MASTERVOLT MV62000550 AGM Battery 55Ah Battery
Observe these instructions and keep them located near the battery for future reference. Work on the battery should only
be carried out by qualified personnel.
Do not smoke or introduce sparks in the vicinity of the battery. Explosion and
fire hazards are present.
While working on batteries wear protective eye-glassing and clothing. Observe
accident protection rules.
Any acid splashes on the skin or in the eyes must be flushed with plenty of
water immediately. Then seek medical assistance. Spillages on clothing should
be
rinsed out with water.
Explosion and fire hazard. Do not short circuit, use insulated tools.
Electrolyte is strongly corrosive. Under normal conditions contact with electrolyte is
impossible. If the housing is damaged the electrolyte can be available.
Batteries are heavy. Ensure adequate mounting security and always use suitable
handling equipment for transportation.
Metal parts of the battery are always alive. Do not place tools or other items
on the battery. Do not wear any metallic items such as watches, bracelets, et
cetera.
General
Master volt AGM batteries are immediate ready for use.
Installation
- Prior to installation check battery for mechanical damages and firmly tightened terminals.
- Recommended torque for screw connections: 14.7 to 19.6 Nm / 130 to 170 InLbs (Model 55Ah: 11 to 14.7 Nm / 97 to 130 InLbs).
- Install in upright position.
- Keep >1cm />0.5 inch space between the batteries.
- Keep away from heat sources.
- Allowed operating temperature: –20 to 55ºC / –4 to 131ºF; Nominal operating temperature: 5 to 35ºC / 41 to 95ºF. Recommended at 25ºC/ 77ºF. The battery life is halved for every 10ºC of rise in temperature. Lower temperatures will reduce the available capacity
- Under overcharging conditions lead acid batteries can vent an explosive mixture of hydrogen gas. If contained, assure adequate ventilation.
- Clear the terminals before connection.
- During installation all loads and chargers must be switched off.
- For best possible connection, direct mounting of the cable lug to the battery post is recommended. Therefore the battery pole adapter should be removed first. See figure 6.
- Use properly sized and reliable cable lugs and battery terminals. Tighten all connections firmly.
- Connect the battery with correct polarity. The position of the battery poles may differ from previous installed batteries!
- Connect the minus cable last of all.
- Use protective battery terminal insulators.
- Batteries in series or parallel must be of the same brand, type, capacity and state of charge. Do not mix old and new batteries. See figure 1 to 5 if batteries must be connected in parallel or in series.
Charging
Use only chargers with IUoUo characteristic.
Voltage settings: float charge 13.80V @ 25ºC / 77ºF; absorption charge 14.25V
@ 25ºC / 77ºF (max 5 hrs). Temperature compensated charging is recommended
(–30mV/ºC or –17mV/ºF).
Maximum charge current: 30% of rated capacity @ C10. Incomplete charges may
damage the batteries. Therefore the batteries must be charged to the full 100%
regularly, at least every month.
Discharge
Avoid deep discharges. Regular discharges beyond 50% of the nominal capacity
are not recommended as they might shorten the lifetime of the battery.
Recharge the battery immediately after a discharge. Never discharge below the
final discharge voltage. The final discharge voltage is related to the
discharge current. See table “Final discharge voltage”.
Maintenance
Check batteries and connections on a regular base, at least every three
months. Defects such as loose or corroded connections must be corrected
immediately. Keep battery in charged condition. Elevated environmental
temperatures increase the self-discharge rate of the batteries. See “Battery
storage” Batteries should be recharged when the open circuit voltage drops
below 12.3 Volt. Keep the battery dry and clean. Use only a wet soft cloth to
clean the battery. Never use any additives, acids and/or scourers.
Do not open the battery. Never add acid or distilled water.
Disposal of batteries
Spent batteries are harmful to health and the environment. Therefore batteries
may not be mixed with domestic or industrial waste but must be collected and
recycled separately. Contact your supplier for recollection and recycling of
batteries or contact an authorized waste management company.
SERIAL CONNECTION
- 24V /90Ah
- 48V /90Ah
PARALLEL CONNECTION
- 12V/180Ah
- 12V/360Ah
Maximum number of batteries: 4
Connection of the plus and minus wiring must be crosswise.
SERIAL-PARALLEL CONNECTION
Serial-parallel connection
Maximum number of batteries: 4
- 24V /180Ah
Connection of the plus and minus wiring must be crosswise.
BATTERY POST CONNECTION
-
Recommended connection
-
Option
RATED CAPACITY
Rated capacity| @25ºC/77ºF| | | | | | Capacity affected by
temperature:|
---|---|---|---|---|---|---|---|---
Model| C20| C10| C5| C3| C1| |
AGM-55Ah| 55Ah| 51Ah| 44Ah| 39.9Ah| 30.6Ah| | Temperature:|
Capacity
AGM-70Ah| 70.6Ah| 65Ah| 56Ah| 50.7Ah| 39Ah| | 0ºC (32ºF)| 86%
AGM-90Ah| 90Ah| 85Ah| 72.5Ah| 66.4Ah| 51Ah| | 20ºC (68ºF)| 97%
AGM-130Ah| 128Ah| 120Ah| 102Ah| 92.4Ah| 70Ah| | 25ºC (77ºF)| 100%
AGM-160Ah| 160Ah| 150Ah| 134Ah| 121.8Ah| 92Ah| | 40ºC (104ºF)| 103%
AGM-225Ah| 226Ah| 210Ah| 180.5Ah| 163.8Ah| 126Ah| | |
AGM-270Ah| 270Ah| 255Ah| 229Ah| 214Ah| 176Ah| | |
FINAL DISCHARGE VOLTAGE
Battery model Discharge current
AGM-55Ah
| < 11A| 11 – 23A| 23 – 55A| > 55A
---|---|---|---|---
AGM-70Ah| < 13A| 13 – 32A| 32 – 65A|
65A
AGM-90Ah
| < 17A| 17 – 42A| 42 – 85A| > 85A
AGM-130Ah| < 24A| 24 – 60A| 60 – 120A|
120A
AGM-160Ah
| < 30A| 30 – 75A| 75 – 150A| > 150A
AGM-225Ah| < 42A| 42 – 105A| 105 – 210A|
210A
AGM-270Ah
| < 51A| 51 – 128A| 128 – 255A|
255A
Final discharge voltage
| **10.8V| ****10.5V| ****10.2V**|
**9.6V**
| | | |
MAXIMUM DISCHARGE CURRENT
Model:| AGM| AGM| AGM| AGM| AGM| AGM|
AGM
---|---|---|---|---|---|---|---
| 55Ah| 70Ah| 90Ah| 130Ah| 160Ah| 225Ah|
270Ah
Continual discharge:| 50A| 65A| 85A| 120A| 150A| 210A| 255A
Discharge time t ≤ 2min:| 150A| 195A| 255A| 360A| 450A| 630A| 765A
Discharge time t ≤ 10sec:| 300A| 410A| 510A| 720A| 900A| 1260A| 1530A
CONSTANT CURRENT DISCHARGE (AMPS @25ºC/77ºF)
Time (minutes)| 10| 15| 20| 30| 45| 60|
120| 180| 240| 300| 360| 480| 600| 1200
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Final voltage (V)| 7.8| 7.8| 7.8| 9.6| 9.6|
10.0| 10.2| 10.5| 10.5| 10.5| 10.5| 10.8|
10.8| 10.8
AGM-55Ah| 132.5| 99.7| 82.2| 55.0| 43.7| 31.2| 18.0| 13.4| 10.7| 8.8|
7.8| 6.1| 5.1| 2.8
AGM-70Ah| 162.5| 123.5| 97.5| 78.8| 52.0| 39.0| 22.8| 16.9| 13.0| 11.2|
9.9| 7.7| 6.5| 3.5
AGM-90Ah| 213.0| 162.0| 127.5| 98.0| 68.0| 51.0| 30.0| 21.8| 17.1| 14.5|
12.9| 10.1| 8.5| 4.8
AGM-130Ah| 300.0| 228.0| 180.0| 137.5| 95.0| 70.0| 40.3| 30.8| 19.2|
20.4| 18.1| 14.3| 12.0| 6.4
AGM-160Ah| 390.0| 318.6| 245.5| 179.0| 122.4| 92.0| 54.2| 40.6| 30.8|
26.8| 23.5| 18.2| 15.0| 8.0
AGM-225Ah| | | 315.0| 241.5| 168.0| 126.0| 73.5| 54.6| 42.0| 36.1| 31.9|
25.0| 21.0| 11.3
AGM-270Ah| | | | 318.4| 222.9| 175.8| 95.5| 71.3| 54.8| 45.8| 39.2|
30.6| 25.5| 13.5
CONSTANT POWER DISCHARGE (WATT /CELL @25ºC/77ºF )
Time (minutes)| 10| 15| 20| 30| 45| 60|
120| 180| 240| 300| 360| 480| 600| 1200
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Final voltage (V)| 7.8| 7.8| 7.8| 9.6| 9.6|
10.0| 10.2| 10.5| 10.5| 10.5| 10.5| 10.8|
10.8| 10.8
AGM-55Ah| 225.4| 174.5| 147.4| 100.5| 83.2| 59.0| 34.3| 25.7| 20.7|
17.1| 15.0| 12.9| 10.2| 5.5
AGM-70Ah| 305.5| 234.0| 191.1| 141.1| 103.4| 77.2| 45.2| 33.7| 25.9|
22.3| 19.8| 15.5| 13.0| 7.0
AGM-90Ah| 400.0| 306.0| 250.0| 184.5| 135.2| 101.6| 59.0| 42.5| 34.0|
29.0| 25.8| 20.2| 17.0| 9.0
AGM-130Ah| 564.0| 432.0| 353.0| 259.5| 188.5| 139.4| 80.5| 61.5| 46.3|
40.7| 36.1| 28.6| 24.0| 12.8
AGM-160Ah| 730.5| 600.6| 471.5| 337.5| 243.3| 182.0| 106.8| 80.8| 61.2|
53.2| 46.8| 36.4| 29.9| 16.0
AGM-225Ah| | | 588.0| 434.0| 318.0| 237.7| 136.5| 101.6| 80.1| 69.9|
62.0| 48.0| 42.0| 21.4
AGM-270Ah| | | | 600.8| 443.0| 348.0| 189.9| 142.1| 109.2| 91.4| 78.5|
60.9| 50.9| 27.0
BATTERY STORAGE
The rate of self discharge is approximately 3% per month @ 20ºC. Therefore
batteries need supplementary charge according to the table below to keep its
capacity.
DIMENSIONS
Dimensions in mm. See
www.mastervolt.com/batteries for detailed
drawings
Battery casing material: ABS
SPECIFICATIONS MASTERVOLT AGM BATTERIES
Model | AGM-55Ah | AGM-70Ah | AGM-90Ah | AGM-130Ah |
---|---|---|---|---|
Part number | 62000550 | 62000700 | 62000900 | 62001300 |
Nominal voltage | 12V | 12V | 12V | 12V |
Nominal capacity (C20) | 55Ah | 70Ah | 90Ah | 130Ah |
Reserve capacity* | 80 min | 113 min | 179 min | 240 min |
Number of cells per battery | 6 | 6 | 6 | 6 |
Maximum charge current: | 15.3A | 19.5A | 25.5A | 36A |
Approximate weight: | 17.0 kg / 37 Lbs | 21.0 kg / 46 Lbs | 28.0 kg / 62 Lbs |
37.6kg / 83 Lbs
BCI group number| 24| 27| 31| – –
Terminal: threaded insert stud| M6| M8| M8| M8
Short circuit current acc. to IEC60896-2| 1500A| 1625A| 2000A| 2700A
CCA to DIN| 250 A| 290 A| 360 A| 590 A
CCA to SAE| 400 A| 460 A| 570 A| 940 A
Model| AGM-160Ah| AGM-225Ah| AGM-270Ah
---|---|---|---
Part number| 62001600| 62002250| 62002700
Nominal voltage| 12V| 12V| 12V
Nominal capacity (C20)| 160Ah| 225Ah| 270Ah
Reserve capacity*| 351 min| 474 min| 600 min
Number of cells per battery| 6| 6| 6
Maximum charge current:| 45A| 63A| 76.5A
Approximate weight:| 42.3 kg / 93 Lbs| 62.5 kg / 138 Lbs| 73.0 kg / 161 Lbs
BCI group number| 4D| 8D| Super 8D
Terminal: threaded insert stud| M8| M8| M8
Short circuit current acc. to IEC60896-2| 3500A| 3650A| 4400A
CCA to DIN| 550 A| 680 A| 750 A
CCA to SAE| 870 A| 1080 A| 1200 A
| | |
General| | |
Operating temperature| –20 to 55ºC / –4 to 131ºF;| |