Danfoss FK09 iC7 Series Frequency Converters Installation Guide

May 15, 2024
Danfoss

Installation Guide
Pedestal Kit for FK09/FB09 and FK10/FB10
iC7 Series Frequency Converters

Overview

1.1 Description
The pedestal kit is intended for floor-mounted FK09/FB09 and FK10/FB10 frequency converters. A pedestal and a cable entry plate are required for proper operation of the frequency converter. The pedestal features a front grill to allow proper airflow for cooling. Reuse the cable entry plate that ships with the frequency converter to maintain the IP21/Type 1 or IP54/Type 12 protection rating.

1.2 Kit Numbers
Use these instructions with the following kits.

Table 1: Pedestal Kits for FK09-FK10/FB09-FB10 Frequency Converters

Number Description
176F4034 400 mm (15.7 in) pedestal kit for FK09a/FB09a frequency converters
176F4035 400 mm (15.7 in) pedestal kit for FK10a/FB10a frequency converters
176F4036 200 mm (7.9 in) pedestal kit for FK09c/FB09c frequency converters

1.3 Items Supplied
The following parts are contained in the kit.
Table 2: Items Supplied in Pedestal Kits

Item Quantity
Pedestal base 1
Front cover 1
Upper front flange 1
Lower front flange 1
Side plate 2
M5x18 screw 6
M10 hex nut 2
M8 hex nut 4
M5x14 countersunk screw 12

Installation

2.1 Safety Information

NOTICE

QUALIFIED PERSONNEL

Only qualified personnel are allowed to install the parts described in these installation instructions.

  • Disassembly and reassembly of the frequency converter must be done in accordance with the corresponding service guide.
  • Use the standard fastener torque values from the service guide, unless the torque value is specified in these instructions.

WARNING

ELECTRICAL SHOCK HAZARD
The frequency converter contains dangerous voltages when connected to mains voltage. Improper installation, and installing or servicing with power connected, can cause death, serious injury, or equipment failure.

  • Only use qualified electricians for the installation.
  • Disconnect the frequency converter from all power sources before installation or service.
  • Treat the frequency converter as live whenever the mains voltage is connected.
  • Follow the guidelines in these instructions and local electrical safety codes.

WARNING

DISCHARGE TIME (20 MINUTES)
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning indicator lights are off.
Failure to wait 20 minutes after power has been removed before performing service or repair work can result in death or serious injury.

  • Stop the motor.
  • Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
  • DC-link connections to other frequency converters.
  • Wait 20 minutes for the capacitors to discharge fully before performing any service or repair work.
  • Measure the voltage level to verify full discharge.

NOTICE
ELECTROSTATIC DISCHARGE
Electrostatic discharge can damage components.

  • Ensure discharge before touching internal frequency converter components, for example by touching a grounded, conductive surface or by wearing a grounded armband.

2.2 Overview of Pedestal Installation

Danfoss FK09 iC7 Series Frequency Converters - Installation
1

1. Pedestal base
2. M10 hex nut
3. Upper front flange
4. M8 hex nut
5. M5x18 screw| 6. Side plate
7. Front cover
8. M5x14 countersunk screw
9. Lower front flange
10. M5x14 countersunk screw
---|---

2.3 Lifting the Frequency Converter

WARNING

LIFTING PRECAUTIONS
The frequency converter is heavy. Failure to follow local safety regulations for lifting heavy weights can cause death, personal injury, or property damage.

  • Ensure that the lifting equipment is in proper working condition.
  • Check the weight of the frequency converter and verify that the lifting equipment can safely lift the weight.
  • Always lift the frequency converter using the dedicated eye bolts at the top of the frequency converter.
  • Ensure that the angle from the top of the frequency converter to the lifting cable is 65° or greater.
  • Test lift the frequency converter approximately 610 mm (24 in) to verify the proper center of gravity lift point. Reposition the lifting point if the frequency converter is not level.
  • Never walk under suspended loads.

2.4 Securing the Pedestal to the Floor
Use the following steps to secure the pedestal to the floor before installing the frequency converter. See Illustration 2.

  1. Determine proper placement of the pedestal and frequency converter, considering the operating environment and cable access requirements.
  2. Set the pedestal base on the floor and secure 4 bolts through the mounting holes.
  3. Position the upper and lower front flanges in the pedestal base and fasten with 4 M8 hex nuts, 2 per flange.
    Danfoss FK09 iC7 Series Frequency Converters - Installation
2

2.5 Attaching the Frequency Converter
After attaching the pedestal to the floor, attach the frequency converter to the pedestal using the following steps. See Illustration 3.

WARNING

TIPPING PRECAUTION
If the frequency converter is not secured, the frequency converter can tip and cause serious personal injury.

  • After attaching the pedestal to the frequency converter, secure the top of the frequency converter to the wall or mounting panel.

Procedure

  1. Position the frequency converter on the pedestal base.
  2. Secure 2 M10 nuts over the threaded studs at the back of the pedestal, securing the pedestal to the frequency converter.
  3. Fasten 2 M5 screws through the back flange of the pedestal base into the flange on the lower end of the frequency converter.
  4. To secure the frequency converter to the wall or mounting panel, fasten 2 M10 bolts (not supplied) in the mounting holes at the top of the frequency converter. Use 1 bolt per mounting hole.
    Danfoss FK09 iC7 Series Frequency Converters - Installation
31. M5 screw in back flange
    2. M10 nut

2.6 Creating Cable Openings
The cable entry plate provides cable entry and cable termination points, and must be installed to maintain the IP21/Type 1 or IP54/ Type 12 protection rating. The cable entry plate is placed between the frequency converter cabinet and the pedestal. Reuse the cable entry plate that is shipped with the frequency converter.
The cable entry plate can be installed from inside the frequency converter cabinet or before attaching the front cover and side plates of the pedestal. To install the cable entry plate, use the following steps. Refer to Illustration 4.

  1. Create cable entry holes in the plate using a sheet metal punch.

  2. Insert the cable entry plate using 1 of the following methods:
    a. Slide the cable entry plate through the pedestal front opening.
    b. Insert the cable entry plate through the frequency converter cabinet angling the plate until it slides into position.

  3. Align the studs on the cable entry plate with the holes in the pedestal and secure with 8 M5 nuts.

  4. Attach the pedestal side panels with 8 M5x14 countersunk screws, 4 in each panel.

  5. Attach the front cover to the pedestal by securing 4 M5x14 countersunk screws.
    Danfoss FK09 iC7 Series Frequency Converters - Installation
4 Illustration 4: Cable Entry Plate and Pedestal 1. Cable entry plate
    2. Front cover| 3. Side panel
    4. M5 x14 countersunk screw
    ---|---

Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
danfossdrives.com

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

16 | Danfoss A/S © 2022.03
AN361429223580en-000101 / 136R0251