
1+2+3 | ABSORPTION, Uout = abs. (28.5V) |
1+2+3+4 | 3 hrs after start max bulk timer, or I < return amps |
1+2+3+4+5 | FLOAT, 6 hrs after start max bulk timer, or I < return amps for 15 |
min or longer
9| Charge current 0-5% of full current
9+10| Charge current 5-25% of full current
9+10+11| Charge current 25-50% of full current
9+10+11+12| Charge current 50-75% of full current
9+10+11+12+13| Charge current 75-100% of full current
6| Green: normal operation, Red: fault condition, Off: standby or off
7| Green: MasterBus communication, Off: no MasterBus communication
Fault condition,| LED 6 illuminates red
6 red +1| Battery sense error
6 red +2| Charger temperature too high
6 red +3| Short circuit indication, charger will reduce the charge current to
25%
6 red +4| DC error, DC voltage too low or too high
6 red +5| Temperature sense error
3.3.1 Bulk (LED 1 illuminates)
The battery is empty when only the first LED Bulk/ON illuminates. In this
stage the Mass Charger gives full current (see figure 2 stage A) and the
battery voltage will slowly increase.
3.3.2 (LED 1 and 2 illuminate)
After reaching the level of 27.6V (24V charger) the battery is charged for
about 25% and the second LED will also illuminate. The Mass Charger still
gives the maximum output current and the voltage will increase till the
absorption voltage level (see figure 2 stage A). The maximum time of stage A
is 8 hours.
3.3.3 Absorption (LED 1, 2 and 3 illuminate)
The battery has been charged for 80% (figure 2 stage B). The Mass Charger
limits the charge voltage to a safe level and the charge current will decrease
slowly during charging.
3.3.4 (LED 1 to 4 illuminate)
The charge voltage is limited at the absorption level. As the battery is
almost full, the charge current will further decrease.
3.3.5 Float (LED 1 to 5 illuminate)
When all LEDs are illuminated the battery is fully charged.
The float charge stage provides a lower output voltage, sufficient enough to
maintain the batteries at 100% charge but low enough to prevent your batteries
from unnecessary stress. In this stage the Mass Charger is able to supply full
current to the connected users/loads.
Note: The Mass Charger automatically resumes operation
in Bulk stage after it was disconnected from an ACsource temporarily.
3.4 Temperature compensated charging
By installing the battery temperature sensor, the charge voltages are
automatically adapted for deviating temperatures. This can increase the
battery’s lifetime substantially and save you a lot of money.See figure 4. When the battery temperature is low, the charge
voltage increases. On the other hand, when the battery temperature is high,
the charge voltage is decreased. Over charge and gassing are prevented this
way. This will extend the life of your batteries.
3.5 Compensation of the cable losses
The Mass Charger can compensate the voltage drop occurring over the DC cables.
For this purpose, the Mass Charger is provided with terminals for sense wires.
The sense wires are connected closest possible to the batteries in order to
charge them with the right voltage. When only the minus sense wire is
connected only the losses of the minus DC cable will be compensated.
Connecting both cables produces the best result, all losses will be
compensated until a maximum of 3V in total.
3.6 Alarm function
The battery charger is equipped with an integrated alarm function. External
equipment can be controlled by the potential free contacts of this alarm. The
maximum switch current of the relay is 1A. Exceeding the setpoints (refer to
section 7.7) will activate the alarm.
3.7 Charging a second battery
Some installations have a main battery set and besides this a smaller
(cranking) battery with the same voltage. It is possible to maintain this
second battery with the 3A output of the battery charger.
3.8 Equalize mode
An equalizing charge can be necessary after very deep discharges and/or
inadequate charges. This has to be carried out according to the specifications
of the battery manufacturer.
WARNING!
Equalization is ONLY applicable for wet type batteries and will damage
gel/AGM/Spiral type batteries!
Incorrect use of the equalize mode may lead to hazardous situations. Do not
smoke or use any naked flame or other sources of ignition due to risk of
explosion. Always ventilate the battery room during equalizing to clear the
air.
During equalizing the batteries are brought into the gas state and permitted
load voltages may be exceeded. Refer to chapter 9 for characteristics.
Therefore, appropriate measures must be taken, e.g. disconnect all loads from
the battery and ventilate the room. For these reasons the equalizing mode
should only be used by trained technical engineers.
The equalizing mode can only be started when the Mass Charger is in operation.
To start the equalize mode, select Equalize in the MasterBus device settings
(section 7.2).
INSTALLATION
During installation and commissioning of the Mass Charger, the important
safety instructions are applicable at all times.
See chapter 2 of this manual.
Please check the contents of the box before you start with the installation.
The contents of the box need to be:
- The Mass battery charger;
- Battery temperature sensor (incl. 6 m cable);
- A MasterBus terminating device;
- This user’s manual;
If one of these items is missing, please contact your supplier.
4.1 Installation environment
Choosing a location to install:
- Install the Mass charger in a well-ventilated room protected against rain, snow, spray, vapour, bilge, moisture and dust.
- Ambient temperature: 0 … 60°C / 32°F … 140°F; (power derating above 40°C / 104 °F to decrease the internal heat sink temperature).
- Humidity: 0-95% non-condensing.
- Never use the Mass charger at a location where there is danger of gas or dust explosions
- Mount the Mass Charger in such a way that obstruction of the airflow through the ventilation openings is prevented. No objects must be located within a distance of 10 cm / 4 inch around the Mass Charger.
- Mount the Mass Charger vertically, with the connecting cables downwards.
- Do not install the Mass Charger in the same compartment as the batteries. Do not mount the Mass Charger straight above the batteries because of possible corrosive sulphur fumes.
4.2 Connections
Before making the connection between the battery charger and the system be
sure that the AC and DC system are switched off. Remove the fuses in order to
protect your self against unexpected start up.
4.3 Wiring
CAUTION!
The wire and fuse sizes stated in this manual are given as example only.
Prescribed wire and fuse sizes may be different due to local applicable
regulations and standards.
4.3.1 AC wiring
Check if the voltage of your mains source or generator corresponds with the AC
input voltage of the battery charger as mentioned on the identification label,
see section 1.4.
Strip the cable according to figure 5. It is important that the green/ yellow
earth wire is ± 1 cm (0.4 inch) longer than the other wires. By accidentally
pulling at the cable, the earth wire stays connected to the Mass Charger
longer which offers additional safety. Connect the green/yellow wire to PE,
brown to L1 and the blue wire to the N terminal.
Don’t use a cross section that is smaller than indicated. See table below to select the appropriate cross section for the AC wiring (up to 6m / 20ft length):
AC Current | Minimum cross section: |
---|---|
3-4 Amp | 0.5 mm² |
4-6 Amp | 0.75 mm² |
Connection of AC-wiring and recommended wire colours:
Wire color | Meaning | Must be connected to: |
---|---|---|
Brown or black | Phase | L1 |
Blue | Neutral | N |
Green/Yellow | Earth | PE / GND |
4.3.2 AC safety grounding
WARNING!
The ground wire offers protection only if the cabinet of the Mass Charger is
connected to the safety ground. Connect the ground terminal (PE / GND) to the
hull or the chassis.
CAUTION!
For safe installation it is necessary to insert a Residual Current Device
(earth leakage switch) in the AC input circuit of the Mass Charger.
4.3.3 DC wiring
Keep the cable connection between charger and batteries shortest possible. If
available, use coloured battery cables.
If this is not possible, mark the plus and the minus cables with coloured
insulating tape, e.g. red for plus and blue/black for minus. Use the following
diameters:
Model Mass Charger | Length <3 m | Length 3-6 m |
---|---|---|
Mass 24/15-2 | 6 mm² | 10 mm² |
Mass 24/25-2 | 10 mm² | 16 mm² |
Mass 24/25-2 DNV | 10 mm² | 16 mm² |
Connection of main batteries
- Pull the cables through the cable glands of the Mass Charger.
- Crimp on the ring M6 terminals to the cable.
- Connect the cables to the terminals of the Mass Charger. Pay attention to the polarity, positive on positive / negative on negative.
- Integrate a suitable fuse (charger fuse) in the positive cable. When using a DC distribution with fuses, no additional fuse is necessary.
- Cut the cables at length and crimp on the ring terminals. Connect the cable to the DC distribution or batteries.
CAUTION
Reversing the positive and negative battery poles will severely damage the
Mass Charger.
Too thin cables and/or loose connections can cause dangerous overheating of
the cables and/or terminals.
Lay the positive and negative cables next to each other to limit the
electromagnetic field around the cables. The negative cable should be
connected directly to the negative post of the battery bank or the ground side
of a current shunt. Do not use the hull or chassis frame as the negative
conductor.
4.4 Battery capacity
Always follow the instructions published by battery manufacturer. The minimum
required battery capacity for Mastervolt gel batteries is as follows:
Model Mass Charger | Minimum required battery capacity |
---|---|
Mass 24/15-2 | 50 Ah |
Mass 24/25-2 | 60 Ah |
Mass 24/25-2 DNV | 60 Ah |
4.5 Battery isolator
If one or more batteries or battery sets must be charged at the same time via
one output, a battery isolator should be used. It isolates the different
battery sets from one another, to prevent one discharging the other. A
consequence of the battery isolator is a voltage drop of 0.6 Volt. This
voltage drop can be compensated in two ways:
- By changing DIP-switch 4 to On (Diode enabled);
- By using the voltage sense function (see section 4.8).
CAUTION!
Never use both methods. Your batteries will be overcharged and severely
damaged!
Mastervolt offers several Battery Isolators, refer to
www.mastervolt.com.
For a proper installation, see also the connection diagram included with the
battery isolator.
Steps:
- Check if the Mass Charger, the main supply and the DC distribution are switched off.
- Check if the Dc fuses have been removed.
- Connect the battery isolator(s) using cables with the same diameter as the battery cables.
- Compensate the voltage drop over the battery isolator by changing the setting of dip switch 4 (see figure 7).
- Switch on the Mass Charger.
4.6 Connection of second battery (3A output)
The battery chargers are standard equipped with a second charge output of 3A
in order to give a small second battery set like a starter battery a
maintenance charge. The maximum charge current of the second output is 3A,
which comes from the main output.
- Use 2.5 to 4 mm2 cable for connection.
- Connect the minus of the second battery to the minus of the main battery.
- Connect the plus of the second battery to the +3A terminal of the Mass Charger (see figure 7 and 8).
- Integrate a 10A slow blow fuse in the plus cable.
4.7 Temperature sensor
The standard temperature sensor is provided with 6 m cable and a double-sided
tape for easy installation. Determine the warmest place on the battery set and
make it clean and grease free. Remove the piece of paper from the tape and
stick the sensor on the battery. Plug the modular cable into a terminal at the
right of the Mass Charger (see figure 7). It is not necessary to shorten the
cable. When you want to shorten it anyway, please notice the polarity of the
plug and use the old connector as an example.
4.8 Voltage sense
To shorten the charge time substantially, the battery cable losses can be
compensated by using the sense function. Use 0,75 mm2 , preferably red and
black wire and secure these with fuses of 2A slow blow. Connect the wires with
the two upper terminals of the green connector at the right side of the
cabinet (see figure 7). Pay good attention to the polarity of the wires, red
on +S and black on -S. Now connect the other side of the wires: black on the
minus of the battery and red on the battery side of the Mass Charger fuse.
4.9 Alarm function
The battery charger is equipped with a potential free contacts alarm relay,
see figure 7. The alarm function has two modes: standard (factory setting) and
DC alarm mode (continuous mode).
4.9.1 Standard alarm mode
In this mode the relay responds to all fault conditions that the Mass Charger
can detect such as: no AC input voltage,
4.12 Overview connection compartment
Figure 7 shows the Mass Charger connections. too low DC voltage, voltage sense
failure, temperature sense failure.
4.9.2 DC alarm mode
To enable this mode a DIP switch setting needs to be changed (switch 1 and 2
at ON). The alarm now works as a DC alarm and responds to the battery voltage
only.
Note: In the DC alarm mode the electronics stay active permanently and
drain a very small current of ± 25mA, also when the Mass Charger is switched
off.
4.10 DNV version
The Mass Charger 24/25-2 is equipped with a larger connection compartment that
offers more room for the cabling. Refer to section 9.2 Dimensions for more
information on the larger DNV housing.
4.11 Connection of accessories
The battery charger is equipped with several terminals for accessories. Cable
to connect the accessories is not delivered as a standard. Accessories can be
plugged in at all times. Contact your Mastervolt dealer for an overview of
available accessories.
- Earth stud
- AC cable gland
- Screw terminal AC input (N,L)
- MasterBus cable gland
- Cable glands DC (+,-)
- Output extra battery (max 3A)
- Main positive output
- RS232/Temperature sensor port
- 2 MasterBus ports
- Main negative output
- DIP switch module
- Voltage sense/ potential free alarm contact
4.13 Materials
Make sure you have all the parts you need to install the Mass Charger:
Product | Quantity |
---|---|
Mass Charger (included) | 1 |
Battery temperature sensor with cable and plug (included). | 1 |
DC-cable to connect the positive DC connection (+) of the Mass Charger to the
positive pole of the DC-distribution; for specifications see section 4.3.3.| 1
DC-cable to connect the negative DC connection (–) of the Mass Charger to the
negative pole of the DCdistribution; for specifications see section 4.3.3.| 1
DC-fuse holder with a DC-fuse, to be integrated in the positive DC-cable.| 4
Screws / bolts (Ø 6mm) (with plugs) to mount the cabinet to a surface. Use
mounting materials which are suitable to carry the weight of the Mass Charger|
1
AC cable* to connect the AC input to an external power source (e.g. a shore
connection or a generator set);| X
Batteries. See section 4.4 for recommended capacity| X
Appropriate and reliable cable terminals, cable lugs, battery terminals and
cord end terminals| 1
-
Double insulated three wire cable with wire colours according to the locally applicable regulations. The applicable length and wire diameter depend on the electrical installation (see section 4.3.1).
We recommend as a minimum tool kit:- Socket wrench 13mm to fix the DC-input (battery) cables
- Flat blade screwdriver 1.0 x 4.0 mm to fix the screw terminals
- Tools to fix the screws / bolts (Ø 6mm) with plugs to mount the cabinets to a surface
- Philips screwdriver to open the connection area of the Mass Charger
- 2 mm flat blade screwdriver for the sense terminal (figure 7 point 12).
4.14 Connection
WARNING!
Let installation work be done by a licensed electrician. Before beginning with
the connection of the wiring, make the AC distribution as well asthe DC
distribution voltage free.
CAUTION!
Short circuiting or reversing polarity may lead to serious damage to the
batteries, the Mass Charger, the cabling and/or the terminal connections.
Fuses between the batteries and the Mass Charger can not prevent damage caused
by reversed polarity. The damage as a result of reverse polarity is detectable
by the service department and is not covered by the warranty.
CAUTION!
Too-thin cables and/or loose connections can cause dangerous overheating of
the cables and/or terminals. Therefore, tighten all connections well, to limit
transition resistance as far as possible. Use cables of the correct size.
Notes:
- If the battery temperature remains within 15-25°C, connection of the battery temperature sensor is optional.
- The Mass Charger is feasible for the connection of MasterBus and RS 232 compatible remote control panels.
This schematic is to illustrate the general placement of the Mass Charger in a
circuit. It is not meant to provide detailed wiring instructions for any
particular electrical installation.
4.15
Installation step-by-step
-
Mark the position of the mounting spots using the drilling dimensions.
-
Place the four screws first and hang the Mass Charger over them. Then fix the Mass to the wall by securing the screws.
-
Open the connection compartment byloosening the two screws.
-
Feed the AC wiring through cable gland and connect the wiring to the screw terminals.
Tighten the cable gland firmly. -
Connect the DC-cabling of the house bank, positive to +, negative to –.
-
Connect second battery bank: Connect the DC-wiring of the second battery bank (max. 3A).
This bank has a common negative with the main battery. -
Attach the battery temperature sensor to the casing of the main battery bank .
Plug the temperature sensor cable into the “temp.sensor” jack. -
Option: Connect the Mass Charger to the MasterBus network.
-
The factory setting of the Mass Charger is optimal for most installations. Sometimes however, it is desirable to change these settings. See ch. 5 DIP switch adjustment and chapter 7 for MasterBus settings.
-
Check all wiring; see also figure 8 for wiring details. If everything is all right, close the connection compartment by fixing the two screws.
-
Continue with section 4.16 for commissioning of the Mass Charger.
4.16 Commissioning after installation
Note: When your Mass Charger is not new, you have to take into account
that former users may have changed the settings. Reset the Mass Charger to
factory settings when there is any doubt (see section 6.3).
4.16.1 General
The factory settings of the Mass Charger are optimal for most
installations. With some applications however, it is desirable to change these
settings. Therefore, several adjustments can be made. See chapters 5 and 7.
Note: The DIP-switches must be adjusted prior to commissioning; all other
settings can only be made after commissioning.
CAUTION!
Check the polarity of all wiring before commissioning: positive connected
to positive (red cables), negative connected to negative (black cables).
If all wiring is OK, place the DC-fuse(s) of the DCdistribution to connect the
batteries to the Mass Charger.
WARNING!
When placing this fuse, a spark can occur, caused by the capacitors used in
the Mass Charger. This is particularly dangerous in places with insufficient
ventilation, due to the gassing of the batteries an explosion can occur. Avoid
having flammable materials close by.
Now the Mass Charger is ready for operation. After switching on the AC power
supply the Mass Charger will initiate the charging process.
4.16.2 MasterBus (optional)
During first commissioning the Mass Charger will be recognized by the
MasterBus network automatically. The remote control panel of the MasterBus
network will indicate that a new device was found.
Some settings can only be changed via the MasterBus interface. See chapter 7
for an overview of all available MasterBus settings. Refer to the user manual
of the remote control panel to change these settings.
4.17 Decommissioning
If it is necessary to put the Mass Charger out of operation, follow the
instructions in order of succession as described below:
- Switch OFF the Mass Charger (see section 3.1.2).
- Remove the DC-fuse(s) of the DC-distribution and/or disconnect the batteries.
- Remove the AC-fuse(s) of the AC-input and/or disconnect the AC-mains.
- Open the connection compartment of the Mass Charger.
- Check with a suitable voltage meter whether the inputs and the outputs of the Mass Charger are voltage free.
- Disconnect all the wiring.
Now the Mass Charger can be demounted in a safe way.
4.18 Storage and transportation
When not installed, store the Mass Charger in the original packing, in a dry
and dust free environment. Always use the original packing for transportation.
Contact your local Mastervolt Service Centre for further details if you want
to return the apparatus for repair.
4.19 Re-installation
To reinstall the Mass Charger, follow the instructions as described in this
chapter (chapter 4).
DIP SWITCH SETTINGS
The Mass Charger settings can be adjusted in two ways:
- By means of DIP switches;
- Via the MasterBus network (using a remote control panel or the Mastervolt USB interface connected to a PC with MasterAdjust software); see chapter 6. Some settings, e.g. Lithium-ion, can only be changed this way.
Note: Once a DIP switch has been set to On, MasterBus settings are
disabled.
CAUTION!
Invalid settings of the Mass Charger can cause serious damage to your
batteries and/or the connected load! Adjustments of settings may be undertaken
by authorised personnel only!
5.1 DIP switch operation
The Mass Charger has four DIP switches. These switches are operated by
flipping the levers to the other position, using a small screwdriver.
DIP switch | 4 | 3 | 2 | 1 |
---|---|---|---|---|
Standard (Flooded) | 0 | 0 | 0 | 0 |
ForceFloat | 0 | 0 | 0 | 1 |
ContMon | 0 | 0 | 1 | 1 |
Diode | 1 | 0 | 0 | 0 |
ForceFloat + Diode | 1 | 0 | 0 | 1 |
ContMon + Diode | 1 | 0 | 1 | 1 |
Gel/AGM | 0 | 1 | 0 | 0 |
ForceFloat + Gel/AGM | 0 | 1 | 0 | 1 |
ContMon + Gel/AGM | 0 | 1 | 1 | 1 |
Diode + Gel/AGM | 1 | 1 | 0 | 0 |
ForceFloat + Diode + Gel/AGM | 1 | 1 | 0 | 1 |
ContMon + Diode + Gel/AGM | 1 | 1 | 1 | 1 |
Traction | 0 | 0 | 1 | 0 |
ContMon + Traction | 0 | 1 | 1 | 0 |
Diode + Traction | 1 | 0 | 1 | 0 |
ContMon + Diode + Traction | 1 | 1 | 1 | 0 |
1 = ON; 0 = OFF
5.2 DIP switch functions
See the table for the functional overview of the four DIP switches
-
Force Float (DIP switch 1)
For special applications a fixed charge voltage can be required. The battery charger allows you to change the three-stage charge program to a single stage program by activating the function “Force Float”, switching DIP switch 1 to “ON”. The charge voltage will be fixed at 26.5V (24V charger) -
Traction setting (DIP switch 2)
Setting for traction charging: +0.7 V during bulk and +0.4 V in absorption for 24 V batteries. -
Gel/AGM batteries (DIP switch 3) Some gel/AGM batteries need a higher float voltage for optimal charge. Changing the float voltage can be done by setting DIP switch 3 to “ON”. The float voltage will increase to 27.6V (24V charger).
-
Diode setting (DIP switch 4)
Setting for +0.6 V voltage compensation in case a battery isolator is used.
See page 19 for an overview of charging specifications.
Force float: | One step charge program with fixed float voltage. |
---|---|
ContMon: | Continuous monitor mode. MasterBus, RS232 and DC-alarm stay |
functioning at mains failure. Remote stays functioning if it has its own power
source.
Diode:| Diode compensation on (+0.6V)
MASTERBUS
6.1 What is MasterBus?
All devices that are suitable for MasterBus are marked by the MasterBus
symbol.
MasterBus is a fully decentralized data network for communication between the
different Mastervolt system devices. It is CAN-bus based which has proven
itself as a reliable bus-system in automotive applications. MasterBus is used
as power management system for all connected devices, such as the inverter,
battery charger, generator and many more. This enables communication between
the connected devices, for instance to start the generator when the batteries
are low.
MasterBus reduces complexity of electrical systems by using UTP patch cables.
All system components are simply chained together. Therefore, each device is
equipped with two MasterBus data ports. As only a few MasterBus cables are
needed, installation and material costs are reduced importantly. New devices
can be added to the existing network easily. Consequently, the MasterBus
network is highly flexible for extended system configuration.
Mastervolt also offers several interfaces like the Modbus and NMEA interface,
making even non-MasterBus devices suitable to operate in the MasterBus
network. For central monitoring and control of the connected devices
Mastervolt offers different remote control panels. All monitoring panels can
be used for monitoring, control and configuration of all connected MasterBus
equipment.
CAUTION!
Never connect a non-MasterBus device to the MasterBus network directly! This
will void warranty of all MasterBus devices connected.
6.2 How to set up a MasterBus network
Every MasterBus device is equipped with two data ports.
When two or more devices are connected via these ports,a local data network
called the MasterBus is formed.
Keep the following rules in mind:
Place a terminating device on both network ends. Connections between the devices are made by standard straight UTP
patch cables. At least one device in the network must be MasterBus
powering (see specifications). As all powering devices are galvanic isolated,
multiple powering devices are allowed. Do not make ring networks. Do not make T-connections
in the network.
6.3 MasterBus settings
Below parameters can be changed via the MasterBus network by means of a remote
control panel or by means of an interface connected to a PC with MasterAdjust
software. See applicable user manuals for details.
Meaning | Factory setting | Adjustable range |
---|
Device
Language| Language that is displayed on a monitoring device connected to the
MasterBus.| English| EN, NL, DE, FR, ES,
IT, NO, SV, FI, DA
Name| Name for the Mass Charger.| CHG Mass+type| 0-12 characters
Device| Device name recognized by MasterBus.| Mass Charger| –
Battery name| Name for the main battery bank.| House Bank| 0-16 characters
Factory settings| Option to reset the Mass Charger to default settings.| |
Presets
Diode compensate| Option for charger diode +0.6 V voltage compensation. If it
is enabled, the compensation value is adjustable.| Disabled| Disabled,
Enabled: 0-2.50 V
Forced float| Option for Forced Float or constant voltage charging. If it is
enabled, Forced Float voltage is adjustable.| Disabled| Disabled, Enabled
Continuous mode| Option to keep MasterBus powered by the battery when the Mass
Charger is disabled.| Disabled| Disabled, Enabled
Battery| The battery type settings are based on Mastervolt batteries. If
connecting batteries of a different manufacturer, make sure the manufacturer’s
recommendations are met. Should this not be the case, then “User defined” must
be selected to change the settings.| Flooded| User defined, Gel/AGM, Flooded,
Traction, NiCad,
Lithium-ion
Equalize| Option to enable Equalizing. Shown only when no other battery type
has been selected.
WARNING!
Equalize is ONLY applicable for flooded batteries! Do not use Equalize for
other battery types!
General
Max. current| Maximum charge current, adjustable model dependent.| Model
dependent| 0-100% Imax
Temp. compensate| Charge voltage compensation for temperature(V/°C).| -0.060
V/°C| -1.000 .. 1.000 V/°C
Output reduction| Output reduction that can be used as target event to adjust
the maximum current.| 0%| 0-90%
Relay| Alarm setpoints
DC Alrm high on| Alarm DC High on| 32.00 V| 16.00-32.00 V
DC Alrm high off| Alarm DC High off| 31.00V| 16.00-32.00 V
DC Alrm low on| Alarm DC low on| 20.00V| 16.00-32.00 V
DC Alrm low off| Alarm DC low off| 22.00V| 16.00-32.00 V
DC Alrm delay| Alarm delay time| 30 sec| 0-255 sec
Bulk
Bulk voltage| Bulk voltage| 28.50 V| 16.00-32.00 V
Max bulk time| Maximum bulk timer| 480 min| 0-600 min
Min bulk time| Minimum bulk timer| 2 min| 0-600 min
Start bulk time| Voltage at which to start the bulk timer.| 26.50 V|
16.00-32.00 V
Bulk ret. volt.| Return to Bulk voltage| 25.60 V| 16.00-32.00 V
Bulk ret. time| Adjustable Return to Bulk time after the Return to Bulk
voltage has been reached.| 30 sec| 0-255 sec
Absorption
Abs. voltage| Absorption voltage| 28.50 V| 16.00-32.00 V
Max absorption| Maximum absorption timer| 240 min| 0-600 min
Min absorp. time| Minimum absorption timer| 15 min| 0-180 min
Return amps| Return to Bulk current (in A)| 6.0 %*I max| 0-25 A
Meaning| Factory setting| Adjustable range
---|---|---
Float
Float voltage| Float voltage| 26.50 V| 16.00-32.00 V
Equalize voltage| Equalize voltage| 31.00 V| 16.00-32.00 V
Equalize time| Equalize time| 360 min| 0-600 min
* Depending on model
Note: the following charge specifications are based on Mastervolt
batteries. Specifications for a given chemistry of a different manufacturer
may vary.
Charging specifications | Battery type |
---|---|
Flooded | GEL/AGM |
Bulk voltage | 28.50V |
Max bulk time | 480 min |
Min bulk time | 2 min |
Start bulk time at | 26.50V |
Return to bulk voltage | 25.60V |
Bulk return time | 30 sec |
Absorption voltage | 28.50V |
Max abs. time | 240 min |
Min abs. time | 15 min |
Return amps | 6.0 %*I max |
Float voltage | 26.50V |
- Depending on model
6.4 Event based commands
With MasterBus a device can be programmed to initiate an action at another connected device. This is done by means of eventbased commands.
Events
Field | Meaning | Factory setting | Adjustable range |
---|---|---|---|
Event x source | Event-based command. |
Mass Charger event that should result in an action by another device on the
MasterBus network.| Disabled| See Event source list.
Event x target| Select a connected MasterBus device that should take action
due to a Mass Charger event.| Select…| Selectable targets are system
dependent.
Event x command| Action to be taken by the target device.| Select…| See
command list in selected device manual
Event x data| Data is linked to the command. See also figure 10.| Off| Off,
On, Copy, Copy Invert, Toggle.
Event x+1| The next event appears after enabling Event x.| Disabled| See Event
x.
Input (pulses)
The input is represented by an on/off switch.
Output (data)
On changes the status to On at the first signal.
Off changes the status to Off at the first signal.
Copy lets the status follow the input.
Copy Invert lets the status follow the opposite of the input
Copy is used for dimming too by holding the pulse switch pressed for a
longer time.
Toggle changes the status at the first signal and back at the second
signal. It is used in combination with a pulse switch.
Mass Charger event source list (Mass Charger as event source)
Event source | Meaning |
---|---|
Charging | Mass Charger state is On |
Bulk | Charge stage is Bulk |
Absorption | Charge stage is Absorption |
Float | Charge stage is Float |
Failure | Charger failure MasterBus alarm |
CSI | Charger Status Interface MasterBus alarm to generate an audible alarm at |
charger failure
Equalize| Mass Charger is in Equalize mode
TC Error| Battery temperature sensor error
Fan| MasterBus signal for an external fan to start (at 50% load / 50°C)
LED Bulk| LED Bulk illuminates
LED 20-40| LED 2 illuminates (see figure 3)
LED Abs| LED Abs illuminates
LED 60-80| LED 4 illuminates (see figure 3)
LED Float| LED Float illuminates
LED Failure| LED Failure illuminates
Mass Charger event target list (Mass Charger as event target)
Event target | Meaning |
---|---|
Mpc reduce | Command to reduce AC current at a 5%/sec rate |
Mpc off | Command to reduce AC current fast |
Bulk | Command to start the Bulk stage of charge |
Absorption | Command to start the Absorption stage of charge |
Float | Command to start the Float stage of charge |
On/ Standby | Command to switch on the Mass Charger |
Output reduction | Command to reduce the output of the Mass Charger e.g. when |
set to 90%, max. current will be 10% when event is received
TROUBLE SHOOTING
In case of a failure, the Mass Charger display shows an error code to help you
find its source. See section 3.3 for error codes.
If you cannot solve a problem with the aid of the fault-finding table, contact
your local Mastervolt Service Centre. See
www.mastervolt.com. Make sure you have the
article and serial number present if you have to contact your local Mastervolt
Service Center to solve a problem (See section 1.4)
Malfunction | Possible cause | What to do |
---|---|---|
No output voltage and/or current | No AC-input. | Check AC wiring, check remote |
control panel.
AC-input voltage too low (< 180VAC).| Check input voltage, check generator.
AC input frequency out of range.| Check input voltage, check generator.
Output voltage too low, charger supplies maximum current| Load that is
connected to the batteries is larger than charger can supply.| Reduce load
taken from the batteries.
Batteries not 100% charged.| Measure battery voltage. After some time this
will be higher.
Charge current too low| Batteries almost fully charged.| Nothing, this is
normal when the battery is almost fully charged.
High ambient temperature.| Nothing; if ambient temperature is more than 40°C
the charge current is automatically reduced.
Low AC input voltage. At lower AC-input voltages the charge current is
reduced.See figure 12.| Check AC-input voltage.
Batteries not fullycharged| Charge current too low.| See “Charge current too
low”.
Current to load is too high.| Reduce load taken from the batteries.
Charge time too short.| Use a battery charger with higher capacity.
Battery temperature too low.| Use the battery temperature sensor.
Defective or old battery.| Check battery and replace if necessary.
Batteries are discharged too fast| Battery capacity reduced due to wastage or
sulphation, stagnation.| Charge and recharge a few times, this might help.
Check battery and replace if necessary.
Batteries are too warm, gassing| Defective battery (short circuit in cell).|
Check battery and replace if necessary.
Battery temperature too high.| Use the battery temperature sensor.
Charge voltage too high.| Check settings (see chapter 7).
TECHNICAL DATA
8.1 Specifications
Model| Mass 24/15-2| Mass 24/25-2| Mass 24/25-2 DNV / large
cabinet
---|---|---|---
Product code| 40020156| 40020256| 40720266 / 42720266
INPUT
Mains voltage| 230V, -10% + 15%| 230V, -10% + 15%| 230V, -10% + 15%
Frequency| 50/60 Hz ± 5 Hz| 50/60 Hz ± 5 Hz| 50/60 Hz ± 5 Hz
Inrush current| None, the battery charger is equipped with a soft start in
accordance with IEC 1003-3
Input current| 2.5 A| 3.6 A| 3.6 A
Power factor (Cos phi)| 1| 1| 1
Maximum efficiency| 89%| 89%| 89%
Input power| 550W| 800W| 800W
OUTPUT
Nominal voltage| 24V DC| 24V DC| 24V DC
Max charge current (Imax)| 15 A| 25 A| 25 A
Outputs| 1×15 A and 1×3 A| 1 x 25 A and 1×3 A| 1 x 25 A and 1×3 A
Charge characteristic| 3-step, fully automatic| 3-step, fully automatic|
3-step, fully automatic
Battery types*:| Flooded lead acid, gel/AGM lead acid, NiCd, Mastervolt
Lithium-ion (Mastervolt MLI) (see section 6.3 for settings)
Default charge voltages at 25°C:
absorption| 28.5V| 28.5V| 28.5V
float| 26.5V| 26.5V| 26.5V
Voltage ripple| max. 100mV RMS with resistive load @ full power
Short circuit current
(1/4 of I)| 3.75 A| 6.25 A| 6.25 A
Cable size (within 3 m)| 6.0 mm2| 10 mm2| 10 mm2
Charger fuse (external)| 20A| 32A| 32A
ENVIRONMENTAL
Ambient temperature| 20 to 40°C @ 100% output power, derated with 2,5% / °C
above 40°C
Cooling| Forced air, by means of a ventilator with variable speed
Humidity| Maximum 95%RV, non-condensing
MASTERBUS
MasterBus powering capability| Yes| Yes| v
MasterBus menu languages| English, Dutch, German, French, Spanish, Italian
ENCLOSURE TYPE| C1| C1| C1
Dimensions (hxwxd) mm| See figure 11| See figure 11| See figure 11
Protection degree| IP23| IP23| IP23
Weight| 3.3 kg| 3.3 kg| 3.5 kg
COMPLIANCE
Standards, approvals & listings| CE, ABYC A-31, RRR,RMRS| CE, ABYC A-31,
RRR,RMRS| CE, ABYC A-31, RRR, RMRS, DNVGL (40720266 only)
- Adjustable, see chapter 5.
Specifications are subject to change without prior notice.
8.2 Dimensions 8.3 Characteristics (230 V AC)
We welcome your feedback and suggestions!
Send feedback on this document to
info@mastervolt.com
Europe, Middle East & Africa
Technical Support
T: +31 (0) 20 34 22 100
E: ts.emea@OneASG.com
Location & Shipping
Navico Group EMEA
Snijdersbergweg 93
1105 AN Amsterdam
The Netherlands| Americas & Caribbean
Technical Support
T: +1 262 293 0600 / 800 307 6702
E: tech.mastervolt@OneASG.com
Location & Shipping
Navico Group US
N85 W12545 Westbrook Crossing
Menomonee Falls, WI 53051
United States| Asia Pacific
Technical Support
T: +64 9 415 7261
E: technical.apac@OneASG.com
Location & Shipping
Navico Group APAC
42 Apollo Drive
Rosedale, Auckland 0632
New Zealand
---|---|---
Document version: 10000001887/03 (December 23)
Copyright ©2023 Navico Group EMEA B.V.
All rights reserved.