ACEUP ENERGY AG4350 Gasoline Generator Instruction Manual
- June 17, 2024
- ACEUP ENERGY
Table of Contents
ACEUP ENERGY AG4350 Gasoline Generator Instruction Manual
Section 1 Introduction and Safety
Introduction
⚠ WARNING
Consult Manual. Read and understand manual completely before using product.
Failure to completely understand manual and product could result in death or
serious injury.
The owner is responsible for proper maintenance and safe use of the equipment.
Before operating, servicing or storing this generator:
- Study all warnings in this manual and on the product carefully.
- Become familiar with this manual and the unit before use.
- Refer to the Assembly section of the manual for instructions on final assembly procedures. Follow the instructions completely.
Save these instructions for future reference. ALWAYS supply this manual to any
individual that will use this machine.
THE INFORMATION CONTAINED HEREIN WAS BASED ON MACHINES IN PRODUCTION AT THE
TIME OF PUBLICATION. BALDR INTERNATIONAL LLC RESERVES THE RIGHT TO MODIFY THIS
MANUAL AT ANY TIME.
Safety Rules
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all inclusive. If using a procedure, work method or operating technique that the manufacturer does not specifically recommend, verify that it is safe for others. Also make sure the procedure, work method or operating technique utilized does not render the equipment unsafe. Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death
or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor
or moderate injury.
NOTE: Notes contain additional information important to a procedure and will
be found within the regular text of this manual. These safety warnings cannot
eliminate the hazards that they indicate. Common sense and strict compliance
with the special instructions while performing the action or service are
essential to preventing accidents.
Safety Symbols and Meanings
DANGER Using a generator indoors CAN KILL YOU IN MINUTES. Generator exhaust contains carbon monoxide. This is a poison you cannot see or smell.
- Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be operated outdoors.
⚠ DANGER
Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not avoided, will result in death or
serious injury.
DANGER
Electrocution. Water contact with a power source, if not avoided, will result
in death or serious injury.
DANGER
Electrocution. Turn utility and emergency power supplies to OFF before
connecting power source and load lines. Failure to do so will result in death
or serious injury.
- It is recommended to obtain parts and service from your local IASD to keep this unit in safe working order.
- Do not operate unit on uneven surfaces, or in areas where it can be exposed to excessive moisture, dirt, dust, or corrosive vapors.
WARNING
Moving Parts. Keep clothing, hair, and appendages away from moving parts.
Failure to do so could result in death or serious injury.
WARNING
Hot Surfaces. When operting machine, do not touch hot surfaces. Keep machine
away from combustables during use. Hot surfaces could result in severe burns
or fire.
WARNING
Equipment and property damage. Do not alter construction of, installation, or
block ventilation for generator. Failure to do so could result in unsafe
operation or damage to the generator.
WARNING
Do not insert any object through the air cooling slots. Generator can start at
any time and could result in death, serious injury, and unit damage.
- When working on this equipment, remain alert at all times.
- Never work on the equipment when physically or mentally fatigued.
- Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
Exhaust and Location Hazards
DANGER
Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not avoided, will result in death or
serious injury.
DANGER
The exhaust system must be properly maintained. Do not alter or modify the
exhaust system as to render it unsafe or make it noncompliant with local codes
and/or standards. Failure to do so will result in death or serious injury.
WARNING
Asphyxiation. Always use a battery operated carbon monoxide alarm indoors and
installed according to the manufacturer’s instructions. Failure to do so could
result in death or serious injury.
WARNING
Equipment and property damage. Do not alter construction of, installation, or
block ventilation for generator. Failure to do so could result in unsafe
operation or damage to the generator.
· If you start to feel sick, dizzy, or weak after the generator has been
running, move to fresh air IMMEDIATELY. See a doctor, as you could have carbon
monoxide poisoning.
Electrical Hazards
DANGER
Electrocution. Contact with bare wires, terminals, and connections while
generator is running will result in death or serious injury.
DANGER
Electrocution. Water contact with a power source, if not avoided, will result
in death or serious injury.
- National Electric Code (NEC) requires the frame and external electrically conductive parts of the generator be properly connected to an approved earth ground. Local electrical codes may also require proper grounding of the generator. Consult with a local electrician for grounding requirements in the area.
- Use a ground fault circuit interrupter in any damp or highly conductive area (such as metal decking or steel work).
DANGER
Electrocution. In the event of electrical accident, immediately shut power
OFF. Use non-conductive implements to free victim from live conductor. Apply
first aid and get medical help. Failure to do so will result in death or
serious injury.
WARNING
Accidental Start-up. Disconnect the negative battery cable, then the positive
battery cable when working on unit. Failure to do so could result in death or
serious injury.
Fire Hazards
DANGER
Explosion and Fire. Fuel and vapors are extremely flammable and explosive. Add
fuel in a well ventilated area. Keep fire and spark away. Failure to do so
will result in death or serious injury.
DANGER
Do not overfill fuel tank. Fill to 1/2 in. of top of tank to allow for fuel
expansion. Overfilling may cause fuel to spill onto engine causing fire or
explosion, which will result in death or serious injury.
DANGER
Risk of fire. Allow fuel spills to completely dry before starting engine.
Failure to do so will result in death or serious injury.
WARNING
Do not insert any object through the air cooling slots. Generator can start at
any time and could result in death, serious injury, and unit damage.
- Do not operate the generator if connected electrical devices overheat, if electrical output is lost, if engine or generator sparks or if flames or smoke are observed while unit is running.
- Keep a fire extinguisher near the generator at all times.
Replacement Hazard Labels
Vertical CO Warning Decal
Section 2 General Information and Setup
Emissions
The United States Environmental Protection Agency (US EPA) (and California Air Resources Board (CARB), for engines/equipment certified to California standards) requires that this engine/equipment complies with exhaust and evaporative emissions standards. Locate the emissions compliance decal on the engine to determine applicable standards. For emissions warranty information, please reference the included emissions warranty. It is important to follow the maintenance specifications in the manual to ensure that the engine complies with the applicable emissions standards for the duration of the product’s life.
TABLE 1.
Product Specifications
Section 3 Operation
Transporting/Tipping of the Unit
Do not operate, store or transport the unit at an angle greater than 15 degrees.
Starting Pull Start Engines
⚠ WARNING
Recoil Hazard. Recoil could retract unexpectedly. Kickback could result in
death or serious injury.
⚠ CAUTION
Equipment and property damage. Disconnect electrical loads prior to starting
or stopping unit. Failure to do so could result in equipment and property
damage.
- Unplug all electrical loads from the unit’s receptacles before starting engine.
- Place generator on a level surface.
- See Figure 3-1. Open the fuel shut-off valve (A).
- Turn engine ON/OFF switch (B) to ON. See Figure 3-1.
- Slide engine choke (C) to Full CHOKE position (left). See Figure 3-2.
- See Figure 3-1. Firmly grasp recoil handle (D) and pull slowly until increased resistance is felt. Pull rapidly up and away.
- When engine starts, move choke knob to RUN position. If engine falters, move choke back to 1/2CHOKE position until engine runs smoothly, then to RUN position.
NOTE: If engine fires, but does not continue to run, move choke lever to Full CHOKE and repeat starting instructions. IMPORTANT NOTE: Do not overload generator or individual panel receptacles. These outlets are overload protected with pushto- reset circuit breakers. If amperage rating of any circuit breaker is exceeded, that breaker opens and electrical output to that receptacle is lost. Read Know Generator Limits carefully.
Generator Shut Down
⚠ CAUTION
Equipment and property damage. Disconnect electrical loads prior to starting
or stopping unit. Failure to do so could result in equipment and property
damage.
- Shut off all loads and unplug electrical loads from generator panel receptacles.
- Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.
- Move ON/OFF switch to OFF.
- Close fuel valve.
NOTE: Under normal conditions, close fuel valve and allow generator to run carburetor bowl out of fuel. For emergencies, switch to OFF.
Low Oil Level Shutdown System
The engine is equipped with a low oil level sensor that shuts down the engine automatically when the oil level drops below a specified level. The engine will not run until the oil has been filled to the proper level. If the engine shuts down and there is sufficient fuel, check engine oil level.
Section 4 Maintenance and Troubleshooting
Maintenance
Regular maintenance will improve performance and extend engine/equipment life. BALDR INTERNATIONAL LLC. recommends that all maintenance work be performed by an Independent Authorized Service Dealer (IASD). Regular maintenance, replacement or repair of the emissions control devices and systems may be performed by any repair shop or person of the owner’s choosing. However, to obtain emissions control warranty service free of charge, the work must be performed by an IASD. See the emissions warranty.
Maintenance Schedule
Follow maintenance schedule intervals, whichever occurs first according to use. NOTE: Adverse conditions will require more frequent service. NOTE: All required service and adjustments should be each season as detailed in the following chart.
Preventive Maintenance
Dirt or debris can cause improper operation and equipment damage. Clean generator daily or before each use. Keep area around and behind muffler free from combustible debris. Inspect all cooling air openings on generator.
⚠ WARNING
Do not insert any object through the air cooling slots. Generator can start at
any time and could result in death, serious injury, and unit damage.
- Use a damp cloth to wipe exterior surfaces clean.
- Use a soft bristle brush to loosen caked on dirt, oil, etc.
- Use a vacuum to pick up loose dirt and debris.
- Low pressure air (not to exceed 25 psi) may be used to blow away dirt. Inspect cooling air slots and openings on generator. These openings must be kept clean and unobstructed.
NOTE: DO NOT use a garden hose to clean generator. Water can enter engine fuel system and cause problems. If water enters generator through cooling air slots, some water will be retained in voids and crevices of rotor and stator winding insulation. Water and dirt buildup on generator internal windings will decrease insulation resistance of windings.
Engine Maintenance
WARNING
Accidental start-up. Disconnect spark plug wires when working on unit. Failure
to do so could result in death or serious injury.
Engine Oil Recommendations
To maintain the product warranty, the engine oil should be serviced in accordance with the recommendations of this manual. For your convenience, BALDR INTERNATIONAL LLC Maintenance Kits are available that include engine oil, oil filter, air filter, spark plug(s), a shop towel and funnel. These kits can be obtained from an Independent Authorized Service Dealer (IASD).
Only high-quality detergent oils classified for service SF, SG, SH, SJ or higher are recommended. DO NOT use special additives. Climate determines proper engine oil viscosity. See chart to select correct viscosity.
Inspect Engine Oil Level
WARNING
Risk of burns. Allow engine to cool before draining oil or coolant. Failure to
do so could result in death or serious injury.
Inspect engine oil level prior to each use, or every 8 hours of operation.
- Place generator on a level surface.
- Clean area around oil fill.
- See Figure 4-1. Remove oil fill cap and wipe dipstick clean.
- Screw dipstick into filler neck. Remove dipstick and verify oil level is within safe operating range. See Figure 4-2.
- Add recommended engine oil as necessary.
- Replace oil fill cap and hand-tighten.
NOTE: Some units have more than one oil fill location. It is only necessary to use one oil fill point.
Change Engine Oil
WARNING
Accidental start-up. Disconnect spark plug wires when working on unit. Failure
to do so could result in death or serious injury.
When using generator under extreme, dirty, dusty conditions, or in extremely
hot weather, change oil more frequently.
NOTE: Don’t pollute. Conserve resources. Return used oil to collection
centers. Change oil while engine is still warm from running, as follows:
- Place generator on a level surface.
- Disconnect the spark plug wire from the spark plug and place the wire where it cannot contact spark plug.
- Clean area around oil fill, and oil drain plug.
- Remove oil fill cap.
- Remove oil drain plug and drain oil completely into a suitable container.
- Install oil drain plug and tighten securely.
- Slowly pour oil into oil fill opening until oil level is between L and H marks on dipstick. DO NOT overfill.
- Install oil fill cap, and finger tighten.
- Wipe up any spilled oil.
- Properly dispose of oil in accordance with all applicable regulations.
Air Filter
Engine will not run properly and may be damaged if run with a dirty air filter. Service air filter more frequently in dirty or dusty conditio. ns. To service air filter:
- See Figure 4-3. Turn knob (A) and remove air filter cover (B).
- Wash in soapy water. Squeeze filter (C) dry in clean cloth (DO NOT TWIST).
- Clean air filter cover before re-installing it. NOTE: To order a new air filter, contact the nearest authorized service center at +1 855-801-0798.
Service Spark Plug
To service spark plug:
- Clean area around spark plug.
- Remove and inspect spark plug.
- Inspect electrode gap with wire feeler gauge and reset spark plug gap to 0.028 – 0.031 in (0.70 – 0.80 mm). See Figure 4-4.
NOTE: Replace spark plug if electrodes are pitted, burned or porcelain is cracked. Use ONLY recommended replacement plug. See Specifications. 4. Install spark plug finger tight, and tighten an additional 3/8 to 1/2 turn using spark plug wrench.
Inspect Muffler and Spark Arrestor
NOTE: Use ONLY original equipment replacement parts. Inspect muffler for cracks, corrosion, or other damage. Remove spark arrestor, if equipped, inspect for damage or carbon blockage. Replace parts as required.
Inspect Spark Arrestor Screen
WARNING
Hot Surfaces. When operating machine, do not touch hot surfaces. Keep machine
away from combustibles during use. Hot surfaces could result in severe burns
or fire.
- Loosen clamp (A) and remove screw. See Figure 4-5.
- Inspect screen (B) and replace if torn, perforated or otherwise damaged. If screen is not damaged, clean with commercial solvent.
- Replace spark arrestor cone (C) and screen (B). Secure with clamp (A) and screw.
Valve Clearance
IMPORTANT NOTE: If uncomfortable about doing this procedure, or the proper tools are not available, take generator to the nearest service center to have valve clearance adjusted. Check valve clearance after the first fifty-hours of operation. Adjust as necessary.
- Intake — 0.15 ± 0.02mm (cold), (0.006 ± 0.0008 in)
- Exhaust — 0.20 ± 0.02mm (cold) (0.008 ± 0.0008 in)
Storage
General
DANGER
Risk of Fire. Hot surfaces could ignite combustibles, resulting in fire. Fire
could result in death or serious injury.
DANGER
Risk of Fire. Verify machine has properly cooled before installing cover and
storing machine. Hot surfaces could result in fire.
It is recommended to start and run the generator for 30 minutes, every 30
days. If this is not possible, refer to the following list to prepare unit for
storage.
- DO NOT place a storage cover on a hot generator. Allow unit to cool to room temperature before storage.
- DO NOT store fuel from one season to another unless properly treated.
- Replace fuel container if rust is present. Rust in fuel will cause fuel system problems.
- Cover unit with a suitable protective, moisture resistant cover.
- Store unit in a clean and dry area.
- Always store generator and fuel away from heat and ignition sources.
Prepare Fuel System for Storage
Fuel stored over 30 days can go bad and damage fuel system components. Keep
fuel fresh, use fuel stabilizer. If fuel stabilizer is added to fuel system,
prepare and run engine for long term storage. Run engine for 10-15 minutes to
circulate stabilizer throughout fuel system. Adequately prepared fuel can be
stored up to 24 months. NOTE: If fuel has not been treated with fuel
stabilizer, it must be drained into an approved container. Run engine until it
stops from lack of fuel. Use of fuel stabilizer in fuel storage container is
recommended to keep fuel fresh.
-
Change engine oil.
-
Remove spark plug.
-
Pour tablespoon (5-10cc) of clean engine oil or spray a suitable fogging agent into cylinder.
⚠ WARNING
Vision Loss. Eye protection is required to avoid spray from spark plug hole when cranking engine. Failure to do so could result in vision loss. -
Pull starter recoil several times to distribute oil in cylinder.
-
Install spark plug.
-
Pull recoil slowly until resistance is felt. This will close valves so moisture cannot enter engine cylinder. Gently release recoil.
Change Oil
Change engine oil before storage. See Change Engine Oil.
Troubleshooting
Engine runs well at no-load, but bogs when load is applied.
Engine will not start; or starts and runs rough.
1.Short circuit in a connected load.
2.Generator is overloaded. 3.Engine speed is too slow. 4.Shorted generator
circuit.
1.Fuel shut-off is OFF. 2.Dirty air filter. 3.Out of fuel. 4.Stale fuel.
5.Spark plug wire not connected
to spark plug. 6.Bad spark plug. 7.Water in fuel. 8.Overchoking. 9.Low oil
level. 10.Excessive rich fuel mixture. 11.Intake valve stuck open or
closed. 12.Engine lost compression.
Engine shuts down during operation.
Engine lacks power.
Engine surges or stumbles.
1.Out of fuel. 2.Low oil level. 3.Fault in engine.
1.Load is too high. 2.Dirty air filter. 3.Engine needs to be serviced.
1.Choke is opened too soon. 2.Carburetor is running too rich
or too lean.
CORRECTION
1.Reset circuit breaker. 2.Check and repair. 3.Connect another device that is
in good condition. 4.Contact IASD. 5.Correct ground fault and press
reset button on GFCI receptacle (if equipped).
1.Disconnect shorted electrical load.
2.See Know Generator Limits . 3.Contact IASD. 4.Contact IASD.
1.Turn fuel shut-off ON. 2.Clean or replace air filter. 3.Fill fuel tank.
4.Drain fuel tank and fill with
fresh fuel. 5.Connect wire to spark plug. 6.Replace spark plug. 7.Drain fuel
tank; fill with fresh
fuel. 8.Set choke to no choke posi-
tion. 9.Fill crankcase to correct level. 10.Contact IASD. 11.Contact IASD.
12.Contact IASD.
1.Fill fuel tank. 2.Fill crankcase to correct level. 3.Contact IASD.
1.Reduce load (see Know Generator Limits).
2.Clean or replace air filter. 3.Contact IASD.
1.Set choke to 1/2 CHOKE until engine runs smoothly.
2.Contact IASD.
10
Owner’s Manual for Petrol Generator
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>