Danfoss 175G9002 VLT MCD DeviceNet Module Instruction Manual
- June 1, 2024
- Danfoss
Table of Contents
INSTALLATION INSTRUCTIONS:
MCD DEVICENET MODULE
Order Code: 175G9002
Important User Information
Observe all necessary safety precautions when controlling the soft starter
remotely. Alert personnel that machinery may start without warning.
It is the installer’s responsibility to follow all instructions in this manual
and to follow correct electrical practice.
Installation
CAUTION
Remove mains and control voltage from the soft starter before attaching or
removing accessories. Failure to do so may damage the equipment.
Install the Device Net Module using the following procedure:
- Remove control power and mains supply from the soft starter.
- Attach the module to the soft starter as illustrated.
- Set the Device Net Module Node Address (MAC ID) and Data Rate.
- Apply control power to the soft starter.
- Insert the network connector into the module and power up the Device Net network.
2.1. Physical Installation
- Fully pull out the top and bottom retaining clips on the module.
- Line up the module with the comms port slot.
- Push in the top and bottom retaining clips to secure the module to the starter.
Remove the module using the following procedure:
- Take the module off-line.
- Remove the Device Net connector.
- Remove control power and mains supply from the soft starter.
- Fully pull out the top and bottom retaining clips on the module.
- Pull the module away from the soft starter.
CAUTION
Network designs must decrease the maximum allowable cumulative dropline length
by 400 mm for every module installed on the network. Failure to do so may
result in network communication errors and decreased reliability.
Example : ODVA specifies a maximum cumulative dropline length of 156 m on
a network operating at 125 kb/s. If six modules were installed on this
network, the total cumulative dropline length would need to be decreased to
153.6 m.
Configuration
The Device Net Module is a Group 2 slave device, using a predefined
master/slave connection set.
I/O data is produced and consumed using polled I/O messaging.
The soft starter must be added to the Device Net manager project using the EDS
file and configuration/management software tool. This file is available from
www.danfoss.com/drives. In order to operate
successfully, the correct EDS file must be used. An on-screen graphics bitmap
file (device.bmp) is also available.
Adjustment
The factory default settings for the rotary adjustment switches are:
Changes to the rotary switch settings take effect when the Device Net network
is next powered up.
N.B.!:
The Data Rate and Node Address (MAC ID) must be set locally on the module.
These cannot be set using DeviceNet management software.
When the Data Rate and MSD Node Address (MAC ID) rotary switches are set on
PGM position, the module uses the previously used valid on-line Data Rate and
Node Address (MAC ID).
Connection
MCD 200: For the MCD Device Net Module to accept serial commands, a link must
be fitted across terminals A1-N2 on the soft starter.
In order for the MCD 500 to accept commands from the serial network, the soft
starter must be in Auto On mode and links must be fitted to terminals 17, 18
and 25, 18.
In Hand On mode, the starter will not accept commands from the serial network
but the starter’s status can still be monitored.
1| MCD 200| 1| MCD 500 (Auto On mode)
17, 18: Stop
25, 18: Reset
---|---|---|---
2| MCD Device Net Module| 2| MCD Device Net Module
3| Standard connection onto Device Net network| 3| Standard connection onto
Device Net network
N.B.!:
If MCD 500 parameter 3-2 Comms in Remote is set to Disable Comms in Remote,
the starter will not accept start or stop commands from the serial network
(the starter will still accept reset commands and allow status monitoring).
Module and Network LEDs
The Module LED indicates the condition of the power supply and module
operation.
The Network LED indicates status of the communication link between the Device
Net Module and the network Master.
LED | State | Description |
---|
(1)(Module)
| Off| Network power off
Green| Normal operation
Red| Unrecoverable fault
Red/Green flashing| Self Test mode
(2)(Network)
| Off| Duplicate MAC ID test has not been completed
Green flashing| Online but no connection with Master
Green| Online and allocated to a Master
Red flashing| One or more timed out I/O connections
Red| Failed communication between module and Master
Red/Green flashing| Communication faulted and received an Identity
communication faulted request
N.B.!:
When a communications failure occurs, the soft starter may trip if the
Communication Timeout parameter for the network is set greater than zero. When
communication is restored, the soft starter must be reset.
Device Net Polled I/O Structure
Once the EDS file has been loaded, the Device Net Module must be added to the scanner list with parameters shown in the following table:
Parameter | Value |
---|---|
I/O connection type | Polled |
Poll receive size | 14 bytes |
Poll transmit size | 2 bytes |
Once the soft starter, module and Master have been set up, configured and
powered up, the Master will transmit 2 bytes of data to the module and receive
14 bytes of data from the module.
Master > Slave polled I/O output data is as follows:
Byte | Bit | Function |
---|---|---|
0 | 0 | 0 = Stop command |
1 = Start command
1| 0 = Enable Start or Stop command
1 = Quick Stop (i.e. coast to stop) and disable Start command
2| 0 = Enable Start or Stop command
1 = Reset command and disable Start command
3 to 7| Reserved
1| 0 to 1| 0 = Use soft starter remote input to select motor set 1 = Use
primary motor set when starting 1
2 = Use secondary motor set when starting 1
3 = Reserved
2 to 7| Reserved
1Ensure that the programmable input is not set to Motor Set Select before
using this function.
Slave > Master polled I/O input data is as follows:
Byte | Bit | Function | Value |
---|---|---|---|
0 | 0 | Trip | 1 = Tripped |
1 | Warning | 1 = Warning | |
2 | Running | 0 = Unknown, not ready, ready to start or tripped 1 = Starting, |
running, stopping or jogging
3| Reserved|
4| Ready| 0 = Start or stop command not acceptable 1 = Start or stop command
acceptable
5| Control from Net| 1 = Always except in Program mode
6| Local/Remote| 0 = Local control
1 = Remote control
7| At reference| 1 = Running (full voltage at the motor)
1| 0 to 7| Status| 0 = Unknown (menu open)
2 = Starter not ready (restart delay, thermal delay or run simulation)
3 = Ready to start (including warning state) 4 = Starting or running
5 = Soft stopping 7 = Trip
8 = Jog forward
9 = Jog reverse
2| 0 to 7| Trip/Warning code| See trip code table.
3| 0| Initialised| 1 = Phase sequence bit is valid (bit 1) after 1st start
1| Phase sequence| 1 = Positive phase sequence detected
2 to 7| Reserved|
4 1| 0 to 7| Motor current (low byte)| Current (A)
5 1| 0 to 7| Motor current (high byte)
6| 0 to 7| Current %FLC (low byte)| Current as a percentage of soft starter
FLC setting (%)
7| 0 to 7| Current %FLC (high byte)
8| 0 to 7| % Motor 1 temperature| Motor 1 thermal model
9| 0 to 7| % Motor 2 temperature| Motor 2 thermal model
10| 0 to 7| % Power factor| Percentage power factor (100 = power factor of 1)
11| 0 to 7| Power (low byte)| Power low byte, scaled by power scale
12| 0 to 3| Power (high nibble)| Power high nibble, scaled by power scale
4 to 5| Power scale| 0 = Multiply power by 10 to get W 1 = Multiply power by
100 to get W 2 = Power (kW)
3 = Multiply power by 10 to get kW
6 to 7| Reserved|
13| 0 to 3| Digital Input state| 0 = Start (0 = open, 1 = closed)
1 = Stop
2 = Reset 3 = Input A
4 to 7| Reserved|
1For models MCD5-0428C and smaller this value will be 10 times greater than the value displayed on the LCP.
7.1.1. Trip Codes
Code | Trip Type | MCD 201 | MCD 202 | MCD 500 |
---|---|---|---|---|
0 | No trip | **** | **** | **** |
11 | Input A trip | **** | ||
20 | Motor overload (thermal model) | **** | **** | |
21 | Heatsink overtemperature | **** | ||
23 | L1 phase loss | **** | ||
24 | L2 phase loss | **** | ||
25 | L3 phase loss | **** | ||
26 | Current imbalance | **** | **** | |
28 | Instantaneous overcurrent | **** | ||
29 | Undercurrent | **** | ||
50 | Power loss/Power circuit | **** | **** | **** |
54 | Phase sequence | **** | **** | |
55 | Frequency (Mains supply) | **** | **** | **** |
60 | Unsupported option (function not available in inside delta) | **** | ||
61 | FLC too high (FLC out of range) | **** | ||
62 | Parameter out of Range | **** | ||
70 | Miscellaneous | **** | ||
75 | Motor thermistor | **** | **** | |
101 | Excess start time | **** | **** | |
102 | Motor connection | **** | ||
104 | Internal fault x (where x is the fault code detailed in the table | |||
below). | **** | |||
113 | Starter communication (between module and soft starter) | **** | **** |
114| Network communication (between module and network)| | |
115| L1-T1 shorted| | |
116| L2-T2 shorted| | |
117| L3-T3 shorted| | |
119| Time-overcurrent (Bypass overload)| | |
121| Battery/clock| | |
122| Thermistor circuit| | |
- For MCD 500, time-overcurrent protection is only available on internally bypassed models.
The table below details the internal fault code associated with trip code 104.
Internal fault | Message displayed on the LCP |
---|---|
70 ~ 72 | Current Read Err Lx |
73 | Power On in Simulation mode |
74 ~ 76 | Motor connection Tx |
77 ~ 79 | Firing fail SCRx |
80 ~ 82 | VZC Fail Px |
83 | Low Control Volts |
84 ~ 98 | Internal fault X |
Contact your local supplier with the fault code (X).
Parameter Object
The Device Net Module supports parameter objects through explicit messaging. Soft starter parameters can be uploaded (written) and downloaded (read) using Device Net management software. When the Device Net Module is powered up, it automatically obtains parameter information from the soft starter.
Detail | Value (Hex) | Comment |
---|---|---|
Class | 0F | Parameter object address |
Instance | 1 ~ xxx | xxx = maximum soft starter parameter number |
Attribute ID | 01 | Always 0x01 |
Get Service | 0E | Read single soft starter parameter value |
Set Service | 10 | Write single soft starter parameter value |
N.B.!:
Only available on MCD 500 soft starters. For parameter details, see the soft
starter User Manual.
Specifications
Enclosure
Dimensions ………………… 40 mm (W) x 166 mm (H) x 90 mm (D)
Weight ……………………………………. 250 g
Protection …………………….. IP20
Mounting
Spring-action plastic mounting clips (x 2)
Connections
Soft starter …………………………. 6-way pin assembly
Network ………………………………. 5-way male and unpluggable female connector (supplied)
Maximum cable size ………………………………………. 2.5 mm2
Contacts …………………………………….. Gold flash
Settings
Node address (MAC ID)
Setting …………………………………… Rotary switches
Range ……………….. 0 to 63 (63, factory default)
Data rate
Setting ………………………… Rotary switch
Options ……………………………………… 125 kB, 250 kB, 500 kB (125 kB, factory default)
Power
Consumption
steady state ……………….. 19 mA at 25 VDC ……………… 31 mA at 11 VDC in-rush (at 24
VDC) ……………… 1.8 A maximum for 2 ms
Galvanically isolated
Certification
CE …………………………. IEC 60947-4-2
MG17HA02 – VLT® is a registered
Danfoss trademark
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>