KRUEGER KBHD Blower Coils Direct Drive User Manual
- June 17, 2024
- KRUEGER
Table of Contents
- INTRODUCTION
- PRODUCT DESCRIPTION | GENERAL INFORMATION
- PRODUCT DESCRIPTION | FEATURES
- COILS | GENERAL INFORMATION
- ELECTRIC HEAT FEATURES & CAPACITIES
- MOTOR ELECTRICAL INFORMATION
- FAN CURVES | SIZES 08 & 12
- DIMENSIONAL DATA | KBHD | SINGLE BLOWER
- SUGGESTED SPECIFICATION & CONFIGURATION
- Documents / Resources
KBHD, KBVD
Blower Coils | Horizontal and Vertical Direct Drive
|
---|---
KBHD| KBVD
INTRODUCTION
Krueger model KBHD and KBVD direct drive blower coils offer a wide range of
application flexibility, while maintaining a simple, easy to install unit
design.
These units are intended to provide comfort cooling and heating within a small
footprint. They may be applied in many types of building structures including
schools, office buildings, hospitals, condominiums, assisted living
facilities, apartments or stores.
Applications can be constant or variable volume with several control options.
There are many applications the KBHD and KBVD direct drive blower coils can be
utilized based on the control option selected. Some examples are listed below.
SINGLE-SPEED:
- Constant volume
- Field balanced
- Manually adjustable
- Direct Expansion (DX) split systems
- Static environments (such as service areas)
- Available with all other catalog coil configurations
MULTI-SPEED:
-
Four discrete speeds (high-medium-low-idle)
-
Field balanced
-
Manually adjustable
-
Functional with multiple operators:
– Building Management System (BMS)
– Thermostats
– 3-Speed switch -
Static environments (such as service areas)
-
Great for setting electric heat minimum CFM
VARIABLE-SPEED:
-
Multiple remote signal options:
– 0 – 10VDC
– 2 – 10VDC
– 4 – 20mA -
BMS Compatible
-
Upstream of Variable-Air-Volume (VAV) systems
-
Constant pressure
-
BMS turn down for energy efficiency
MODELS
KBHD – Horizontal Direct Drive Blower Coil Unit
KBVD – Vertical Direct Drive Blower Coil Unit
PRODUCT DESCRIPTION | GENERAL INFORMATION
ACOUSTICS
Control of noise within both occupied and unoccupied spaces has become
increasingly important to designers and building owners/occupants. Proper
consideration must be given to placement of indoor air conditioning units,
particularly in the occupied space.
Inherent flexibility of the fan and coil combination in the vertical
configuration makes it a great solution for sound sensitive areas. In such
instances, a fan running at a low speed with a high capacity coil normally
yields satisfactory results. It also may be desirable to select a larger
nominalcapacity unit and operate it at a less than nominal airflow for further
acoustical benefits. Being able to choose between single or dual blower
configurations for the size 30 and 40 units allows for greater flexibility
when trying to optimize the selection for both sound and performance. Even
better, the enhanced control options also allow for a quieter turndown and the
direct drive design also eliminates any noise issues caused by squeaky belts.
It is also recommended to use 3-phase motors for sound sensitive applications
to avoid potential 1-phase motor hum.
INSTALLATION
These floor mounted or ceiling hung units can be installed with external
vibration isolation on a base rail (KBHD or KBVD) or hanger rods (KBHD only)
at the corner points. This requires flex connections at the corner brackets,
ductwork, electrical connections, and piping connections.
One of the most important and basic IAQ issues is condensate management. The
first step to trouble-free operation is proper installation. It is very
important that the unit be mounted high enough so that the condensate drain
from the unit may be properly trapped. Please refer to the IOM manual found at
www.krueger-hvac.com for specifics on this
issue. As with all HVAC systems, these units should be installed according to
all applicable ASHRAE standards, SMACNA, and local code requirements. When
selected and installed properly, the units are seismically certified.
OPERATING LIMITATIONS
Krueger direct drive blower coil units offer unmatched performance
capabilities across a broad range of airflow and static pressure requirements.
Units must not be operated above maximum fan speed or unit airflow as listed
in the Fan Performance section of this catalog. Unit operation at greater than
maximum fan speed could drastically reduce bearing life and may resultin a
catastrophic wheel failure.
Operating at greater than the maximum allowable airflow in the cooling mode
may result in unsatisfactory operation due to moisture carryover from the
coil. In addition, it is often not economical to operate a unit at its maximum
fan speed due to the greater motor power requirements.
Units with electric heat should not be operated with a leaving air temperature
greater than 104°F (40°C) to prevent electric heat limit trips and room
stratification. To prevent excessive leaving air temperatures and limit trips,
a hydronic (or steam) coil and electric heat should not be operated
simultaneously. Electric heat units are equipped with a high limit lockout
switch that disables the electric heater if the temperature of the hydronic
coil is greater than 104°F (40°C).
Water coils must not be operated above a fluid velocity of 8 ft/sec to reduce
the possibility of velocity induced erosion and flow noise. Water coils must
not be operated below a fluid velocity of 1 ft/sec to prevent degraded coil
performance caused by laminar flow. These high or low fluid flow rates may not
be included in the AHRI coil certification.
DESIGNED FOR MAXIMUM FLEXIBILITY
Both horizontal and vertical direct drive blower coils are designed to
maximize flexibility of selection and installation.
The units will exceed the stringent quality standards of the institutional
markets, while remaining cost competitive in the light commercial markets.
COMPONENT OPTIONS
The extensive variety of standard options available on the KBHD and KBVD units
are where you find the versatility to fit any HVAC system designer’s needs.
Options include mixing boxes with standard low-leak dampers, high-efficiency
filter sections for 2” prefilter and 4” final filter, and blow thru electric
heat with single point power connection. All electric heat units are listed
with ETL as an assembly and carry the cETLus label.
Disconnects and fusing mean easier coordination between mechanical and
electrical trades.
Direct drive fans eliminate noise and reduce maintenance time caused by belts.
All KBHD and KBVD direct drive blower coils have the option of foil faced or
closed cell foam insulation.
COIL OPTIONS
Coil options allow for 3, 4, or 6-row cooling coils. Water coils have optional
circuiting that can be used to reduce water pressure drop, which may also
allow for pipe size reductions and lower material cost. Hot water or standard
steam coils may be placed in the preheat or reheat positions.
QUALITY PRODUCT
KBHD and KBVD direct drive blower coils are built from 18 gage galvanized
steel. This metal surpasses the ASTM 125 hour salt spray test for corrosion
and rust. Standard insulation is 1” thick fiberglass, complying with UL 181
and NFPA 90A.
All units, with or without electric heat, are cETLus listed and labeled. All
wiring is in compliance with NEC, assuring safety and quality for the owner.
BEST IN CLASS PERFORMANCE
Krueger direct drive blower coils feature class leading airflow, coil
capacity, and pressure capabilities. The single and dual blower configuration
options for the size 30 and 40 units also allow for greater flexibility when
configuring for sound and performance.
LOWER INSTALLED COST
All KBHD or KBVD direct drive blower coils are shipped completely assembled,
reducing field installation time and labor. All units are thoroughly inspected
and tested prior to shipment, eliminating potential problems at startup.
Standard wiring allows for single point power connection and all wiring is in
compliance with NEC, ensuring safety and quality.
A wide variety of fan discharge configurations allow for increased flexibility
and easier installation on the jobsite, resulting in cost reductions by
eliminating expensive elbows, etc.
PRODUCT DESCRIPTION | FEATURES
STANDARD FEATURES
Construction
- Galvanized steel cabinet construction, minimum 18 gage
- 1” thick fiberglass insulation
- 1” supply duct collars
- Gasketed, removable access panels sized for easy handling
- IAQ galvanized steel drain pan (not included with heating-only units)
- Left and right hand arrangements
Fan Assembly
- Forward curved (double width, double inlet) fans
- Solid steel shafting
- Statically and dynamically balanced
Fan Motor and Drive
- Directly driven motor and blower
- Electronically commutated 1 and 3-phase motors with electronic protection
Electrical Control
- 1-speed motor controls accessible from exterior of control enclosure
- Three different control options to choose from:
1. Variable 1-speed with manual adjustment
2. Variable multi-speed with manual adjustment
3. Proportional speed (2-10VDC, 0-10VDC or 4-20mA remote signal) with external adjustment
Coils
- Coils are designed, manufactured and tested by Krueger
- AHRI 410 certified and labeled
- 1/2” O.D. seamless copper tubes
- High efficiency aluminum surface for optimizing heat transfer, pressure drop, and carryover
- Mechanically expanded copper tubes are leak tested to a minimum 450 PSIG air pressure underwater
- 450 PSIG working pressure at 200°F (93°C)
- Evaporator coils are factory sealed and charged with a minimum of 5 PSIG nitrogen or refrigerated dry air
- Steam coils rated at 15 PSIG maximum operating pressure at about 35°F (2°C)
- 0.016” tube wall thickness (0.025” on steam)
Piping Packages
- Factory assembled, shipped loose
- 1/2”, 3/4”, 1”, 1-1/4” & 1-1/2” piping size
Filters and Filter Rack
- Hinged side access flat filter rack
- Standard size 2” nominal throwaway filters
- Filter rack designed to accept 2” filters
Electrical
- Fan motor wired and terminated to junction box
- All units cETLus listed in compliance with UL/ANSI Standard 1995
OPTIONAL FEATURES
Construction
- IAQ stainless steel drain pan with 1” MPT galvanized pipe outlet
- External rubber-in-shear or spring type vibration isolators, hangers, or floor mount
- Scrim reinforced foil faced insulation
- Closed cell foam insulation
- 1” double wall construction
- Hinged access panels with lift and turn fasteners
- Base rails with rigging slots are factory assembled and installed
- Auxiliary (secondary) drain connections
Fan Motor and Drive
- Directly driven motor and blower
- Electronically commutated 1- and 3-phase motors with electronic protection
Coils
- 3, 4 and 6-row chilled water or DX coils
- 1 and 2-row hot water or standard steam coils
- Heating coil in preheat or reheat position
- Coil connections opposite handing
- Stainless steel coil casings
- Automatic air vents on water coils
- Heat pump compatible cooling coils
- 0.025” tube wall thickness
Filters
- 2” pleated filter
- Spare throwaway or pleated filters
- High efficiency filter rack with 2” and 4” filters
Inlet Damper Section
- Factory assembled and installed
- Heavy gage galvanized steel formed blade dampers
- Low-leak dampers with extruded vinyl blade seals and flexible metal jamb seals
- Parallel blade operation
- Interconnecting damper linkage
Electrical
- Door interlocking disconnect switch (non-fused)
- Hand-Off-Auto (HOA) switch
- Main fusing
- Remote mounted digital display and programmable thermostats
Electrical Heat Section
- Factory mounted electric heater with single point power connection, cETLus listed as an assembly
PRODUCT DESCRIPTION | FEATURES DETAIL
MODEL KBHD
MODEL KBVD
COILS | GENERAL INFORMATION
COILS
Krueger offers hot water, chilled water and direct expansion (DX) coils for
specific application with all Model KBHD and KBVD direct drive blower coils.
AHRI 410 certified and labeled, and strict on-site inspection before, during,
and after installation guarantees the highest quality and performance
available.
STANDARD FEATURES
- Coils are designed, manufactured and tested by Krueger
- AHRI 410 certified and labeled
- 1/2” O.D. seamless copper tubes
- High efficiency aluminum fin surface for optimizing heat transfer, pressure drop and carryover
- Mechanically expanded copper tubes leak tested to a minimum 450 PSIG air pressure under water
- Manual air vent plug on all water coils
- Copper ODM sweat connections
- 450 PSIG working pressure at 200°F
- Evaporator coils are factor y sealed and charged with a minimum of 5 PSIG nitrogen or refrigerated dry air
- Refrigerant coils are provided with distributor (metering device fieldprovided)
- Steam coils rated at 15 PSIG maximum operating pressure at about 35°F
- 0.016” tube wall thickness (0.025” on steam)
OPTIONAL FEATURES
- Stainless steel coil casings
- Automatic air vents on water coils
- Heat pump compatible cooling coils
- 0.025” tube wall thickness
COILS | FILTER INFORMATION
UNIT SIZE| COIL FACE AREA| 2” FLAT FILTERS (QUANTITY) & SIZE|
FILTER FACE AREA
---|---|---|---
08| 2.1 (0.20)| (1) 15.75” x 19.75” x 2” (400 x 502 x 51)| 2.2 (0.20)
12| 2.7 (0.25)| (1) 15.75” x 24.75” x 2” (400 x 629 x 51)| 2.7 (0.25)
16| 3.5 (0.33)| (2) 15.75” x 19.75” x 2” (400 x 502 x 51)| 4.3 (0.40)
20| 4.9 (0.46)| (1) 15.75” x 19.75” x 2” (400 x 502 x 51)
(1) 15.75” x 24.75” x 2” (400 x 629 x 51)| 4.9 (0.46)
30| 6.5 (0.60)| (2) 24.75” x 15.75” x 2” (629 x 400 x 51)
(1) 24.75” x 19.75” x 2” (629 x 502 x 51)| 8.8 (0.82)
40| 8.4 (0.78)| (3) 24.75” x 19.75” x 2” (629 x 502 x 51)| 10.2 (0.95)
NOTES:
- Standard filters are 2” throwaway.
- Filter sizes are nominal and standard size, measure in inches (millimeters).
- Coil and filter face areas are measured in square feet (square meters).
- Cooling and heating coils have same face area.
COILS | COMPONENT STATIC PRESSURE LOSS (“WG)
UNIT SIZE| NOMINAL CFM| CABINET| FILTER (2” T/A)|
COIL| MIXING BOX| ELECTRIC HEAT SECTION
---|---|---|---|---|---|---
1-ROW| 2-ROW| 3-ROW| 4-ROW| 6-ROW
08| 600| 0.05| 0.08| 0.03| 0.05| 0.12| 0.16| 0.24| 0.02| 0.01
700| 0.07| 0.11| 0.04| 0.07| 0.15| 0.20| 0.31| 0.03| 0.02
800| 0.09| 0.15| 0.04| 0.09| 0.19| 0.25| 0.38| 0.04| 0.02
900| 0.11| 0.19| 0.05| 0.11| 0.23| 0.30| 0.46| 0.05| 0.02
1000| 0.14| 0.23| 0.06| 0.12| 0.27| 0.35| 0.54| 0.06| 0.02
12| 1000| 0.06| 0.14| 0.04| 0.08| 0.17| 0.24| 0.36| 0.04| 0.02
1100| 0.08| 0.17| 0.50| 0.10| 0.19| 0.28| 0.42| 0.05| 0.02
1200| 0.09| 0.20| 0.06| 0.11| 0.22| 0.32| 0.47| 0.06| 0.02
1300| 0.11| 0.24| 0.06| 0.12| 0.25| 0.36| 0.54| 0.07| 0.02
1400| 0.12| 0.28| 0.07| 0.14| 0.28| 0.40| 0.60| 0.08| 0.03
16| 1400| 0.08| 0.11| 0.05| 0.09| 0.20| 0.26| 0.37| 0.07| 0.02
1500| 0.09| 0.13| 0.05| 0.10| 0.22| 0.30| 0.42| 0.08| 0.02
1600| 0.10| 0.15| 0.06| 0.11| 0.25| 0.33| 0.46| 0.09| 0.02
1700| 0.11| 0.17| 0.06| 0.12| 0.27| 0.36| 0.51| 0.10| 0.02
1800| 0.13| 0.19| 0.07| 0.14| 0.30| 0.39| 0.56| 0.11| 0.03
20| 1600| 0.07| 0.11| 0.03| 0.07| 0.15| 0.18| 0.30| 0.03| 0.02
1800| 0.09| 0.14| 0.04| 0.08| 0.18| 0.22| 0.36| 0.04| 0.02
2000| 0.11| 0.18| 0.05| 0.10| 0.21| 0.26| 0.41| 0.05| 0.02
2200| 0.13| 0.21| 0.06| 0.11| 0.25| 0.31| 0.48| 0.06| 0.02
2400| 0.16| 0.26| 0.07| 0.13| 0.28| 0.35| 0.55| 0.07| 0.02
30| 2600| 0.11| 0.09| 0.05| 0.09| 0.19| 0.27| 0.41| 0.06| 0.02
2800| 0.12| 0.11| 0.05| 0.10| 0.22| 0.30| 0.43| 0.07| 0.02
3000| 0.14| 0.12| 0.06| 0.12| 0.24| 0.34| 0.47| 0.08| 0.02
3200| 0.16| 0.14| 0.07| 0.13| 0.27| 0.34| 0.53| 0.09| 0.03
3400| 0.18| 0.16| 0.07| 0.14| 0.29| 0.38| 0.58| 0.10| 0.03
40| 3600| 0.13| 0.13| 0.05| 0.10| 0.21| 0.30| 0.43| 0.06| 0.02
3800| 0.14| 0.15| 0.06| 0.11| 0.22| 0.33| 0.47| 0.06| 0.02
4000| 0.16| 0.16| 0.06| 0.12| 0.24| 0.35| 0.51| 0.07| 0.02
4200| 0.18| 0.18| 0.07| 0.13| 0.26| 0.38| 0.55| 0.08| 0.03
4400| 0.19| 0.20| 0.07| 0.14| 0.28| 0.41| 0.59| 0.08| 0.03
NOTES:
- All static pressures are at nominal CFM.
- Coil static pressure for standard coil, 10FPI at 80/67 EAT and 45° EWT with 10° rise.
- For 8, 12 or 14 FPI, refer to Selection Software®, available at www.krueger-hvac.com.
- Filter static pressure based on 50% loaded filter.
- If pleated filters are used in lieu of throwaway, the filter static pressure loss is 0.35.
ELECTRIC HEAT FEATURES & CAPACITIES
ELECTRIC HEAT STANDARD FEATURES
- Flanged construction for direct unit mounting, in blow thru configuration
- Listed for zero clearance installation
- Meets National Electrical Code requirements
- Ni-Chrome wire in ceramic insulators
- Stainless steel element terminals and hardware
- Element support brackets on maximum 3 1/2” centers
- Solid cover with continuous full height hinge
- Over temperature protection
- All internal wiring rated for 105°C minimum
- Airflow switch
- Incoming line power distribution block
- cETL Listed in compliance with UL/ANSI Standard 1995
- Single point power connection
- Heater factory mounted to unit with cETL listing as an assembly
OPTIONAL HEATER CONTROL
- Main incoming power disconnect (non-fused)
- Fusing (main) (per stage)
- Magnetic contactors wired for disconnecting operation
- Fan control package with heater interlock contacts (required for single point power connection)
USEFUL FORMULAS
kW = (kW = CFM x ΔT x 1.085**) / 3413
1Ø AMPs = (kW x 1000) / Volts
- 1kW = 3413 BTU/H
** Capacity at sea level
Altitude Considerations:
Reduce by 0.034 for each 1000 ft. of altitude above sea level.
Example: 5000 ft. / 1000 ft. = 5
5 x 0.034 = 0.17
1.085 – 0.17 = 0.915
ELECTRICAL CALCULATIONS INFORMATION
- Refer to MCA/MOP Calculator at www.krueger-hvac.com for MCA and/or MOP calculations.
- Non-Fused Door Interlock Disconnect Switch shall be sized according to MCA.
- Main Fusing shall be sized according to MOP.
HEATER AMP CALCULATION
VOLTAGE| AMPS PER KW
115 / 1| 8.70
208 / 1| 4.81
230 / 1| 4.35
277 / 1| 3.61
208 / 3| 2.78
230 / 3| 2.51
480 / 3| 1.26
ELECTRIC HEAT kW LIMITS
UNIT VOLTAGE AND PHASE| UNIT SIZE
08| 12| 16| 20| 30 (SINGLE BLOWER)| 40 (SINGLE
BLOWER)| 30 (DUAL BLOWER)| 40 (DUAL BLOWER)
MIN| MAX| MIN| MAX| MIN| MAX| MIN|
MAX| MIN| MAX| MIN| MAX| MIN| MAX| MIN|
MAX
SINGLE PHASE| 115| kW| 3.0| 5.0| 3.0| 5.0| 3.0| 5.0| 3.0| 5.0| 3.0| 5.0| 3.0|
5.0| 5.0| 5.5| 5.0| 5.5
AMPs| 26.1| 43.5| 26.1| 43.5| 26.1| 43.5| 26.1| 43.5| 26.1| 43.5| 26.1| 43.5|
3.5| 47.8| 43.5| 47.8
208| kW| 3.0| 9.0| 3.0| 9.0| 3.0| 9.0| 3.0| 9.0| 3.0| 9.0| 3.0| 9.0| 6.0|
11.0| 6.0| 11.0
AMPs| 14.4| 43.3| 14.4| 43.3| 14.4| 43.3| 14.4| 43.3| 14.4| 43.3| 14.4| 43.3|
28.8| 52.9| 28.8| 52.9
230| kW| 3.0| 11.0| 3.0| 11.0| 3.0| 11.0| 3.0| 11.0| 3.0| 11.0| 3.0| 11.0|
6.0| 13.0| 6.0| 13.0
AMPs| 13.0| 47.8| 13.0| 47.8| 13.0| 47.8| 13.0| 47.8| 13.0| 47.8| 13.0| 47.8|
26.1| 56.5| 26.1| 56.5
277| kW| 3.0| 13.0| 3.0| 13.0| 3.0| 13.0| 3.0| 13.0| 3.0| 13.0| 3.0| 13.0|
6.0| 17.0| 6.0| 17.0
AMPs| 10.8| 46.9| 10.8| 46.9| 10.8| 46.9| 10.8| 46.9| 10.8| 46.9| 10.8| 46.9|
21.7| 61.4| 21.7| 61.4
THREE PHASE| 208| kW| 3.0| 13.0| 3.0| 16.0| 3.0| 16.0| 3.0| 16.0| 3.0| 16.0|
3.0| 16.0| 6.0| 24.0| 6.0| 24.0
AMPs| 8.3| 36.1| 8.3| 44.4| 8.3| 44.4| 8.3| 44.4| 8.3| 44.4| 8.3| 44.4| 16.7|
66.6| 16.7| 66.6
230| kW| 3.0| 13.0| 3.0| 18.0| 3.0| 18.0| 3.0| 18.0| 3.0| 18.0| 3.0| 18.0|
6.0| 26.0| 6.0| 26.0
AMPs| 7.5| 32.6| 7.5| 45.2| 7.5| 45.2| 7.5| 45.2| 7.5| 45.2| 7.5| 45.2| 15.1|
65.3| 15.1| 65.3
480| kW| 3.0| 13.0| 3.0| 20.0| 3.0| 20.0| 3.0| 26.0| 3.0| 26.0| 3.0| 26.0|
6.0| 38.0| 6.0| 38.0
AMPs| 3.8| 16.3| 3.8| 25.1| 3.8| 25.1| 3.8| 32.6| 3.8| 32.6| 3.8| 32.6| 7.5|
47.7| 7.5| 47.7
NOTES:
- Factory certified submittals available upon request.
- Standard heater kW limits are maximum per unit size and voltage.
- Heater should be sized for a maximum leaving air temperature of 104 °F.
- Electric heaters are only available in fan arrangement 3.
MOTOR ELECTRICAL INFORMATION
HORSEPOWER | MAXIMUM MOTOR AMPERAGE |
---|
VOLTAGE/PHASE
115/1| 208/1| 230/1| 277/1| 208/3| 230/3|
480/3
1/2| 7.7| 5.0| 5.0| 4.1| 2.0| 2.0| 1.0
1| 12.8| 9.4| 9.4| 6.9| 3.7| 3.7| 1.7
1 1/2| 19.23| 14.63| 14.63| 11.03| 4.4| 4.4| 2.2
2| 25.63| 18.83| 18.83| 13.83| 7.43| 7.43| 3.43
3| —| —| —| —| 8.83| 8.83| 4.43
NOTES:
- Actual motor nameplate AMPs may vary, but will not exceed values shown.
- Consult factory for applications requiring special motors.
- Amp values are total amp values for (2) motors.
WEIGHTS
UNIT WEIGHTS
COMPONENT| UNIT SIZE
08| 12| 16| 20| 30 (SINGLE BLOWER)| 40 (SINGLE
BLOWER)| 30 (DUAL BLOWER)| 40 (DUAL BLOWER)
BASE UNIT| 115 (52)| 133 (60)| 152 (69)| 175 (79)| 287 (130)| 305 (139)| 357
(162)| 375 (170)
MIXING BOX| 46 (21)| 54 (25)| 65 (30)| 90 (41)| 105 (48)| 105 (48)| 162 (74)|
162 (74)
BLOW THRU ELECTRIC HEATER| 42 (19)| 42 (19)| 55 (25)| 55 (25)| 55 (25)| 125
(57)| 55 (25)| 125 (57)
COIL ROWS| 1 ROW – DRY| 12 (5)| 14 (6)| 17 (8)| 21 (10)| 26 (12)| 26 (12)| 32
(15)| 32 (15)
1 ROW – WET| 14 (6)| 16 (7)| 20 (9)| 25 (11)| 32 (15)| 32 (15)| 41 (19)| 41
(19)
2 ROW – DRY| 17 (8)| 21 (10)| 26 (12)| 33 (15)| 42 (19)| 42 (19)| 52 (24)| 52
(24)
2 ROW – WET| 21 (10)| 26 (12)| 32 (15)| 42 (19)| 54 (24)| 54 (24)| 69 (31)| 69
(31)
3 ROW – DRY| 23 (10)| 28 (13)| 35 (16)| 45 (20)| 57 (26)| 57 (26)| 72 (33)| 72
(33)
3 ROW – WET| 29 (13)| 36 (16)| 44 (20)| 59 (27)| 75 (34)| 75 (34)| 95 (43)| 95
(43)
4 ROW – DRY| 29 (13)| 35 (16)| 44 (20)| 57 (26)| 73 (33)| 73 (33)| 91 (41)| 91
(41)
4 ROW – WET| 37 (17)| 45 (20)| 56 (25)| 74 (34)| 96 (44)| 96 (44)| 121 (55)|
121 (55)
6 ROW – DRY| 40 (18)| 49 (22)| 62 (28)| 81 (37)| 104 (47)| 104 (47)| 132 (60)|
132 (60)
6 ROW – WET| 52 (24)| 64 (29)| 81 (37)| 106 (48)| 138 (63)| 138 (63)| 178
(81)| 178 (81)
NOTES: Unit weight data is shipping weight in pounds (kilograms).
MOTOR/DRIVE WEIGHTS
TYPE| MOTOR HORSEPOWER
1/2| 1| 1 1/2| 2| 3
SINGLE PHASE| 13| 19| 38| 38| —
THREE PHASE| 14| 18| 43| 36| 106
NOTES: Unit weight data is shipping weight in pounds (kilograms).
FAN CURVES | SIZES 08 & 12
FAN CURVES | SIZES 16, 20, 30 & 40
FAN CURVES | SIZES 30 & 40
DIMENSIONAL DATA | KBHD | SINGLE BLOWER
SIZE | FAN SIZE | L | W | H | C | D | E | F | G | J | K |
---|---|---|---|---|---|---|---|---|---|---|---|
08 | 9” x 6” (229 x 152) | 40” (1016) | 30” (762) | 21” (533) | 16” (406) | 20” | |||||
(508) | 5” (127) | 10 3/8” (264) | 8 3/8” (213) | 10 7/8” (276) | 2” (51) | ||||||
12 | 9” x 6” (229 x 152) | 40” (1016) | 36” (914) | 21” (533) | 16” (406) | 25” | |||||
(635) | 5 1/2” (140) | 10 3/8” (264) | 8 3/8” (213) | 13 7/8” (352) | 2” (51) | ||||||
16 | 10” x 8” (254 x 203) | 40” (1016) | 44” (1118) | 21” (533) | 16” (406) | 39 | |||||
1/2” (1003) | 2 1/4” (57) | 11 1/2” (292) | 10 5/8” (270) | 16 5/8” (422) | 2” (51) | ||||||
20 | 10” x 8” (254 x 203) | 40” (1016) | 50” (1270) | 21” (533) | 16” (406) | 44 | |||||
1/2” (1130) | 2 3/4” (70) | 11 1/2” (292) | 10 5/8” (270) | 19 5/8” (498) | 2” (51) | ||||||
30 | 10” x 8” (254 x 203) | 46” (1168) | 59” (1499) | 30” (762) | 25” (635) | 51” | |||||
(1295) | 4” (102) | 11 1/2” (292) | 10 5/8” (270) | 24 1/4” (616) | 9 3/4” (248) | ||||||
40 | 10” x 8” (254 x 203) | 46” (1168) | 68” (1727) | 30” (762) | 25” (635) | 59” | |||||
(1499) | 4 1/2” (114) | 11 1/2” (292) | 10 5/8” (270) | 28 5/8” (727) | 9 3/4” |
(248)
NOTES:
- All dimensions are in inches (millimeters). All dimensions are ±1/4” (6mm). Metric values are soft conversion.
- Right hand unit shown, left hand unit opposite. Motor/drive location may be specified Left or Right Hand. Standard control enclosure location matches motor/drive position.
- Provide sufficient clearance to permit access to controls and comply with applicable codes and ordinances.
- See page F2-89 for filter rack details.
- Base rail is optional on the base unit. Base rails must be used with mixing box.
- See coil connection detail drawings for coil connection sizes and locations.
- Drawings are not to scale and are not for installation purposes.
DIMENSIONAL DATA | KBVD | SINGLE BLOWER
SIZE| FAN SIZE| L| W| H| C| D| E|
F| G| J| K
---|---|---|---|---|---|---|---|---|---|---|---
08| 9” x 6” (229 x 152)| 24” (610)| 30” (762)| 44” (1118)| 16” (406)| 20”
(508)| 5” (127)| 10 3/8” (264)| 8 3/8” (213)| 10 7/8” (276)| 2 1/2” (64)
12| 9” x 6” (229 x 152)| 24” (610)| 36” (914)| 44” (1118)| 16” (406)| 25”
(635)| 5 1/2” (140)| 10 3/8” (264)| 8 3/8” (213)| 13 7/8” (352)| 2 1/2” (64)
16| 10” x 8” (254 x 203)| 24” (610)| 44” (1118)| 44” (1118)| 16” (406)| 39
1/2” (1003)| 2 1/4” (57)| 11 1/2” (292)| 10 5/8” (270)| 16 3/4” (425)| 2 1/2”
(64)
20| 10” x 8” (254 x 203)| 30” (762)| 50” (1270)| 50” (1270)| 16” (406)| 44
1/2” (1130)| 2 3/4” (70)| 11 1/2” (292)| 10 5/8” (270)| 19 3/4” (502)| 2 1/2”
(64)
30| 10” x 8” (254 x 203)| 30” (762)| 59” (1499)| 56” (1422)| 25” (635)| 51”
(1295)| 4” (102)| 11 1/2” (292)| 10 5/8” (270)| 24 1/4” (629)| 10” (254)
40| 10” x 8” (254 x 203)| 30” (762)| 68” (1727)| 59” (1499)| 25” (635)| 59”
(1499)| 4 1/2” (114)| 11 1/2” (292)| 10 5/8” (270)| 28 3/4” (730)| 10” (254)
NOTES:
-
All dimensions are inches (millimeters). All dimensions are ±1/4” (6mm). Metric values are soft conversion.
-
Right hand unit shown, left hand unit opposite. Motor/drive location may be specified Left or Right Hand.
Standard control enclosure location matches motor/drive position. -
Provide sufficient clearance to permit access to controls and comply with applicable codes and ordinances.
-
Flat filter rack may be located at unit inlet as required. See page F2-89 for filter rack details.
-
Base rail is optional on the base unit. Base rails must be used with mixing box.
-
See coil connection detail drawings for coil connection sizes and locations.
-
Drawings are not to scale and are not for installation purposes.
DIMENSIONAL DATA | BLOW THRU UNIT, ELECTRIC HEAT
UNIT SIZE | WEIGHT LBS (KG) | G |
---|---|---|
SINGLE BLOWER | DUAL BLOWER | |
08 | 45” (20) | – |
12 | 45” (20) | – |
16 | 45” (20) | – |
20 | 45” (20) | – |
30 | 45” (20) | 100” (45) |
40 | 45” (20) | 140” (64) |
NOTES:
- All dimensions are inches (millimeters). All dimensions are ± 1/4” (6mm). Metric values are soft conversion.
- Motor/drive location may be specified left or right hand. Standard control enclosure location matches motor/drive position.
- Provide sufficient clearance to permit access to controls and comply with applicable codes and ordinances.
- Available for horizontal discharge only.
- To prevent sweating for units configured with an uninsulated blowthru heat section. ensure that insulation is field-installed prior to cooling mode operation.
- Drawings are not to scale and are not for installation purposes.
DIMENSIONAL DATA | STANDARD MIXING BOX
UNIT SIZE | H | W | A | B | C | D |
---|---|---|---|---|---|---|
08 | 21” (533) | 30” (762) | 9” (229) | 18” (457) | 6” (152) | 18” (457) |
12 | 21” (533) | 36” (914) | 9” (229) | 24” (610) | 6” (152) | 18” (457) |
16 | 21” (533) | 44” (1118) | 9” (229) | 30” (762) | 7” (178) | 18” (457) |
20 | 21” (533) | 50” (1270) | 12” (305) | 36” (914) | 7” (178) | 21” (533) |
30 | 30” (762) | 59” (1499) | 12” (305) | 45” (1143) | 7” (178) | 21” (533) |
40 | 30” (762) | 68” (1727) | 15” (381) | 48” (1219) | 10” (254) | 24” (610) |
NOTES:
- All dimensions are inches (millimeters). All dimensions are ± 1/4” (6mm). Metric values are soft conversion.
- Damper drive rods are internal, located on both sides of unit.
- Mixing box includes space for standard f lat filter rack.
- Base rails must be used with mixing box.
- Drawings are not to scale and are not for installation purposes.
DIMENSIONAL DATA | STANDARD FLAT FILTER RACK
SIZE | A | B | C | QTY & SIZE FILTERS |
---|---|---|---|---|
08 | 16” (406) | 20” (508) | 20” (508) | (1) 16” x 20” |
12 | 16” (406) | 25” (635) | 25” (635) | (1) 16” x 25” |
16 | 16” (406) | 39 1/2” (1003) | 20” (508) | (1) 16” x 20” |
20 | 16” (406) | 44 1/2” (1130) | 25” (635) | (1) 16” x 20” |
(1) 16” x 25”
30| 25” (635)| 51” (1295)| 25” (635)| (1) 16” x 25”
(1) 20” x 25”
40| 25” (635)| 59” (1499)| 25” (635)| (1) 20” x 25”
NOTES:
- All dimensions are inches (millimeters). All dimensions are ± 1/4” (6mm). Metric values are soft conversion.
- Flat filter rack may be located at unit inlet as required.
- Standard rack will accept 1” or 2” thick filters.
- High efficiency rack will accept nominal 2” and/or 4” thick filters.
- High efficiency rack not available on units with filter rack.
- 1” duct connection space provided on entering side of rack for connection of field ductwork.
- Hinged cover provided on both sides of externally mounted filter racks. Internal standard filter racks have pivoting bar type filter retainer.
- See individual unit submittal for location of filter rack on unit.
- Drawings are not to scale and are not for installation purposes.
SUGGESTED SPECIFICATION & CONFIGURATION
GENERAL
Furnish and install Krueger® Model KBHD & KBVD Blower Coil Units where
indicated on the plans and specifications. Units shall be completely factory
assembled and tested and shipped as one piece except where noted.
All units shall be capable of meeting or exceeding the scheduled capacities
for cooling, heating and air delivery. All unit dimensions for each model and
size shall be considered maximums.
All units shall be of “draw-thru” design with coils, fans, motor, and drain
pan completely contained within the unit cabinet.
Electric heat to be in the blow-thru configuration.
Units shall be cETL listed in compliance with UL/ANSI Std. 1995.
All unit coils shall meet or exceed the scheduled cooling and heating
capacity, selected and rated in accordance with AHRI 410.
CONSTRUCTION
All units shall be fabricated of minimum 18 gage galvanized steel, able to
withstand a 125 hour salt spray test per ASTM B-117. Panels shall be die-
formed “multibend” construction for optimum strength and rigidity.
All exterior panels shall be single wall insulated with 1” thick fiberglass
insulation, rated for a maximum air velocity of 5000 f.p.m.
Optional: Single wall with 1” thick, 1.6 pound per cubic foot density scrim
reinforced foil faced insulation.
Optional: Single wall with 1” thick closed cell foam insulation.
Optional: 1” double wall construction.
Insulation must meet all requirements of ASTM C1071 (including C665), UL181
for erosion, and carry a 25/50 rating for flame spread/smoke developed per
ASTM E-84, UL723 and NFPA 90A. In addition to using adhesive complying with
NFPA 90A, the insulation shall incorporate a secondary mechanical fastener
attached to the unit casing wall. Adhesive as the only method of fastening the
insulation to the casing is not acceptable.
All access panels shall be fully insulated and attached with standard
fasteners on at least two opposite sides. No single access panel shall be
larger than 30” x 36” for safety and ease of handling. No coil or drain piping
or electrical connections shall pass through any access panel. Each unit shall
be furnished with a one-piece heavy gage.
G90 steel or optional IAQ stainless steel drain pan with welded corner
construction. Drain pan shall be insulated with minimum 1/8” closed cell foam.
All units shall be provided with 9/16” diameter hanger rod holes in the top
and bottom panels for “through-bolt ” type suspension installation.
Optional: Spring type unit mounting vibration isolators shall be provided by
the unit manufacturer.
Optional: Rubber-in-shear type unit mounting vibration isolators shall be
provided by the unit manufacturer.
Optional: Units to have factory assembled and installed base rails with
rigging slots.
All units shall have a minimum 1” duct collar on both the discharge and
return.
FAN & MOTOR ASSEMBLY
All units shall be furnished with double inlet forward curved centrifugal
blowers statically and dynamically balanced for smooth operation. Blower
wheels shall be mounted directly on the motor shaft. Belt driven blowers are
not acceptable.
Fan motors shall be electronically commutated with thermal overload protection
and a constant torque operation. RPM control shall not be acceptable. Motors
shall feature permanently lubricated ball bearings and operate on three or
single phase power.
All motors to be installed, factory programmed and wired to the control panel.
All motors shall be isolated, depending on motor size, via belly band or
torsion flex mount to the blower housing.
All motor wiring is to be terminated in a junction box, external to the unit
casing.
All motors to be operated by single-speed or multi-speed local or remote
controller.
COILS
All unit coils shall be rated in accordance with AHRI 410.
All coils shall be 1/2” O.D. seamless copper tubes with collared aluminum
fins. All tubes shall be mechanically expanded to provide an efficient bond
between tube and fin. All water coils shall be provided with a manual air vent
fitting to allow for coil venting. Valve core type vent fittings shall not be
accepted.
All chilled water, hot water, and direct expansion (DX) coils shall have
aluminum fins and 0.016” tube wall thickness.
All coils shall be hydrostatically tested with air under water at 450 PSIG
minimum pressure and rated for a maximum of 450 PSIG working pressure at
200°F.
All steam coils shall have 0.025” tube wall thickness.
All steams coils shall be suitable for 15 PSIG maximum operating pressure.
Optional: Provide automatic air vents, in lieu of manual air vents.
Optional: Provide 0.025” tube wall thickness.
FILTER RACK ASSEMBLY
All units shall be furnished with a flat filter rack with hinged access on
both sides designed to accept a 2” nominal standard sized filters. All units
shall be provided with nominal 2” throwaway filters factory installed. One
complete set of spare throwaway filters shall be provided for each unit.
Optional: Factory provided MERV 8 pleated filters.
Optional: Unit shall have a High Efficiency filter rack suitable for a pleated
2” MERV 8 and a pleated 4” MERV 11, MERV 14 or MERV 15 filter.
INLET DAMPER SECTION
Where shown on the plans, the unit manufacturer shall furnish a fully
insulated mixing box section (factory assembled and installed inlet damper
section) to be mounted next to the unit on base rail (unit & mixing box).
The mixing box section shall include heavy gage formed steel blade dampers in
a heavy gage steel frame with extruded vinyl blade seals and flexible metal
jamb seals. Damper drive linkage shall be factory furnished and installed by
the unit manufacturer. A field furnished and installed damper actuator can be
mounted directly to the damper shaft.
ELECTRICAL CONTROL
The unit fan motor shall be completely factory wired to an external electrical
enclosure. Each unit shall include fan control package with 24 volt control
voltage. Each unit shall include a motor control board, motor circuit fusing,
control circuit transformer and terminal strip for connection of field wiring.
Motor Control Board Option 1: Motor control shall be provided by a single
speed or proportional speed controller mounted on the exterior surface of the
control box.
Opening the control box to adjust the fan speed shall not be required.
Motor Control Board Option 2: Four speed motor control shall be provided with
potentiometer type adjustment. Unit to be compatible with three speed control
thermostat.
Calibrated airflow curves shall be provided near the control box to aid in
testing and balancing.
A main incoming power non-fused disconnect switch with lock-out tag-out ready
feature shall be factory furnished and wired by the unit manufacturer for
single point power connection.
ELECTRIC HEAT SECTION
Where shown on the plans, the unit manufacturer shall furnish an electric
resistance heating assembly with the heating capacity, voltage and stages as
shown in the schedule. The heater assembly shall be designed and rated for
installation to the blower coil unit in the blow thru configuration without
the use of duct extensions or transitions between the unit and the heater
assembly. The heater assembly shall be factory assembled to the air handling
unit and completely factory wired. The heater/ unit assembly shall be listed
for zero clearance meeting all N.E.C. requirements and be cETL listed in
compliance with UL/ANSI Std. 1995.
All heating elements shall be open coil design using NiChrome wire mounted in
ceramic insulators and housed in an insulated heavy gage galvanized steel
housing. All elements shall terminate in a machine staked stainless steel
terminal secured with stainless steel hardware. The element support brackets
shall be spaced no greater than 3-1/2” on center. A ll internal wiring shall
be rated for 105°C minimum.
All heaters shall include over temperature protection. All heaters shall
include a non-adjustable airflow switch.
An incoming line power distribution block shall be provided. The power
distribution block shall be designed to accept incoming power wiring capable
of carrying 125% of the calculated load current.
In addition to the above, electric heaters shall include the following
options:
- Main incoming power disconnect (non-fused)
- Main fusing
- Magnetic contactors wired for disconnecting operation
Electric heat section available uninsulated or with insulated double wall construction.
-
SERIES:
KBHD- Horizontal Direct Drive Blower Coil
KBVD – Vertical Direct Drive Blower Coil -
ARRANGEMENT:
Fan Arr. 1 (Upblast Rear)
Fan Arr. 2 (Upblast Front)
Fan Arr. 3 (Horizontal Top Front) -
INLET:
High Efficiency Rack
Mixing Box with Linkage -
MIXING BOX DAMPER LOCATION:
Bottom and Rear Inlet
Top and Bottom Inlet
Top and Rear Inlet -
SIZE:
8, 12, 16, 20, 30, 40 -
MOTOR VOLTAGE:
115/1/60 ECM
208/1/60 ECM
230/1/60 ECM
277/1/60 ECM
208/3/60 ECM
230/3/60 ECM
460/3/60 ECM -
MOTOR CONTROL:
Solo – Manual Adjustment
Select – 3 Speed Adjustable
Sync – Remote Signal Adj 2-10VDC -
MOTOR HAND:
Left-hand Motor
Right-hand Motor -
SPEED SWITCH:
Field Provided
Unit Mounted 3 Speed Switch with Off Position
Remote Mounted 3 Speed Switch with Off Position -
AUTO SWITCH:
Hand-Off Auto Switch -
CONTROL ENCLOSURE LOCATION:
Standard – Discharge End/Access Door Opens from Discharge End
Alternate 1 – Top of Unit/Access Door Opens to Side
Alternate 2 – Discharge End/Access Door Opens to Side -
COIL 1:
3-Row Cold Water
4-Row Cold Water
6-Row Cold Water
3-Row DX, Single Circuit
4-Row DX, Single Circuit
6-Row DX, Single Circuit
1-Row Hot Water
2-Row Hot Water
1-Row Steam
2-Row Steam
3-Row with Changeover
4-Row with Changeover
6-Row with Changeover -
COIL 1 FPI:
8 FPI
10 FPI
12 FPI
14 FPI -
COIL 1 HAND:
Right Hand
Left Hand -
COIL 1 AIR VENT:
Manual
Auto Air Vent -
COIL 1 CASING:
Galvanized Casing
Stainless Steel Casing -
COIL 1 TUBE WALL:
0.016”
0.025” -
COIL 1 REFRIGERANT TYPE:
R-410 -
COIL 1 DISTRIBUTOR:
(See Krueger’s selection software) -
COIL 1 PIPING SIZE:
1/2”, 3/4”, 1”, 1-1/4”, 1-1/2” -
COIL 1 PIPING VALVE:
2-Way Control Valve
3-Way Control Valve
3-Way with Balance ByPass Valve -
COIL 1 PIPING PACKAGE:
Manual Ball Valve w/ Memory Stop
Manual Ball Valve w/ Memory Stop, Fixed Flow Ctrl
Ball Valve in Bypass & Ball Valves w/ Memory Stop -
COIL 1 FIXED GPM:
1 /2” = 0.5 to 4.0 GPM in 0.5 GPM increments4.0 to 9.0 GPM in 1.0 GPM increments
3/4” = 4.0 to 15.0 GPM in 1.0 GPM increments
1” = 11.0 to 22.0 GPM in 1.0 GPM increments
1-1/4” = 18.0 to 29.0 GPM in 1.0 GPM increments
1-1/2” = 26.0 to 45.0 GPM in 1.0 GPM increments -
COIL 1 UNIONS:
Union -
COIL 1 P/T PORTS:
P/T Port -
COIL 1 AQUASTAT BLEED LINE:
Aquastat Bleed Line -
COIL 1 Y-STRAINER:
Y-Strainer
Y-Strainer with blowdown -
COIL 1 ACTUATOR TYPE:
Field Provided by Others 2-Position Close-Off
Factory Provided 2-Position Close-Off, NC
MV, 2-Way, Floating Point, Fail-In-Place, 24V
MV, 3-Way, Floating Point, Fail-In-Place, 24V
HP Close-Off Actuator, 2-Way Valve-24/115/208V
HP Close-Off Actuator, 2-Way Valve-230/277V -
COIL 1 ACTUATOR POSITION:
Normally Closed – 2-Pos Close Off
Normally Open – 2-Pos Close Off
Normally Closed – Modulating
Normally Open – Modulating
Fail in Place – Modulating
Normally Closed – Proportional
Normally Open – Proportional
Fail in Place – Proportional -
COIL 2:
3-Row Cold Water
4-Row Cold Water
6-Row Cold Water
3-Row DX, Single Circuit
4-Row DX, Single Circuit
6-Row DX, Single Circuit
1-Row Hot Water
2-Row Hot Water
1-Row Steam
2-Row Steam -
COIL 2 FPI:
8 FPI
10 FPI
12 FPI
14 FPI -
COIL 2 AUTO AIR VENT:
Manual
Auto Air Vent -
COIL 2 CASING:
Galvanized Casing
Stainless Steel Casing -
COIL 2 TUBE WALL:
0.016”
0.025” -
COIL 2 REFRIGERANT TYPE:
R-410 -
COIL 2 DISTRIBUTOR:
(See Krueger’s selection software) -
COIL 2 PIPING SIZE:
1/2”, 3/4”, 1”, 1-1/4”, 1-1/2” -
COIL 2 PIPING VALVE:
2-Way Control Valve
3-Way Control Valve
3-Way with Balance ByPass Valve -
COIL 2 PIPING PACKAGE:
Manual Ball Valve w/ Memory Stop
Manual Ball Valve w/ Memory Stop, Fixed Flow Ctrl
Ball Valve in Bypass & Ball Valves w/ Memory Stop -
COIL 2 FIXED GPM:
1/2” = 0.5 to 4.0 GPM in 0.5 GPM increments > 4.0 to 9.0 GPM in 1.0 GPM increments
3/4” = 4.0 to 15.0 GPM in 1.0 GPM increments
1” = 11.0 to 22.0 GPM in 1.0 GPM increments
1-1/4” = 18.0 to 29.0 GPM in 1.0 GPM increments
1-1/2” = 26.0 to 45.0 GPM in 1.0 GPM increments -
COIL 2 UNIONS:
Union -
COIL 2 P/T PORTS:
P/T Port -
COIL 2 AQUASTAT BLEED LINE:
Aquastat Bleed Line -
COIL 2 Y-STRAINER:
Y-Strainer
Y-Strainer with Blowdown -
COIL 2 ACTUATOR TYPE:
Field Provided by Others 2-Position Close-Off
Factory Provided 2-Position Close-Off, NC
MV, 2-Way, Floating Point, Fail-In-Place, 24V
MV, 3-Way, Floating Point, Fail-In-Place, 24V
HP Close-Off Actuator, 2-Way Valve-24/115/208V
HP Close-Off Actuator, 2-Way Valve-230/277V -
COIL 2 ACTUATOR POSITION:
Normally Closed – 2-Pos Close Off
Normally Open – 2-Pos Close Off
Normally Closed – Modulating
Normally Open – Modulating
Fail in Place – Modulating
Normally Closed – Proportional
Normally Open – Proportional
Fail in Place – Proportional -
ELECTRIC HEAT CASING:
Blow Through Uninsulated
Blow Through Double Wall -
ELECTRIC HEAT VOLTAGE:
(See Krueger’s selection software.) -
ELECTRIC HEAT KW:
(See Krueger’s selection software.) -
ELECTRIC HEAT HAND:
Lef t-hand
Right-hand -
MAGNETIC CONTACTOR:
Magnetic Contactor -
FUSING PER STEP:
Fusing per Step -
DOOR DISCONNECT:
Door Interlocking Fused Disconnect
Door Interlocking Non-Fused Disconnect -
MAIN FUSING:
Main Fusing -
DRAIN PAN:
IAQ Galvanized Drain Pan
IAQ Stainless Steel Drain Pan -
SECONDARY DRAIN CONNECTION:
None
Drain Connection -
DRAIN PAN HANDING:
Right Hand
Left Hand -
DRAIN PAN FLOAT SWITCH
None
Drain Pan float Switch -
FILTER:
2” Throwaway
2” 30% Pleated (Merv 8)
2” 30% Pleated (Merv 8), 4” 65% Pleated (MERV 11)
2” 30% Pleated (Merv 8), 4” 85% Pleated (MERV 14)
2” 30% Pleated (Merv 8), 4” 95% Pleated (MERV 15) -
SPARE FILTER:
2” Throwaway Spare Filter
2” 30% Pleated Spare (Merv 8)
4” 65% Pleated Spare (MERV 11)
4” 85% Pleated Spare (MERV 14)
4” 95% Pleated Spare (MERV 15) -
BASE RAILS:
Base Rails -
INSULATION TYPE:
Standard Fiberglass
Foil Faced Fiberglass
Closed Cell Foam
Double Wall -
ACCESS DOOR:
Standard
Hinged Doors with Lift and Turn Fasteners -
VIBRATION:
Rubber in Shear
Spring -
AQUASTAT
Aquastat -
THERMOSTAT:
D- Series Digital (No 7 Day program), On/Off Actuator
P- Series Digital (7 day Program), On/Off Actuator
N- Series Digital (Networking Compatible), On/Off Actuator
F- Series Digital (Networking Compatible), Floating Point Actuator
V- Series Digital (Networking Compatible), Proportional Actuator -
THERMOSTAT LOCATION:
Remote Mounted Thermostat
Unit Mounted Thermostat
F2-94
© Copyright Krueger 2021