ANKO A302 VSP And FSP Peristaltic Metering Pumps User Manual
- June 1, 2024
- Anko
Table of Contents
ANKO A302 VSP And FSP Peristaltic Metering Pumps
Product Information
Specifications
- Pump Head Speed Adjustment (Variable Speed Models): 5% to 100%
- Run Time Adjustment (Timer Models): 0% to 100%
- Motor Type: Brushless DC
- Duty Cycle: Continuous
- Tubing Accepted: Anko Premium Class 1/4, 3/16 & 1/8
- Operating Voltage: 100-240V, 50/60Hz
- Plug Type: NEMA 5-15P
- Max Working Pressure: 25 psi
- Compliance: UL778; FCC Part 15b Class A
Product Usage Instructions
Installation
Follow the installation guidelines provided in the manual. Ensure the pump
is connected to a grounded receptacle protected by a ground-fault circuit
interrupter (GFCI).
Operation
- Controls: Confirm the rocker switch is in the Off position before connecting to power.
- Adjusting Flow Output: Follow the instructions to adjust the flow output based on the model type.
- Remote Operation: Refer to the manual for instructions on remote operation if applicable.
Maintenance
- Routine Inspection: Periodically inspect tubing for tears, cracks, cuts, or abrasions.
- Tube Replacement: Use only factory-approved tubing from the designated class to prevent performance issues or pump damage.
- Pumphead Maintenance: Refer to the manual for detailed instructions on maintaining the pumphead.
- Fuse Replacement: If needed, follow the manual’s guidance for replacing fuses.
FAQ
-
Q: Can I use non-approved tubing with the pump?
A: No, using incorrect tubing can affect performance and damage the pump. Always use factory-approved tubing. -
Q: How should I adjust the flow output of the pump?
A: Refer to section 4.2 of the manual for instructions on adjusting the flow output based on your pump model.
SAFETY
- WARNING: Failure to follow the instructions in this manual may result in serious injury or death.
- WARNING: Risk of electric shock. This pump has been rated for indoor use only.
- WARNING: Risk of electric shock. Connect only to a grounding-type receptacle protected by a ground-fault circuit interrupter (GFCI). Contact a qualified electrician if you cannot verify that the receptacle is protected by a GFCI and that your installation meets local electrical codes.
- WARNING: Risk of electrical shock. Always make sure the voltage on the pump data plate matches the installation voltage before plugging the pump into a wall outlet or hooking it up to an electrical supply.
- WARNING: Risk of electrical shock. Always disconnect the power to the pump before conducting any maintenance or repairs.
- WARNING: Risk of chemical exposure. Always wear protective clothing, including gloves and safety eye protection, when working on or near this pump.
- WARNING: Risk of chemical exposure. Always depressurize the system and drain chemicals prior to installation or maintenance.
- WARNING: Risk of fire or explosion. Do not pump flammable liquids.
- WARNING: Risk of injury. Severe pinching of fingers can occur while installing and removing the tubing. Caution must be used to keep fingers away from rotating parts.
SPECIFICATIONS
General Specifications
Pump Head | A302 |
---|---|
Speed Adjustment (Variable Speed Models) | 5% to 100% |
Run Time Adjustment (Timer Models) | 0% to 100% |
Motor Type | Brushless DC |
Duty Cycle | Continuous |
Tubing Accepted | Anko Premium Class |
Tubing Bores Accepted | 1/4″, 3/16” & 1/8” |
Operating Voltage | 100-240 50/60Hz |
Plug Type | NEMA 5-15P |
Max Working Pressure | 25 psi |
Compliance | UL778; FCC Part 15b Class A |
Materials of Construction
Enclosure | Polypropylene |
---|---|
Pump Head | Polycarbonate |
Rollers | MoS2 Filled Nylon |
Rotor | CRS – Zinc Plated |
Dimensions
INSTALLATION
- When facing the pump, the roller assembly spins in a clockwise direction. The inlet (suction) side is located on the left side of the pumphead, and the outlet (discharge) is located on the right.
- Mount the pump in a level, dry location close to the injection point. To minimize backpressure on the system, keep the discharge tubing as short as possible.
- The recommended location is above the height of the solution tank. Mounting the pump lower than the solution tank will gravity feed the solution and create a “flooded suction” installation. In this scenario, a shut-off valve or other device must be installed to stop the solution flow to the pump during pump servicing.
- In installations involving pressure, a check valve should be used at the point of injection to prevent potential backflow.
- DO NOT mount pump directly over an open solution tank as chemical fumes may damage the pump.
- Voltage and frequency of power supply must be the same as shown on unit specification label.
- AC power must be connected to a Grounded Power Outlet (Ground Fault Circuit Interrupter GFCI). DO NOT operate pump on an un-grounded circuit.
- Ambient air temperature should not exceed 104° F (40° C) and adequate air flow should be provided.
OPERATION
- WARNING: Tube failure may result in fluid being sprayed from pump. Use appropriate measures to protect operator and equipment. Tubing should be inspected periodically for tears, cracks, cuts, or abrasions.
- WARNING! Use only factory approved tubing from the designated tubing class. Incorrect tubing can adversely affect performance or damage the pump.
Controls
All pumps are equipped with a rocker switch mounted on the front of the
pump. Always confirm the switch is in the designated Off position before
plugging the pump into any power receptacle.
- 2-Way Rocker – For units equipped with a two-way rocker, the up position is ON, and the down position is OFF.
- 3-Way Rocker – For units equipped with a 3-way rocker, up is ON, center is OFF, and the down position is either EXTERNAL or RUN mode, depending on the pump model.
- Potentiometer – Variable speed models are equipped with either a single-turn or 10-turn potentiometer to regulate pump speed. Timer models (Pulse and Cycle) are equipped with a 10-turn potentiometer for control of ON time setting.
- Momentary Button – Pulse timer models are equipped with a momentary button to test the ON time setting for calibration purposes.
Adjusting Flow Output
- Fixed Speed Models – There is no flow output adjustment.
- Variable Speed Models – Flow output is controlled by motor speed utilizing the potentiometer. Rates are adjustable from approximately 5% to 100%. If equipped with a 4-20mA control option, pump speed will vary as the dedicated input signal changes amplitude. Please refer to Remote Operation below for more details on 4-20mA operation.
- Cycle Timer Models – Cycle time is defined as the sum of the ON TIME plus OFF TIME. ON TIME is set by the potentiometer and can be incremented up to the model’s maximum total cycle time. When the 3-way rocker switch is in the down (RUN) position, the pump will dispense for the selected ON TIME, remain off for the balance of the total cycle time, and then repeat the on cycle indefinitely until the pump is powered off or switched out of the RUN mode.
- Pulse Timer Models – ON TIME is set by the potentiometer up to the model’s maximum dispense time. When the 3-way rocker switch is in the down (RUN) position, the pump will dispense for the selected ON TIME whenever a dry contact pulse signal is received, or the momentary button is pressed.
Remote Operation
-
Remote Start/Stop – For pump models equipped with remote start/stop, this feature operates by receiving a dry contact signal and is intended to be connected to a dry contact switch. The input has no polarity. No voltage is permitted on the input signal. The pump will activate and run while the switch is closed and deactivate and stop when the switch opens.
To activate this feature, install the pair of wires from the dry contact switch closure device into the terminal block (Figure 1). Set the 3-way rocker in the down position to place the pump in EXTERNAL mode. The pump will now operate only when receiving a closed contact signal. To return to local control, move the rocker switch to the up, Internal mode, position. -
4-20mA Control – For models equipped with a 4-20mA feature, the pump’s output will vary according to the level of an incoming 4-20mA analog signal. The pump’s maximum output to the signal is scalable between 20% and 100%, as determined by the percentage setting on the potentiometer.
- For standard signal models, the minimum output is approximately 5.0% at 4.8mA and increases in 1.0% increments for every .16mA until 100% of the scaled output (based upon the potentiometer setting) is reached at 20.0mA (Figure 2).
- For inverted signal models, the maximum output (as established by the potentiometer setting) is reached at 4.8mA and decreases, as above, until reaching zero output at 20.0mA (Figure 3).
NOTE: Loop voltage for all models may not exceed 36VDC.
To establish and operate the analog control feature:
- Install the two-wire lead (right side of terminal is positive; left is negative) from the 4-20mA source into the terminal block (Figure 4).
- Set the potentiometer to the desired scaling percentage. To operate without scaling, set the potentiometer to 100%.
- Set the 3-way rocker in the down position to enter EXTERNAL mode. The pump will now operate only when receiving the analog signal.
- While in EXTERNAL mode, the pump can be turned off by setting the potentiometer to 0%.
To return the pump manual control, place the rocker switch to the up, ON position.
MAINTENANCE
Routine Inspection
The pump should be inspected on a weekly basis. Inspect for any signs of
leaking and early indications of potential tube failure (e.g., swelling,
cracking or discoloration). Replace any worn or damaged components
immediately. Always check the chemical compatibility and pressure rating of
the tubing prior to use.
Replacing the Tubing
Pump tubing must be replaced on a regular basis. While replacement within
500 hours of run time is recommended, tube longevity is ultimately determined
by many factors, including tube formulation, the chemical composition of the
fluid being pumped, system back pressure, pump speed, temperature, and more.
Use only factory designated tubing. Incorrect tubing can adversely affect
performance or damage the pump.
- WARNING! Tubing connections may be under pressure. Always depressurize the system prior to connecting or disconnecting the pump.
- WARNING! Tubing may contain chemicals. Wear protective clothing, gloves and safety glasses when working with or near the pump.
- WARNING! Severe pinching of fingers can occur while installing and removing the tubing. Caution must be used to keep fingers away from rotating parts.
Tubing Removal
When facing the pump, the roller assembly spins in a clockwise direction. The
inlet (suction) side is located on the left side of the pumphead, and the
outlet (discharge) is located on the right.
- Disconnect any suction and discharge tubes from the pump tube.
- Remove the pumphead cover.
- With the pump running, pull the inlet (left) side of the tubing out of the pumphead channel. Carefully guide the tube clockwise away from the rollers and pull the tube out of the pumphead.
Tubing Installation
Start with a section of tubing at least 9” in length. Once installed, this
length will result in approximately 1 1/2” extending below both sides of the
pumphead for fittings and attachments.
- With the pump running, insert tube into the channel of the inlet (suction) of pumphead (Figure 5).
- Carefully guide the tube into pumphead and through the channel of the outlet (discharge) side of the pump head and then stop the pump (Figure 6).
- Reinstall the pumphead cover (Figure 7).
- Attach retention clip on the inlet (left) side of the tube just below the base of the pumphead, to prevent tube migration during operation (Figure 8).
Pumphead Maintenance
- Remove tubing per the Tubing Removal procedure.
- Disconnect power to the pump.
- Remove the pumphead cover.
- Slide roller assembly off motor shaft. For two roller configurations, first open the spring clip to release it from the motor shaft (Figure 9).
- Remove roller assembly by sliding it off the motor shaft.
Once disassembled, remove any particles or debris from the pumphead housing and roller assembly. Inspect the pumphead for cracks or other damage. Ensure rollers turn freely. Be sure all cleaning solvents are removed prior to reassembly and tube replacement.
Fuse Replacement
- Disconnect power to pump.
- Slide out the fuse tray from the IEC socket (Figure 10).
- Replace with one of identical size & Amperage rating.
- Slide fuse tray back in to lock.
PARTS & ACCESSORIES
Please visit www.ankoproducts.com for factory- authorized tubing, pump head components and pump accessories.
TROUBLESHOOTING
PROBLEM | POSSIBLE CAUSE | SOLUTION |
---|---|---|
Fluid Leaking | Pump tube worn | Replace tubing |
Excessive back pressure | Ensure system pressure does not exceed tube pressure |
rating
Tube connections are not tight| Ensure tubing connections are properly
connected
Tube Life is Shortened| Non-compatible tubing used| Use specified tubing
Seized rollers caused abrasion on tube| Clean roller assembly or replace
Fluid is not compatible with tubing| Use chemically compatible tubing
Pump will not start| Blown fuse| Replace Fuse
The outlet is not powered| Verify that the unit is plugged into a functioning
outlet
The IEC plug has a loose connection| Verify the power cord is firmly attached
to IEC receptacle
Gearbox assembly is worn| Replace unit
Unit is ON but pump will not turn| Non-compatible tubing used| Use specified
tubing
Gearbox assembly worn| Replace unit
Pump runs but does not meet rated flow| Tubing is worn| Replace tubing
Non-compatible tubing used| Use specified tubing
Fluid viscosity is too high| Lower viscosity, use larger bore tubing
Pump height is too high| Reduce pumping height
LIMITED WARRANTY
Anko Products, Inc, (“ANKO”) warrants, subject to the conditions and exceptions herein, to replace or repair free of charge, any of its products which fail within three years of the date of manufacture. Any failure must be a result of a defect in material workmanship and not because of normal operation as described in the product user manual. This warranty is limited to repairing or replacing any device or part of any device which is returned, transportation prepaid, to the factory and is proven to be defective upon our examination. The warranty shall not apply to repairs required for normal wear and tear, lack of reasonable and proper maintenance, chemical attack, electrical surge, or products that have been misused in our sole judgment. All consumable items such as tubing, and pump head rollers are excluded.
ANKO disclaims all liability for any loss, damage or expense directly or indirectly related to or arising from the use of its products, including damage to other products, machinery, or property. ANKO shall not be liable for any consequential damages including, without limitation, loss of profits, loss of product or loss of production. This warranty does not obligate ANKO to bear any costs of removal, installation, transportation, or other charges which may arise in connection with a warranty claim.
ANKO makes no warranties, either express or implied, other than those stated above. No representative has authority to change or modify this warranty in any respect. Jurisdiction and venue for enforcement of this warranty may be brought only in the State of Florida. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
RETURN AND REPAIR
To return merchandise call 800-446-2656 for a Return Material Authorization (“RMA”), then, if applicable, Buyer may return the defective Products to ANKO with all costs prepaid by Buyer. ANKO will incur shipping costs for warranty products shipped from our factory. All replaced parts shall become the property of ANKO. No repair or replacement will extend the original warranty period.
FOR YOUR RECORDS:
- Model ____
- Date of Installation __
Anko Products, Inc.
6012 33rd St. East, Bradenton, Florida, USA 34203
Phone: 941-749-1960 Fax:
941-748-2307
URL: www.ankoproducts.com