FibroPool FH285-i 85000 BTU Full Inverter Heat Pump Instruction Manual Product Information
- May 15, 2024
- FIBROPOOL
Table of Contents
FH285-i 85000 BTU Full Inverter Heat Pump
“`html
Product Information
Specifications
-
Model No.: FH235-I, FH285-I
-
Heating Capacity (kW): FH235-I (7.2~1.7),
FH285-I (21~4.8) -
Power Input (kW): FH235-I (1.06~0.11), FH285-I
(3.09~0.30) -
COP: 15.8~6.8 for both models
Product Usage Instructions
Safety Information
Operating heat pumps at near-freezing temperatures risks damage
to the heat exchanger. Heat pumps must be empty of water at
freezing temperatures. Refer to the winterization guidelines for
more details.
Installation Instructions
Installation Diagram
*The installation diagram provided may not match your exact
setup. Contact your pool technician or Fibropool technical support
for assistance.
Installation Clearance
Proper clearance is essential to allow sufficient airflow and
access for maintenance and repairs.
Additional By-pass Kits
A bypass is recommended for all installations and required for
pumps larger than 1HP.
Heat Pump Unit Size (mm)
FH235-I Size: [specific dimensions]
FH285-I Size: [specific dimensions]
Heat Pump Exploded View
[Exploded view diagram showing various parts of the heat pump
unit]
Electrical Connection
Suggested power cable specification: FH235-I – 316 AWG, FH285-I
– 314 AWG. Terminal cable max. 12 AWG.
FAQ (Frequently Asked Questions)
Q: Can I install auxiliary electric heaters in the system?
A: It is not recommended to install auxiliary electric heaters
in the system. If absolutely necessary, auxiliary heaters must be
installed and operated by qualified technicians.
“`
WWW.FIBROPOOL.COM
WARNING!
Risk of electric shock! – A faulty electrical installation or excessively high
voltage can lead to electric shock. – Installation of heat pumps should only
be performed by an authorized technician. – Always disconnect the power supply
before opening the heat pump for maintenance or repairs. – Do not connect the
heat pump if the incoming voltage does not match the required voltage on the
unit’s information plate. – Do not operate the heat pump if there is visible
damage to the incoming wiring. – Repairs should only be performed by a
qualified technician unless otherwise instructed. Liability and warranty
claims are excluded in the event of improper repairs. – Keep children away
from the heat pump. – Ensure that the heat pump’s wiring is properly grounded
or bonded before operating.
ATTENTION!
– The manufacturer is not responsible for damage caused by people, foreign
objects, or inappropriate installation against these guidelines. – Always
provide proper ventilation and install away from any fire risks. – Do not
disconnect or attempt repairs on any lines containing refrigerant. Refrigerant
repairs should not be performed in any confined space. – It is vital to follow
proper winterization procedures when the risk of hard freeze approaches, or
the titanium heat exchanger risks being cracked or damaged. Such damage is not
covered under the warranty and repairs will be the owner’s responsibility.
Table of Contents
I. Included parts and accessories II. Safety Information III. Installation of
the unit IV. Technical Specifications V. Electrical Wiring VI. Operating
Instructions VII. Initial Operation VIII. Operation and maintenance IX. Error
codes & Solutions X. WiFi-Function XI. Winterization XII. Warranty Information
I. Included Parts and Accessories
Each unit includes the following accessories:
No.
Name
Qty.
Use
1 Instruction Manual
1 PC Safety and installation manual (this document)
2 Drain-hose
1 PC Used to direct condensation away from the unit
3 Drain-hose adapter
1 PC Connects the unit to the drain hose
4 Rubber shock absorber
4 PCS Limits friction with installation location
5 Heat pump unit
1 SET Heats and cools water pumped through
6 Unions
2 SET Connects the heat pump to 1.5″ PVC
The heat pump requires the following components:
No.
Name
1 Pool pump
2 Filter system
3 Plumbing
Qty.
use
1 Moves water through the system
1 Prevents debris from reaching the unit
1 Connect the equipment and make circulation
NOTE
The exact amount and setup of the plumbing, valves, filter equipment, sterilizing equipment, etc. vary from one pool to another. At minimum, a pool pump and filter are required. It is not recommended to install auxiliary electric heaters in the system. If absolutely necessary, auxiliary heaters must be installed and operated by qualified technicians. Fibropool cannot provide support for auxiliary heating systems.
Heat Pump Overview
II. Safety Information
Required Operating Conditions: 1. Power supply: 208-230V 50/60Hz. 2. Air
temperature: 35°F-105°F 3. Water temperature range:
45°F-104°F in Heating Mode 45°F-82°F in Cooling Mode
NOTE: Operating heat pumps at near-freezing temperatures risks damage to the
heat exchanger. Heat pumps must be empty of water at freezing temperatures.
See winterization guidelines for more details.
Verify the ground connection before operation. Improper grounding increases
the risk electric shock and death. Grounding protects both swimmers and
technicians from electric shock. It is absolutely necessary to properly ground
the unit. Heat pumps should be installed outdoors when possible. If necessary,
indoor installations must have adequate ventilation and clearance. Keep
children away from the heat pump. The lock function can be used to prevent
improper operation. Keep fingers and other objects away from the fan. Fan
blades are extremely sharp and can cut or damage objects put inside. If you
notice any unusual sounds, burning smell, electrical shorts, etc., please
immediately disconnect the heat pump and contact Fibropool support. Do not
install the unit near any combustible objects or materials. Install the heat
pump such that the base rests on a solid, level foundation. When cleaning the
unit, the heat pump should be off and disconnected from any power source.
III. Installation Instructions
3.1 Installation Diagram
*The above diagram may not fit your exact installation. Please contact your pool technician or Fibropool technical support for assistance. 3.2 Installation Clearance Proper clearance is mandatory to allow sufficient airflow and access for maintenance and repairs.
3.3 Additional By-pass kits A bypass is recommended for all installations and
is required for pumps larger than 1HP.
3.4 Heat pump unit size (mm)
FH235-I
FH285-I
3.5 Heat pump Exploded View
No. Parts 1 Display 2 Front panel 3 Side panel 4 Pillar 5 Pillar 6 Water flow switch 7 Pressure gauge 8 Sensor clip 9 Fan motor bracket 10 Fan motor 11 Fan blade
No. Parts 12 Top frame 13 Bolt 14 Top cover 15 Ventilation 16 Pillar 17 Back frame 18 Evaporator 19 Wire cover 20 Side panel 21 Wire clip
No. Parts 22 Wire clip 23 Terminal 24 Pillar 25 Compressor 26 Base tray 27 Four-way valve 28 EEV 29 Titanium heat exchanger 30 Electric box 31 Electric cover
3.6 Electrical connection Suggested power cable specification
Model FH235-I FH285-I Terminal Electrical connection
Power Cable Specification 316 AWG 3 14 AWG
Terminal cable max. 12 AWG
IV. Technical Specifications
4.1 Specifications
Model No.
FH235-I
FH285-I
- Heating Capacity at 80°Air Temp, Humidity 80%, Water 78°in, 82°out
Heating Capacity (kW)
7.2~1.7
21~4.8
Power Input (kW)
1.06~0.11
3.09~0.30
COP
15.8~6.8
15.8~6.8
- Heating Capacity at Air 59°, Humidity 70%, Water 78° in, 82°out
Heating Capacity (kW)
5.9~1.4
16.5~3.8
Power Input (kW)
1.2~0.18
3.37~0.5
COP
7.6~4.9
7.6~4.9
- Cooling Capacity at Air 95°, Water 84°in, 80°out
Cooling Capacity (kW)
4.2~1.0
11.6~2.7
Power Input (kW)
1.11~0.15
3.05~0.4
EER
6.6~3.8
6.7~3.8
- General data
Power supply
208-230V/1/60
Max Power Input (kW)
1.45
3.2
Max Current (A)
7.1
14.7
Water Flow Volume (gal/h)
660
1700
Refrigerant
R410a
Heat Exchanger
Titanium
Air Flow Direction
Vertical
Defrost Method
4 way valve
Working temp. range (°F)
5~109
Casing Material
ABS
Water Proof Level
IPX4
Noise level 1m dB(A)
41~51
47~58
Noise level 10m dB(A)
21~31
27~38
Net Weight (lbs)
98
135
Gross Weight (lbs)
122
159
Net Dimensions (in)
20.920.925.2
25.625.630.3
Package Dimensions (in)
2223.630.7
26.828.335.8
- Above data may change without notice.
4.2 Unit Details
MODEL POWER SUPPLY (VOLTS) CIRCUIT (AMPS) RUNNING TEMP RANGE (F) HEATING CAPACITY (BTU) COP MAX TEMPERATURE (F) RATED WATER FLOW (GPM) WATER PRESSURE DROP (PSI) MAX INPUT POWER (BTU) MAX INPUT CURRENT (AMPS) REFRIGERANT TYPE REFRIGERANT WEIGHT (LBS) NOISE (DB) NET WEIGHT (LBS) UNIT DIMENSIONS (IN) PIPE CONNECTIONS (IN) WATERPROOF CLASS ELECTRICITY SHOCK PROOF
FH-235-I
208-230V/1PH/60Hz
10 5~109 24000 4.90 104 10.80
5.8 5442
7.23 R410A 1.146
38 97 212125 1-1/2″ IPX4 I
FibroPool Co LLC. BAY ST. LOUIS, MS, USA
www.FibroPool.com
MODEL POWER SUPPLY (VOLTS) CIRCUIT (AMPS) RUNNING TEMP RANGE (F) HEATING CAPACITY (BTU) COP MAX TEMPERATURE (F) RATED WATER FLOW (GPM) WATER PRESSURE DROP (PSI) MAX INPUT POWER (BTU) MAX INPUT CURRENT (AMPS) REFRIGERANT TYPE REFRIGERANT WEIGHT (LBS) NOISE (DB) NET WEIGHT (LBS) UNIT DIMENSIONS (IN) PIPE CONNECTIONS (IN) WATERPROOF CLASS ELECTRICITY SHOCK PROOF
FH-285-I
208-230V/1PH/60Hz
20 5~109 62000 4.670 104 27.90
7.3 12501
16.7 R410A 3.109
45 134 252529 1-1/2″ IPX4
I
FibroPool Co LLC. BAY ST. LOUIS, MS, USA
www.FibroPool.com
V. Electrical Connections
5.1 Electric wiring diagram
VI. Heat Pump Operation
6.1 Controller interface
6.2 Start up & Locking
Hold the power button for 1 second to switch the heat pump on or off. This
button is also used to return back to the main interface.
Hold the button for 3 seconds to lock or unlock the display. (The lock will be
activated automatically after 60 seconds of inactivity). When the display is
locked, the logo appears. Note: Controller will need to be unlocked before
changing any settings.
Attention: Before you start, make sure the filtration pump is running and that
water is flowing through the heat pump. Water flow is required for heat pump
to start. 6.3 Temperature Mode Selection
From the main screen, press to switch between temperature modes:
Auto
Heating
Cooling
*While in Auto mode, if the heat pump is currently heating the display will show
cooling mode, the display will show 6.4 Operation Mode Selection
and .
and . In
From the main screen, press to switch between the following operational modes:
Silent mode: Limits noise by reducing fan speed. Eco mode: Controls fan speed
and compressor output to reduce energy usage. Powerful mode: Highest heating
and cooling potential.
Note: Auto runs in Eco mode only. Other modes not available. 6.5 Temperature
Adjustment
From the main screen, press and to adjust the desired water temperature of your pool.
When the
icon lights up, press the power button
6.6 Clock & Timer setting
to save.
From the main screen, press and hold and for 3 seconds to enter the clock setting. Press
and hold them for 3 seconds again to enter the Timer setting, the
will flash.
Cancel timer: When you have set the Timer, under the Timer setting interface, hold and for 3 seconds again to cancel the Timer.
Clock or Timer setting: To adjust clock or timer settings, change the hours with and , then
press the to edit the minutes. Change the minutes with and the setting and
return to the main screen.
Note: There are 3 individual timers available for separate scheduling.
, press
to confirm
6.7 Other Icons
Water Inlet
Water outlet
Fan motor
Defrosting Wi-Fi
Note: On the main screen, the Water inlet temp. and Water outlet temp. will display alternately.
6.8 Manual Defrosting
Hold and for 3 seconds to start Manual defrosting function. Note: These heat pumps enter defrost mode automatically when necessary. Contact Fibropool technical support if you encounter frequent defrosting or need to manually enable defrost. 6.9 Restoring Factory settings
Hold and and and for 5 seconds to restore factory settings. 6.10 Running Parameter checking
Hold
for 3 seconds to enter the parameter overview, then press
and
to check the
parameters listed below:
Code A01 A02 A03 A04 A05 A06 A07 A08 A09 A10 A11 A12 A13 A14
Description Inlet water temp. Outlet water temp. Ambient temp.
Exhaust temp. Gas return temp. Outer piping temp. Inner piping temp.
EEV aperture Compressor current
Radiator temp. Voltage value
Frequency Fan motor speed Fan motor speed
Unit °F °F °F °F °F °F °F
A (amps)
V (volts) Hz (Hertz) r/min (rotations/minute) r/min (rotations/minute)
6.11 Parameter setting
Hold
for 3 seconds to enter the Parameter setting, press
to select the parameter, then
press
Code P01 P02 P03 P04 P05
and to set the new data for the below parameters.
Description Inlet water temp. in Heating mode Inlet water temp. in Cooling
mode
Inlet water temp. in Auto mode Water temp. difference before restart Heat pump
ON/OFF when reached the desired water temp.
Default 27 27 27 1 1
Scope 8~40 8~28 8~40 1~18 1 ON, 0 OFF
6.12 Wi-Fi Setting
Hold
Hold
for 5 seconds, enter the mode of intelligent net distribution for 5 seconds, enter the mode of AP net distribution
6.13 Change Display of Temperature from (°C) to (°F)
Hold
for 5 seconds, if fail, try to hold it for 5 seconds again. When you see the icon is
changed, then succeed.
Note: When the temperature display is changed, you need to set the Wi-Fi again.
VII. Initial Operation
7.1 Attention When first connected, allow water to flow through to purge air
from lines. Always inspect electrical connections before operation. Verify
that grounding lug is attached to a grounding rod or pool bonding according to
local electrical codes. 7.2 Preparation Before Adjustment Ensure the system is
installed correctly according to these guidelines. Check that water
connections are secure and in the correct positions. Verify supply voltage is
sufficient for heat pump operation. Verify adequate ventilation around the
unit
VIII. Operating Instructions
8.1 To ensure proper operation, frequently inspect water and electrical
connections. Follow the guidelines below when performing maintenance or
repairs:
Always disconnect the incoming power from the breaker or a shutoff switch
before opening unit.
Unless necessary or instructed by Fibropool, most default settings do not need
to be adjusted.
Frequently inspect electrical connections for loose or damaged wiring and
components.
Evaporator fins should be cleaned when dirty or every six months. An air
compressor can safely remove most dirt and debris. A damp cloth can be used,
but use caution as the fins are sharp and may tear the cloth and cut skin.
After long periods of inactivity (after winterization, for example): inspect
and clean all equipment, flush plumbing, inspect the pool pump, and recheck
and tighten all electrical connections.
Aftermarket replacement parts are not recommended and cannot be supported by
Fibropool. Visit www.fibropool.com for replacement parts or contact technical
support for assistance.
8.2 Draining Heat Exchange
When not installed for prolonged periods of time or in anticipation of hard
freeze, the heat pump should be completely drained by tilting the outlet at
least 45°. A shop vac is recommended to remove any remaining water. Plug the
water inlet and outlet before storage to prevent insects and rodents from
entering tank.
- Warning: A heat exchange cracked due to freezing is not covered under the warranty for this product. It is the homeowner’s responsibility to observe proper winterization procedures. See section XI: Maintenance and Winterization for more details.
IX. Error Codes and Troubleshooting
Code Description
Potential reasons
Solutions
Ensure that water connections are in
Insufficient water flow
the correct order, that the pump is operating properly, and that all
Water flow protection
necessary valves are open
Check the wiring and reconnect water Water flow switch disconnected
flow switch
Water flow switch defective
Replace flow switch
E04 Antifreeze protection
Ambient/Inlet water temperature are too low
Wait for the ambient/inlet water temperature to increase
Ensure that water connections are in
Insufficient water flow
the correct order, that the pump is operating properly, and that all
necessary valves are open
Ambient/ Water temperature is Wait for the ambient/inlet water
too high
temperature to decrease
E05 High pressure protection Fan motor speed is abnormal or Inspect fan motor,
replace if necessary
fan motor is damaged
Excess refrigerant gas
Drain excess refrigerant*
High pressure switch
Reconnect or replace high pressure
disconnected or defective
switch*
Verify all plumbing is clear of Plumbing is clogged or jammed
obstructions and flowing properly
Ensure the heat pump has sufficient
Bad ventilation
clearance and adequate airflow. Clean the evaporator fins. Verify the
fan is running correctly.
Low pressure switch
Reconnect or replace low pressure
E06 Low pressure protection
disconnected or defective Gas leakage
switch Verify that the pressure is within acceptable range. Repair leaks
Fan motor speed is abnormal or Inspect fan motor, replace if necessary
fan motor is damaged
EEV blocked or piping system Verify all plumbing is clear of
jammed
obstructions and flowing properly
Connection failure
Bad wire connection
Check wire between motherboard and controller
E09 between motherboard Defective controller
Replace controller
and controller
Defective motherboard
Replace motherboard
Communication failure E10 between motherboard
and driver module
Bad wire connection
Defective motherboard Defective Driver module
Check wire between motherboard and controller Replace motherboard Replace driver module
Ensure that water connections are in
Insufficient water flow
the correct order, that the pump is operating properly, and that all
Excessively high exhaust E12
temperature
Low refrigerant Plumbing is clogged or jammed
necessary valves are open Check gauge for pressure Verify all plumbing is clear of obstructions and flowing properly
Defective exhaust temperature Replace sensor
sensor
Inlet water temperature Sensor disconnected or
E15
sensor failure
defective
Reconnect or replace sensor
Outer piping temperature Sensor disconnected or
E16
sensor failure
defective
Reconnect or replace sensor
Exhaust temperature E18
sensor failure
Sensor disconnected or defective
Reconnect or replace sensor
Inverter module E20
abnormal protection
Verify all incoming voltage and major electrical components
Ambient temperature E21
sensor failure
Sensor disconnected or defective
Reconnect or replace sensor
Ensure that water connections are in
Insufficient water flow Overcooling protection in E23 cooling mode
the correct order, that the pump is operating properly, and that all necessary valves are open
Outlet water temperature sensor failure
Replace sensor
Outlet water E27 temperature sensor
failure
Sensor disconnected or defective
Reconnect or replace sensor
Suction temperature E29
sensor failure
Sensor disconnected or defective
Reconnect or replace sensor
Ensure that water connections are in
Insufficient water flow Overheating protection in E32 heating mode
the correct order, that the pump is operating properly, and that all necessary valves are open
Outlet water temperature sensor failure
Replace sensor
Piping temp. too high
Ambient/water temperature is
Verify unit temperature limits
E33 protection under cooling too high in cooling mode
mode
Refrigerant system anomaly
Check refrigerant lines*
Inner piping temperature Sensor disconnected or
E42
sensor failure
defective
DC fan motor E46
malfunction
Bad wire connection Fan motor defective
Reconnect or replace sensor
Check fan motor wiring Replace fan motor
*Any manipulation of the refrigerant or related components must be performed by a qualified technician. Contact Fibropool technical support for assistance.
X. WiFi Connection and Operation
Scan the QR code below with your phone’s camera for step-by-step WiFi
connection and operation instructions
Hold
for 5 seconds, enter the mode of intelligent net distribution
Hold
for 5 seconds, enter the mode of AP net distribution
XI. Maintenance and Winterization
· For best performance, we recommend setting the temperature and allowing your
heater to run as often as possible.
· Clean your pool’s filtration system regularly to avoid damage to the unit
due to a dirty or clogged filter.
· Keep the coils clean by using a foaming air conditioner coil cleaner or
pressurized air from an air compressor or air duster.
· Winterization: If the unit is not running during winter months, disconnect
the power supply and water connections, and drain water from unit by tilting
the heater toward the water inlet side at a 45 degree angle. A shop vac can
also be used.
· Winterization: If possible, store the unit indoors after disconnected to
minimize risks of freeze damage or excessive wear due to winter conditions.
· After the unit is winterized, it is ideal to cover the unit with a tarp or
similar cover.
- Warning: A heat exchange cracked due to freezing is not covered under the warranty for this product. It is the homeowner’s responsibility to observe proper winterization procedures.
FIBROPOOL HEAT PUMP LIMITED FACTORY WARRANTY
This warranty certificate applies only to FibroPool brand electric heat pumps
Fibropool Co. LLC warrants this Pool/ Spa Heat Pump, to the original owner, to
be free of material and workmanship
defects for a limited TEN(10) year term. Heat pumps utilizing Fibropool
Titanium Heat Exchangers carry a lifetime warranty on the titanium coil
tubing.
Specific warranty terms are listed below. This warranty will begin on the day
of purchase, verified by the homeowner’s proof of purchase documents.
The full warranty term includes parts and labor charge to remove, repair or
replace defective components or failure due to workmanship
CLAMS FOR WARRANTY REIMBURSEMENT MUST HAVE PRIOR AUTHORIZATION BY FIBROPOOL
and be performed by a qualified person .This warranty does not cover
transportation charges for equipment or component parts to and from the
factory. PROOF OF PURCHASE REQUIRED FOR WARRANTY COVERAGE This warranty is
applicable only if the unit’s installation and operation is expressly and
completely followed in accordance with the purchase model’s Owner /
Installation manual. These documents are furnished with each unit and are
available by contacting Fibropool Co. LLC. The liability of Fibropool Co. LLC.
shall not exceed the repair or the replacement of defective parts under the
including refrigerant or transportation to or from the Fibropool Service
Center.
Fibropool Co. LLC. Is not liable for any damages of any sort whatsoever,
including incidental and consequential. This warranty does not include damage
to any internal piping or components due to freezing conditions, negligence
and abuse, installations in corrosive environments or atmospheres, nor acts of
God.
There are no implied warranties of merchant ability of fitness for a
particular purpose that apply to this product. To obtain warranty
authorization, please contact: Fibropool Co. LLC., PO Box 2425, Bay Saint
Louis, MS 39521 USA
Warranty Schedule:
Lifetime parts warranty on titanium tubing heat excharge (plastic tank is excluded) 1 Year Labor on the entire unit 1 Year full on compressor, cabinet, motherboard and digital display 2-10 years prorated warranty on the compressor, cabinet and digit display 1 Year full warranty on all other parts 2-10 years prorated warranty on all other parts
PRORATED WARRANTY COVERAGE IS AS FOLLOWS: 0-1 YEAR: 100% 1-2 YEARS: 90% 2-5 YEARS: 50% 5-10 YEARS: 25%
Above mentioned warranties apply only to the original purchase. Warranty is
non-transferable. Fibropool will have the option to repair or replace the item
if found to be defective after inspection.
Purchaser is responsible for shipping cost to and from the nearest warranty /
repair center. FIBROPOOL WILL NOT BE HELD RESPONSIBLE FOR ANY CONSEQUENTIAL,
INCIDENTAL OR CONTINGENT DAMAGE Some states do not allow exclusion of
incidental and consequential damages and on how long implied warranty lasts;
so above
conditions and limitations may not apply to you. This warranty grants you
specific rights which may vary from state to state.
Toll free: 1-877 342 7676
Fax:+1-201 328 3300
Email: support@Fibropool.com
V2022.04
References
- Fibropool® Official Site - Shop Home Pool and Spa Equipment
- Fibropool® Official Site - Shop Home Pool and Spa Equipment
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>