JUNG 214201SR Area Line Coupler Instruction Manual

May 15, 2024
JUNG

JUNG 214201SR Area Line Coupler

Safety instructions

  • To avoid potential damage, read and follow the following instructions:
  • Electrical devices may be mounted and connected only by electrically skilled persons.
  • The danger of electric shock. During installation and cable routing, comply with the regulations and standards that apply to SELV circuits.
  • This manual is an integral part of the product and must remain with the customer.

System information

  • This device is a product of the KNX system and complies with the KNX directives.
  • Detailed technical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
  • The function of this device depends upon the software. Detailed information on loadable software and attainable functionality as well as the software itself can be obtained from the manufacturer´s product database.
  • The device can be updated. Firmware can be easily updated with the Jung ETS Service App (additional software).
  • The device is KNX Data Secure capable. KNX Data Secure offers protection against manipulation in building automation and can be configured in the ETS project. Detailed technical knowledge is required. A device certificate, which is attached to the device, is required for safe commissioning. During mounting, the device certificate must be removed from the device and stored securely.
  • Planning, installation and commissioning of the device is carried out using ETS version 5.7.7. or higher in the case of use as a backbone coupler, line coupler or amplifier or 6.1.1 in the case of use as a backbone coupler, line coupler, segment coupler or secure proxy.

Device components

JUNG-214201SR-Area-Line-Coupler-FIG- \(1\)

  1. KNX device connection terminal, subordinate lineSL
  2. Status LED Run
  3. Status LED Main
  4. Status LED Sub
  5. Status LED Mode
  6. Button Pass IA
  7. Button Pass GA
  8. Programming LED, red
  9. Programming button PROG.
  10. KNX device connection terminal, higher-order line ML

Status LED function Run

  • Power failure on higher-order line
  • Lights up green Ready for operation, higher-order and subordinate
  • lines are supplied with voltage.
  • Lights up red Power failure on subordinate line.
  • Lights up orange Group address filter function is deactivated
  • Flashes orange (approx. 1 Hz) Physical address filter function is deactivated
  • Flashes orange quickly (approx.
  • 4 Hz)
  • Both filter functions are deactivated

Status LED function Main

  • Lights up orange for 6 ms Telegram reception, higher-order line
  • Lights up red for 6 ms One-time communication error, higher-order line
  • Lights up red for 100 ms Repeated communication error, higher-order line
  • The display of errors has a higher priority.

Status LED function Sub

  • Lights up orange for 6 ms Telegram reception, subordinate line
  • Lights up red for 6 ms One-time communication error, subordinate line
  • Lights up red for 100 ms Repeated communication error, subordinate line
  • The display of errors has a higher priority.

Status LED function Mode

  • The device functions as a backbone coupler or line coupler
  • Lights up green Device functions as a segment coupler or line amplifier
  • Lights up orange Device functions as a backbone coupler, line coupler or segment coupler; and the secure proxy is activated
  • Lights up red for 100 ms Pass IA or Pass GA button has been pressed

Self-test of the status LED
During restart, the status LEDs light up green for 0.5 seconds and then red in sequence from the top to the bottom

Intended use

  • Establishes a data link between two KNX lines/segments/backbones and ensures electrical separation between these lines/segments/backbones
  • Operation as a backbone coupler, line coupler or segment coupler (from
  • ETS 6.1.1 onwards) or amplifier (up to ETS 5.7.7)
  • Installation in small distribution board on a DIN rail according to IEC 60715

Product characteristics

  • KNX Data Secure
  • Secure proxy for connection to an unencrypted and encrypted line
  • Electrical separation between the higher-order and subordinate line
  • Manual control used to deactivate filter functions

Area of use

Backbone coupler and line coupler

JUNG-214201SR-Area-Line-Coupler-FIG- \(2\)

  • Backbone coupler (BK): The physical address is the address of a backbone coupler
  • X.0.0 and must match the logical topology of the KNX system.
  • Connection of a mainline (HL) with a backbone line (BL). Alternatively with or without filter function. The coupler is logically assigned to the subordinate line.
  • Observe the instructions in the technical documentation regarding the address.
  • Line coupler (LK): The physical address is the address of a line coupler X.Y.0 and must match the logical topology of the KNX system.
  • Connection of a line with a mainline (HL). Alternatively with or without filter function.

The coupler is logically assigned to the subordinate line. Observe the instructions in the technical documentation regarding the address.

  • BK = Backbone coupler
  • LK = Line coupler
  • TLN = Bus device
  • SV = KNX power supply
  • DR = Choke
  • Each line segment requires a separate power supply (SV) including a choke (DR).

Segment coupler and amplifier

JUNG-214201SR-Area-Line-Coupler-FIG- \(3\)

Segment coupler (SK): The physical address is the address of a normal KNX participant X.Y.Z (Z≠0) and must match the logical topology of the KNX system. Division of a line (max. 256 participants) into independent line segments. Alternatively with or without filter function. The segment coupler is logically assigned to the subordinate line segment. Observe the instructions in the technical documentation regarding the address.

Amplifier (LV): The physical address is the address of a normal KNX participant X.Y.Z (Z≠0) and must match the logical topology of the KNX system. Division of a line (max. 256 participants) into independent line segments. Preparation and repetition of telegrams on a line, no filter function. Observe the instructions in the technical documentation regarding the address.

  • SK = Segment coupler
  • LV = Amplifier
  • TLN = Bus device
  • SV = KNX power supply
  • DR = Choke
  • Each line segment requires a separate power supply (SV) including a choke (DR).

Operation

  • Deactivating the physical address filter function
  • Press the Pass IA button.
  • The status LED Mode briefly lights up red.
  • The status LED Run displays the state of the filter functions, (see Figure 1).
  • The filter is deactivated until the Pass IA button is pressed again.
  • Deactivating the group address filter function
  • Press the Pass GA button.
  • The status LED Mode briefly lights up red.
  • The status LED Run displays the state of the filter functions, (see Figure 1).
  • The filter is deactivated until the Pass GA button is pressed again.
  •  Information for electrically skilled persons

DANGER!

  • The electric shock when live parts are touched.
  • Electric shocks can be fatal.
  • Cover up live parts in the installation environment.

Mounting and Electrical Connection

Secure operation

  • Secure commissioning in the ETS is activated.
  • Remove the device certificate from the device and store it securely.
  • Enter or scan the device certificate and add it to the project. Recommendation:
  • Use a high-resolution camera to scan the QR code.
  • Document all passwords and keep them safe.
  • Mounting and connecting the device
  • Observe cable routing and spacing
  • Mount the device on the DIN rail.
  • Connect bus lines to KNX device connection terminals (see Figure 1) observing the correct polarity.
  • Connect the higher-order line to the lower device connection terminal (10).
  • Power is supplied to the device via this terminal.
  • Connect the subordinate line to the upper device connection terminal (1).
  • Attach the cover caps to the KNX connections as protection against hazardous voltages.
  • The subordinate line requires a separate power supply.

Commissioning
Programming the physical address and application program with ETS

  • Switch on the bus voltage.
  • Press the programming button (9) PROG..
  • The programming LED (8) lights up.
  • Programming the physical address.
  • The programming LED goes out.
  • Program the application program and filter table.

Safe-state mode and master reset
Activating safe-state mode

  • The safe-state mode stops the execution of the loaded application program.
  • Only the system software of the device is still functional. ETS diagnosis functions and programming of the device are possible. No telegrams are transmitted.
  • Switch off the bus voltage or remove the KNX device connection terminal (10) of the higher-order line.
  • Press and hold down the programming button for approx. 15 seconds.
  • Switch on the bus voltage or attach the KNX device connection terminal. Release the programming button only after the programming LED starts flashing slowly.
  • The safe-state mode is activated.
  • By briefly pressing the programming button again, the programming mode can also be switched on and off in the safe-state mode. If the programming mode is active, the programming LED stops flashing.

Deactivating safe-state mode

  • Switch off the bus voltage for approx. 15 seconds or trigger a restart via the ETS.

Master reset
The master reset restores the basic device settings (physical address 15.15.0, firmware remains in place). The device must then be recommissioned with the ETS. In secure operation: A master reset deactivates device security. The device can then be recommissioned with the device certificate.

Performing a master reset

  • Precondition: The safe-state mode is activated.
  • Press and hold down the programming button for > 5 s.
  • The programming LED flashes quickly.
  • Release the programming button.
  • The device performs a master reset, restarts and is ready for operation again after approx. 5 s.

Restoring the device to factory settings
The device can be reset to factory settings with the Jung ETS Service App. This function uses the firmware contained in the device that was active at the time of delivery (delivered state). Restoring the factory settings causes the device to lose its physical address and configuration.

Technical data

  • Ambient temperature -5 … +45°C
  • Storage/transport temperature -25 … +70°C
  • Protection class III
  • Weight 90 g
  • Installation width 18 mm / 1 HP
  • KNX medium TP256
  • Commissioning mode S mode
  • Rated voltage KNX DC 21 … 32 V SELV
  • Current consumption KNX
  • Higher-order line 9 mA
  • Subordinate line 5 mA
  • Connection mode KNX Device connection terminal

Accessories

Connection cover Art. no. 2050 K

Warranty
The warranty is provided by the specialist trade under statutory requirements.
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
58579 Schalksmühle

GERMANY
Telefon: +49 2355 806-0
Telefax: +49 2355 806-204

[email protected]
www.jung.de

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

JUNG User Manuals

Related Manuals